
9Wait 1 minute for the boiler to stabilize before carrying out the combustion analyses. Read the CO2 value (%) and compare it with the values given in the table below:GasCO2 (%) CO(ppm)NG8.9 – 10.0<175LP9.9 – 11.0<175
Table 3 –
CO2 Max – Min
ATTENTION: The CO2 at Min Power must be set lower than the CO2 at Max Power by 0.4 – 0.8% (
e.g. if, using LP, the CO2 at Max Power = 10.3%, the CO2 at Min Power must be between 9.5 – 9.9%
).
ATTENTION!! Values must be obtained with the front cover installed.If the CO2values given in Table 3, adjust the gas valve following the instructions below. Otherwise move directly to the next operation.Figure 6 – Max PowerCO2 Adjustment
ATTENTION!! Test Function will automatically deactivate after 30 minutes. Test Function can be turned off manually by pressing the RESET button.
Wait 1 minute for the boiler to stabilize before carrying out the combustion analyses.
2. Checking/Adjusting the CO2 at Max Power
Set the thermostats at the highest possible setting to create a demand for heat. Select Max Power from the Test Mode – Burner Test screen, then wait for the Burner Power gauge to reach 100%.
3. Checking/Adjusting the CO2 at Min Power
Select Min Power from the Test Mode – Burner Test screen, then wait for the Burner Power gauge to reach 10%.
Part 3.
Checking/Adjusting the CO2 at Max and Min PowerMax Power(100%)Min Power(10%)8.5 – 9.69.5 – 10.6
Adjusting the Gas Valve at Max Power
Adjust the gas valve by turning throttle screw (4) counterclockwise to increase the CO2 level; clockwise to reduce the CO2 level. Adjust in increments of 1/16th of a turn, waiting 1 minute after each adjustment.NOTE: when switching direction between clockwise and counter-clockwise, it may take a half to a full turn before a change in CO2 is realized.
When the measured value
corresponds
to the value givenin Table 3, Max
Power adjustment is complete.
(4)