Notifier AIM-200 User manual

12 Clintonville Road
Northford, CT 06472
Phone: 203-484-7161
Fax: 203-484-7118
EE
EE
E
AIM-200
The Addressable Intelligent Module
for the System 5000 Fire Alarm Control Panel
P/N 15949:E1 ECN 97-407
FORWARD
STEP
REVERSE
DETECTOR
ADDRESS
MODULE
Floor 1
Floor 2
Floor 3
Floor 4
Floor 5
Floor 6
Floor 7
Floor 8
Document# 15949
10/29/97 Revision:
Technical Manuals Online! - http://www.tech-man.com

2Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com

3
Document 15949 Rev. E 4/12/95 P/N 15949:E
Table of Contents
Section One: The AIM-200 ........................................................... 4
1.1: General Information ......................................... 4
SectionTwo: Inventory................................................................. 5
2.1: Optional Peripherals ........................................ 6
2.2: Addressable Modules ...................................... 7
Section Three: Installation.............................................................. 9
3.1: Installing the AIM-200...................................... 9
3.2: Wiring the Communications Circuit ................. 11
3.3: The Isolator Module ......................................... 20
3.4: The MMX-1 ...................................................... 21
3.5: The MMX-2 ...................................................... 22
3.6: The MMX-101 .................................................. 23
3.7: The CMX-2....................................................... 28
3.8: The Addressable Manual Pull Station ............. 32
3.9: The Intelligent Detector.................................... 33
3.10: Inserting the AIM-200 Cards .......................... 34
Section Four: Programming ......................................................... 35
4.1: Default Zone Map ............................................ 35
4.2: Display Status.................................................. 38
4.3: Program Edit .................................................... 40
4.4: Alarm Bus ........................................................ 41
4.5: General Alarm Service .................................... 42
4.6: Backup Alarm Bus ........................................... 43
4.7: Signal Silence Function ................................... 44
Section Five: Operation................................................................ 46
5.1: Zone Display.................................................... 46
Appendix A: Operating the Control Modules ............................ 50
Appendix B: AIM-200 Power Requirements .............................. 54
Appendix C: AIM-200 Point Annunciation ................................. 55
Technical Manuals Online! - http://www.tech-man.com

4Document 15949 Rev. E 4/12/95 P/N 15949:E
Section One: The AIM-200
1.1 General Description
Note: AIM-200 features discussed in this document are available with AIM-200 software
part number 73264 or greater.
The Addressable Intelligent Module (AIM-200) functions as an interface between the Sys-
tem 5000 Fire Alarm Control Panel and intelligent/addressable devices. To the System
5000, the AIM-200 looks like an IZM-8 Initiating Zone Module. On its single communications
loop, the AIM-200 will communicate with up to 99 addressable modules and 99 intelligent
detectors. The AIM-200 will communicate with the following:
SDX-551 Intelligent Photoelectric Smoke Detector
SDX-751 Low Profile Intelligent Photoelectric Smoke Detector
CPX-551 Intelligent Ionization Smoke Detector
CPX-751 Low Profile Intelligent Ionization Smoke Detector
FDX-551 Intelligent Thermal Sensor
MMX-1 Addressable Monitor Module
MMX-2 Addressable Monitor Module
MMX-101 Miniature Monitor Module
CMX-2 Addressable Control Module
BGX-101L Addressable Manual Pull Station
DHX-501/DHX-502 Intelligent Duct Detector Housing (for use with SDX-551 only)
The 198 devices are mapped into eight software zones by the AIM-200. The status of these
zones is reported to the CPU-5000. The AIM-200 includes a digital display for identifying
the exact device address within a zone. The display is also used to display device types and
analog detector sensitivity values.
Although the AIM-200 is intended primarily as an initiating input module, it can support
CMX-2 Control Modules on the loop. The CMX-2 modules may be mapped to AIM-200
zones much like outputs are mapped to inputs during standard System 5000 programming.
The AIM-200 may be mixed in a system with any of these system modules:
IZM-8 Initiating Zone Module
IZE-A Initiating Zone Expander
ICM-4 Indicating Circuit Module
ICE-4 Initiating Circuit Expander
CRM-4 Control Relay Module
CRE-4 Control Relay Expander
VCM-4 Voice Control Module
VCE-4 Voice Control Expander
DCM-4 Dual Channel Module
TCM-2 Time Control Module (Single hazard release)
TCM-4 Time Control Module (Multiple hazard release)
In addition, ACM remote annunciators, AMG-1 and FFT-7 voice/telephone modules, and
several power supplies can be employed with an AIM-200.
Up to ten AIM-200s may be installed in one System 5000 for a capacity of 1,980 points
(subject to limitations of system power supply, refer to Appendix B).
Technical Manuals Online! - http://www.tech-man.com

5
Document 15949 Rev. E 4/12/95 P/N 15949:E
SectionTwo: Inventory
Card File
A special card file is attached to the bottom front of the AIM-200. Several
standard 4 in. by 2-1/4 in.cards are provided and may be marked with device
information by the installer. A reference card, which defines all display codes,
is included.
The AIM-200
Addressable Intelligent Module
TheAIM-200communicates with upto99
intelligent detectors and up to 99 addres-
sable modules. The AIM-200 reports de-
vice alarm or trouble activity back to the
CPU as one of eight mapped zones.
aim200m
d
FOWARD
STEP
REVERSE
DISPLAY
STATUS
ENTER
AIMLABEL
DETECTOR
ADDRESS
MODULE
ON-LINE
SKIP
STYLE 6
LOOP FAULT
RESET
Label Inserts
Theslide-in labels areprintedwith
identification for system-defined
LEDsand switches. Spaceis pro-
vided to type in custom informa-
tion for the eight user-defined
zones.
aimcard
1
1
1
1
1
AIM-200
Addressable
Intelligent Module
1
This module moditors 8 zones of fire detedtion devices. Each
zone may consist ofmany individual detectors or other devices.
The address of the device in alarm or trouble (fault) is indicated by
the 2-digitdisplay. If multiple addresses are displayed, press the
STEP switches to control the display. Additional information about
each device is provided behind this card. This module can
measure the condition and status ofits detectors (intelligent).
Information and controls are provided behind all cards (authorized
individuals only).
Technical Manuals Online! - http://www.tech-man.com

6Document 15949 Rev. E 4/12/95 P/N 15949:E
BX-501 Base
These intelligent, addressable detectors provide analog information to
the AIM-200. The AIM-200 processes this analog information and con-
tinually makes decisions on the alarm, maintenance, or normal status of
each device. Each detector head mounts to a BX-501 base for ease of
installation or replacement. The sensitivity of each detector can be set by
the programmer at the AIM-200 for one of three levels (low, medium, and
high). Each detector responds to an address that is set in the head via
built-in rotary decimal switches.
BX-501BH Sounder built into base
B501 Flangeless base
SDX-551
An intelligent photoelectric smoke detector that provides analog mea-
surements of the optical smoke level in its chamber to the AIM-200 panel.
SDX-751
A low profile intelligent photoelectric smoke detector.
CPX-551
An intelligent ionization smoke detector that measures the level of com-
bustion products in its chamber using the ionization principle and reports
this measurement to the AIM-200.
CPX-751
A low profile intelligent ionization smoke detector.
FDX-551
An intelligent thermal sensor (135-degree F fixed temperature).
RA400Z
A remote single LED annunciator that can be wired directly off of an ad-
dressable detector for annunciation of that detector’s alarm status.
BX-501 Base
2.1 Optional Peripherals:Intelligent Detectors
Technical Manuals Online! - http://www.tech-man.com

7
Document 15949 Rev. E 4/12/95 P/N 15949:E
Control and Monitor Modules
The CMX-2 control module and the MMX-1 monitor module provide
the interface between the System 5000 and conventional initiating and
notification devices. Both types of modules respond to an address
that is set by the installer with built-in rotary decimal switches. A flash-
ing LED indicates power is applied. A thermoplastic cover (illustrated
at left) is provided with each module for mounting to a 4-inch square
mounting box.
MMX-1
An addressable monitor module that can be used to monitor conven-
tional normally open contact alarm initiating devices, such as manual
pull stations, 4-wire smoke detectors, heat detectors, waterflow, and
supervisory devices. Supervised circuit can be wired NFPA Style B
or Style D.
MMX-2
An addressable monitor module that monitors conventional 2-wire
smoke detectors. Supervised circuits can be wired NFPA Style B or
Style D. MMX-2 supervises initiating device circuit wiring, communi-
cation loop, and input power.
CMX-2
An addressable control module that can be used as a notification
appliance circuit for powering and supervising compatible, UL Listed
notification appliances. Supervised circuits can be wired NFPA Style
Y or Style Z. By breaking two built-in tabs, the CMX-2 can be em-
ployed as a Form-C control relay.
ISO-X
The loop isolator module is an automatic switch that opens the circuit
voltage to a predetermined communications loop branch(es) when-
ever a fault is detected on that circuit. The remainder of the commu-
nications loop leading up to the ISO-X will continue to operate, unaf-
fected by the fault.
MMX-101
An addressable module that is functionally identical
to an MMX-1 monitor module (Style B circuits only),
but offered in a smaller package for mounting di-
rectly in the electrical box of the device being moni-
tored.
mmx10
ADDRESS
LOOP
5
012
3
4
6
789
5
012
3
4
6
789
CAUTION
2.2 Optional Peripherals:Addressable Modules
Technical Manuals Online! - http://www.tech-man.com

8Document 15949 Rev. E 4/12/95 P/N 15949:E
BGX-101L
The addressable manual pull station features a key-lock reset. The pull
station responds to an address set by the installer with built-in rotary
decimal switches. Includes key.
System Sensor (SSD) A2143-00
The 47K end-of-line resistor assembly is used in the supervision of MMX-1 Monitor and
CMX-2 Control Module circuits. It is included with each MMX-1 or CMX-2 module.
N-ELR
The N-ELR resistor assortment is required for use in Canada. It provides
a variety of resistor values to mount to a single ELR plate (included).
Resistors can be used for the supervision of an MMX-1 monitor module
or CMX-2 control module circuit.
Resistors included:
120 ohms, 470 ohms, 1.8K, 2.2K, 4.7K, 6.8K, 10K, 27K, and 47K.
PUSH IN
THEN
PULL DOWN
FIRE
Technical Manuals Online! - http://www.tech-man.com

9
Document 15949 Rev. E 4/12/95 P/N 15949:E
SectionThree: Installation
This section outlines the installation procedure for the AIM-200. For information on install-
ing other System 5000 equipment and power limited wiring, refer to the Installation Manual,
Document 15583.
3.1 Installing the AIM-200
Complete the following steps to install the AIM-200 onto the CHS-4 Chassis.
1) Mount the AIM-200 to a CHS-4 Chassis.
2) Insert the tab on the bottom of the AIM-200 into the slot on the bottom of the CHS-4.
3) Fasten the AIM-200 to the top of the CHS-4 using the two captive screws in the top
corners of the module. Refer to Figure 3-1.
4) Connect the ribbon cable. See Figure 3-2.
Note: If point annunciation (192 intelligent AIM-200 points and 56 standard system circuits)
ofasingleAIM-200isdesired,theAIM-200mustbe mounted in the second slot of the
first chassis (directly to the right of the CPU). This annunciation option must also be
selected in system programming.
Connecting the Alarm Bus Cable
Connect the alarm bus cable following the steps below. Use the alarm bus cable (Part No.
71033) included with the AIM-200.
1) Remove the 2-pin connector on one end of the cable.
2) Separate and strip the wires, leaving about half an inch of bare wire exposed.
3) Connect wires to Terminals 14 and 15 on the CPU.
4) Connect the other end of the trouble cable to the left-most 2-pin terminal on the
bottom left-hand corner of the AIM-200. If additional AIM-200s are employed, see
Figure 3-3.
AIM-200 CHS-4 AIM-200 CHS-4
Figure 3-1: Mounting the AIM-200
Technical Manuals Online! - http://www.tech-man.com

10 Document 15949 Rev. E 4/12/95 P/N 15949:E
aim200-3
FC-2000 1st Row or
Expander Ribbon Cable
To Next
Module
From
CPU-2000
AIM-200
Figure 3-2: Connecting the Ribbon Cable
!
CAUTION: Do not connect any other device or circuit to the alarm
relay contacts on the CPU-5000 while the alarm bus cable (Part No.
71033) is installed in the system.
FC-2000 AIM-200
AIM-200
aimalrm
Alarm Bus
Cable
Part No. 71033
2 13 14 15 16 17 18 19 20
To FirstAIM-200
From
CPU-2000 To Next
AIM-200
Figure 3-3: Connecting the Alarm Bus Cable
Note: Refer to the System 5000 manual for power limited wiring requirements, document
number 15583.
From
CPU-5000
CPU-5000 1st Row or
Expander Ribbon Cable
CPU-5000
From
CPU-5000
Technical Manuals Online! - http://www.tech-man.com

11
Document 15949 Rev. E 4/12/95 P/N 15949:E
3.2 Wiring the Communications Loop Circuit
The AIM-200 communicates with intelligent and addressable initiating, monitor and control
devices through a communications loop. The System 5000 can support up to ten communi-
cations loops, each controlled by an AIM-200 module. The communications loops can be
wired as non-redundant (Figure 3-6), redundant (Figure 3-7), or isolated redundant (Figure
3-8).
Isolator Modules
Isolator modules (ISO-X) permit a zone of detectors and modules to be electrically isolated
from the remainder of the communications loop, allowing critical loop components to func-
tion in the event of a circuit fault (see Figures 3-8 and 3-12).
Monitor Modules
Addressable monitor modules (MMX-1, MMX-2, and MMX-101) allow the AIM-200 to moni-
tor entire circuits of conventional normally open contacts, alarm initiating devices, manual
pull stations, 4-wire smoke detectors, heat detectors, and waterflow and supervisory de-
vices (Figures 3-13A and 3-14A). A type of monitor module, the addressable BGX-101L,
provides point annunciation of manual pull stations (Figure 3-18).
Control Modules
Through addressable control modules (CMX-2), the System 5000 can selectively activate
notification appliance circuits or Form-C output relays (see Figures 3-15 through 3-17).
Intelligent Detectors
Through the communications loop, the AIM-200 communicates with intelligent ionization,
photoelectric, and thermal detectors (Figure 3-19).
Loop Capacity
The capacity of each AIM-200 includes up to 99 intelligent detectors and an additional
combination of up to 99 addressable pull stations, control modules, and monitor modules.
One to ten AIM-200s can be employed, depending on system requirements.
Notes:
1) Communications loop is supervised and power limited.
2) Maximum loop length is 10,000 feet (total twisted pair length).
3) Maximum loop voltage: 27.6 VDC.
4) Maximum loop current: 200 mA (short circuit) 100 mA (normal operation)
5) Maximum loop resistance: 40 ohms.
6) Refer to the proper installation drawing supplied with each communications loop ap-
pliance.
Technical Manuals Online! - http://www.tech-man.com

12 Document 15949 Rev. E 4/12/95 P/N 15949:E
Table 3-1: Communications Loop Performance
Fault Condition
Single
Open on
Loop
Single
Ground
on Loop
Loop has
Been
Shorted
Loop
Shorted
and
Opened
Loop
Shorted
and
Grounded
Loop
Opened
and
Grounded
Commun
Loss
with
Control
Panel
Non-Redundant (2-Wire) Loop Operation
Trouble
(Note 1) Trouble
with
Alarm
Capability
(Note 2)
Trouble Trouble Trouble Trouble Trouble
Redundant (4-Wire) Loop Operation
Trouble
with
Alarm
Capability
Trouble
with
Alarm
Capability
Trouble Trouble Trouble Trouble
with Alarm
Capability
Trouble
Isolated Redundant (4-Wire) Loop Operation (Note 3)
Trouble
with
Alarm
Capability
Trouble
with
Alarm
Capability
Trouble
with
Alarm
Capability
Trouble Trouble
with Alarm
Capability
Trouble
with Alarm
Capability
Trouble
Notes:
1. Trouble indicates that a trouble signal will be generated at the control
panel under the abnormal condition.
2. Alarm capability indicates whether or not an alarm signal can be trans-
mitted to the control panel during the abnormal condition.
3. Isolated redundant loop operation is a method of protecting, or isolat-
ing, entire physical zones of devices on the communications loop from
faults that occur within other areas of the loop.
Technical Manuals Online! - http://www.tech-man.com

13
Document 15949 Rev. E 4/12/95 P/N 15949:E
Branch Resistance
Short the termination point of one branch at a time and measure DC resistance from the
beginning of the loop to the end of that particular branch. The total DC resistance from
panel to branch end cannot exceed 40 ohms. Repeat this procedure for all remaining
branches.
Communications Loop Out
Branch
Figure 3-4: AIM-200Wiring Requirements Non-Redundant Circuit
+ - + -
AIM-200
Branch D
Branch B Branch E
Branch A
Loop
Out
aimwire1
For Each Loop:
Add the lengths of all the branches on one
loop. This sum cannot exceed 10,000 feet
per loop.
(Branch A)
+ (Branch B)
+ (Branch C)
+ (Branch D)
+ (Branch E)
= 10,000 feet or less
Branch C
Technical Manuals Online! - http://www.tech-man.com

14 Document 15949 Rev. E 4/12/95 P/N 15949:E
resistn3
Loop Out
Loop Return
Figure 3-5: Redundant Circuit
Total length of the communications loop pair cannot exceed 10,000 feet (measured from the
control panel out, and back to the control panel).
The DC resistance of the communications loop pair cannot exceed 40 ohms. This measure-
ment may be obtained by disconnecting loop out and return at the control panel, shorting
the two leads of communications loop return together and metering loop out.
No T-tapping is allowed
on a redundant circuit.
+ - + -
AIM-200
Loop
Out
aimwire2
Loop
Return
Technical Manuals Online! - http://www.tech-man.com

15
Document 15949 Rev. E 4/12/95 P/N 15949:E
Figure 3-6: Non-Redundant Communications Loop
Technical Manuals Online! - http://www.tech-man.com

16 Document 15949 Rev. E 4/12/95 P/N 15949:E
Figure 3-7: Redundant Communications Loop
Technical Manuals Online! - http://www.tech-man.com

17
Document 15949 Rev. E 4/12/95 P/N 15949:E
Isolated-Redundant Circuit
By flanking each communications loop device with a pair of ISO-X fault isolator modules,
each device is protected from short circuit faults that may occur on other devices. For
example, a fault on Zone 2 will not effect Zones 1 and 3. The isolator modules on either side
of Zone 2 will open the loop. Zone 1 will still operate from power on loop out and Zone 3 will
operate from loop return. Since the system will no longer be able to communicate with Zone
2, a trouble signal(s) will be generated for that device.
This circuit is a variation of the redundant circuit, therefore, no T-tapping or branching is
allowed. The ratings and characteristics are the same as for the redundant circuit.
Figure 3-8: Isolated-Redundant Communications Loop
+ - + -
AIM-200
Loop
Out
commloop3
Loop
Return
M500XJ
Isolator Module
Protected
Premises
Area "3"
Protected Premises Area "2"
M500XJ
Isolator Module
M500XJ
Isolator Module M500XJ
Isolator Module
Protected
Premises
Area "1"
ISO-X ISO-X
ISO-X ISO-X
Technical Manuals Online! - http://www.tech-man.com

18 Document 15949 Rev. E 4/12/95 P/N 15949:E
ShieldTermination in No Conduit
Do not allow the shield drain wire to enter the control panel cabinet. Connect the drain wire
to the outside of the cabinet via a BX-type connector.
( + )
( - )
Shield
Shield
FC-2000
Cabinet
Figure 3-9: ShieldTermination in No Conduit
ShieldTermination in Full Conduit
The shield drain wire must be connected to the negative (-) side of the loop. Do not allow the
shield drain wire or the shield foil to touch the control panel cabinet.
Note: For redundant or isolated redundant field wiring of the communications loop, connect
each end of the shield to the negative side of the respective channel.
( + )
( - )
Shield
Shield
FC-2000
Cabinet
The shield must not be connected to
earth ground at any point.
Figure 3-10: ShieldTermination in Full Conduit
ShieldTermination in Partial Conduit
Do not allow the shield drain wire to enter the control panel cabinet or the conduit. Connect
the drain wire to the termination point of the conduit run (such as a single-gang box as
illustrated in Figure 3-11). The conduit cannot be longer than 20 feet.
System 5000
Cabinet
System 5000
Cabinet
Technical Manuals Online! - http://www.tech-man.com

19
Document 15949 Rev. E 4/12/95 P/N 15949:E
FC-2000 Controller Enclosure Shield
2
To
AIM-200
Shield
Must employ metal conduit and
a metal box.
Figure 3-11: ShieldTermination in Partial Conduit
Do not allow the shield drain wire to enter the control panel cabinet or the conduit. Connect
the drain wire to the termination point of the conduit run (such as a single-gang box as
illustrated above).
The conduit cannot be longer than 20 feet.
System 5000
Cabinet
Technical Manuals Online! - http://www.tech-man.com

20 Document 15949 Rev. E 4/12/95 P/N 15949:E
3.3 The Isolator Module
The loop isolator module (ISO-X) is used to protect critical elements of the communications
loop from faults on other branches or sections of the loop. The ISO-X continuously monitors
the circuit connected toTerminals 3 (-) and 4 (+). Upon power up, an integral relay is latched
on. The ISO-X periodically pulses the coil of this
relay. A short circuit on the loop resets the relay.
The ISO-X sees this short and disconnects the
faulted branch by opening the positive side of the
loop(Terminal4). This effectivelyisolatesthefaulted
branch from the remainder of the loop. Once the
fault is removed, the ISO-X automatically reapplies
power to the communications loop branch. Figure
3-12 illustrates the use of an ISO-X on a
non-redundant communications loop. For employ-
ing ISO-Xs on a redundant or isolated-redundant
communications loop, see Figure 3-8.
Note: During a fault condition, the System 5000
will register a trouble condition for each zone mapped to the isolated loop branch.
Figure 3-12: Isolating Non-Redundant Communications Loops
Shorts on this branch of an isolated non-redundant communications loop will be isolated
from all devices installed both upstream of the ISO-X and on the continuation of the loop
(shown as dotted line).
commloop5
T-Tapped Branch off the Communications Loop
Continuation of the Communications Loop
Communications
Loop
M500XJ
1
2
3
4
comloop4
ISO-X
Loop In (-)
Loop In (+)
Loop Out (-)
Loop Out (+)
ISO-X
Technical Manuals Online! - http://www.tech-man.com
Table of contents
Other Notifier I/O System manuals
Popular I/O System manuals by other brands

ALLEN & HEATH
ALLEN & HEATH DT02 Getting started guide

Allen-Bradley
Allen-Bradley Flex integra 1793-IB16 installation instructions

ETAS
ETAS ES5321.1 user guide

Allen-Bradley
Allen-Bradley Compact 1769-IR6 user manual

Unitronics
Unitronics IO-ATC8 quick start guide

KonNad
KonNad C2000-A2-SMD4440-AE1 user manual

National Instruments
National Instruments roboRIO user manual

Pepperl+Fuchs
Pepperl+Fuchs PROFINET WCS-PNG210 manual

Acromag
Acromag BusWorks 900MB Series user manual

Beijer Electronics
Beijer Electronics NA-9379 Start-up

National Instruments
National Instruments 9211 CALIBRATION PROCEDURE

DATAEAGLE
DATAEAGLE Compact 2 Series Quick reference guide