manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. NVC
  6. •
  7. Security Sensor
  8. •
  9. NVC SPARTAN 3CCT User manual

NVC SPARTAN 3CCT User manual

1
SPARTAN 3CCT SELECTABLE IP65 LED BULKHEAD INSTRUCTIONS
Issue 02 on 6th March 2021
THANK YOU for buying this product. To help ensure it gives complete satisfaction please install it according to these
instructions and then pass the instructions to the appropriate person for retention and future reference.
SAFETY This is a mains powered product. It is designed to be installed by suitably qualified personnel
only and in accordance with the applicable building and electrical regulations. Before installation or
maintenance the electrical supply to the product must be isolated.
INSTALLATION SUPPORT If installation advice or accessories are required please contact us at the
above address. We will do our best to help. When reporting a suspected fault or seeking installation support the problem
is likely to be resolved most quickly if you have full product details to-hand, as well as details of when and where it was
purchased.
INSTALLATION
1. Loosen the 3 diffuser fixing screws & remove the diffuser geartray assembly from the base by unhooking the
retention strap.
2. Prepare the mains supply cable & fixing points on the chosen mounting surface ensuring it is able to retain the
weight of the luminaire.
3. Pass the mains supply cable through the cable entry hole, offer the base to the mounting surface & secure using
the screws provided.
Note! It is the installer’s responsibility to ensure the fixing points & cable entry point are appropriately
sealed to maintain the IP rating
4. Route the mains supply cable to the terminal block on the gear tray & terminate ensuring correct polarity is
observed.
Note! This luminaire must be earthed
5. Select the required CCT by sliding the switch on the back of the gear tray to the allocated colour
6. Refit the diffuser gear tray assembly (opposite of point 1) & secure by retightening the screws.
7. Reconnect power supply & check for correct operation.
Note! Luminaires fitted with electronic drivers are exempt from insulation resistance tests as this may
cause damage to the drivers.
8. For suffix ../M3 and suffix…/MW versions see further instructions below.
BEZEL TRIMS
If this option has been selected, then install as follows:
1. Offer the bezel trim to the main luminaire aligning the lugs in the trim with the screw slots in the diffuser (3
places).
2. Push fit until it clips into position.
Note! If eyelid trim is selected then care will need to be taken to ensure slots are in the correct position when
securing the base.
MAINTENANCE
1. Cleaning should be carried out at regular intervals so as not impair photometric performance or thermal safety of
the luminaire.
2
GENERAL MAINTAINED EMERGENCY LUMINAIRE INSTRUCTIONS
(SUFFIX .../M3)
These instructions should be followed in conjunction with the standard luminaire instructions. Please read
carefully and pass to the end user/responsible person for retention and future reference.
INSTALLATION
1. Following the installation of the luminaire in accordance with the standard luminaire installation instructions, a
separate permanent live supply should be terminated in the 4-pole terminal block in the luminaire, in the
connection marked ‘L PERM’. The permanent supply MUST be taken from the same phase as the corresponding
switched supply and MUST be wired at the switchboard so that upon instances of tests, it is isolated at the same
time as the switched supply.
2. Connect the battery to the module via the ‘plug and mate’ connector, ensuring correct polarity is observed. Failure
to observe correct battery polarity will result in permanent damage to the emergency module/driver.
3. Upon restoration of the power supply to the luminaire, check that the indicator LED fitted within the luminaire
illuminates green. This indicates that the batteries are charging and that the charging circuit is healthy.
4. Allow the battery to charge for an uninterrupted period of not less than 24 hours prior to carrying out a full
discharge test.
MAINTENANCE
5. The battery pack in this luminaire must be replaced when it is no longer able to satisfy its full rated duration.
6. In emergency mode the light level of the luminaire will be at a reduced output. Regular maintenance and gentle
cleaning is recommended so as to ensure that the Emergency Output Factor (E.O.F) remains at pre-determined
levels.
7. Isolate the supply before servicing.
8. DO NOT INSULATION TEST
***************************IMPORTANT WARNING ****************************
This unit is using Lithium Ion Phosphate cells (LiFePO4) in its battery pack. These batteries
require close monitoring and protection circuitry to operate safely. The same ‘battery’ pack will
be required when exchanging battery packs in the future during maintenance.
TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedures in line with BS 5266-1:2016 & BS EN 50172:2004.
MICROWAVE SENSOR C/W DIP SWITCHES INSTRUCTIONS
(SUFFIX .../MW)
These instructions are in addition to the standard luminaire instructions that were also supplied with the product
you have purchased. They should be read carefully & luminaire installed as per both sets of instructions, then
pass on to the appropriate person for retention for future reference & maintenance.
DESCRIPTION
The micro-wave sensor option offers presence detection to provide automatic control of lighting loads. It is installed inside
the luminaire so does not affect external aesthetics or IP rating. Manual adjustments on the sensor allow it to be
individually tailored to suit your application.
3
POSITIONING
The luminaire with detector should be sited so that the occupants of the room fall inside the detection patterns shown in
the appropriate diagram below:
 The diagram is based on a ceiling mounting height.
Note that the lower the sensor is installed, the
smaller the detection range will be.
 If wall mounted, the detection zone will vary
depending on the surroundings but perpendicular
reach will be at least 10m
 The area closest to the sensor & also the area more
perpendicular to the sensor will have higher
sensitivity.
 The distances quoted are approximate & may vary
depending on surroundings
 Avoid direct sunlight entering the sensor.
 Do not site within 1m of forced air heating or
ventilation.
 Do not fix to a vibrating surface.
 Avoid metallic objects directly in front of the sensor
head.
 These sensor kits are capable of switching/controlling
more than one luminaire in a ‘master & slave’ set up.
This is done by linking non-sensored fittings (slaves)
to the one with the sensor fitted (master) using the
live output from the sensor.
Note! DO NOT link other fittings containing MW
sensors together in this way, as it can cause false
triggering of the sensors.
SETTINGS
The following adjustments can be made using the DIP switches located on the sensor unit.
DEFAULT FACTORY SETTINGS…
Sensitivity – 10m, Time – 20mins, Lux Level control disabled
LUX
Set the required Lux level by using S1, S2 & S3 DIP switches as shown
below.
TIME
Set the required time delay between 5 secs - 30 mins using S4, S5 & S6 DIP switches as shown below:
N.B. DIP switch ON (up) or -- (down)
Ceiling mounted height: 6m
Sensitivity:100%/75%
Wall mounted height: 2m
Sensitivity: 100%
4
SENSITIVITY
Set the detection range using the S7 & S8 DIP switches as shown below.
RATINGS
Power supply : 220-240VAC 50/60Hz
Rated Load : 400W (Inductive) & 800W ( Resistive)
Operating Temperature: -25°C …+60°C
FAULT FINDING
If you experiencing a problem please check through the following before making contact with NVC:
Fault - Load does not come on
 Check to see if the live supply to the circuit is good.
 If the supply & wiring are good, check the LUX setting. Increase the LUX level setting to allow the sensor to turn
on at a higher ambient light level.
Fault - Lights do not go off
 Ensure that the area is left unoccupied for longer than the selected timer setting.
 Make sure that the sensor is not adjacent to circulating air, heaters or lamps.
 If the unit “false triggers” reduce the SENSITIVITY level to narrow the area of detection.
 Ensure luminaire is not connected in parallel with other luminaires containing MW sensors

Popular Security Sensor manuals by other brands

ATS BULLSEYE user manual

ATS

ATS BULLSEYE user manual

Honeywell Friedland FGGA03 Series Quick installation guide

Honeywell

Honeywell Friedland FGGA03 Series Quick installation guide

GEZE GC 307+ quick start guide

GEZE

GEZE GC 307+ quick start guide

Radon TEVISO RA14 Application notes

Radon

Radon TEVISO RA14 Application notes

Leviton DOS02 quick start guide

Leviton

Leviton DOS02 quick start guide

DAITEM 173-21X installation manual

DAITEM

DAITEM 173-21X installation manual

Pilot Communications M1 user manual

Pilot Communications

Pilot Communications M1 user manual

RKI Instruments 35-3010RKA-01 manual

RKI Instruments

RKI Instruments 35-3010RKA-01 manual

LEGRAND 488 21 manual

LEGRAND

LEGRAND 488 21 manual

Autonics CR Series product manual

Autonics

Autonics CR Series product manual

Adixen ASM 142 operating manual

Adixen

Adixen ASM 142 operating manual

Kayoba 951-197 User instructions

Kayoba

Kayoba 951-197 User instructions

sewerin rmld operating instructions

sewerin

sewerin rmld operating instructions

Edimax EW-7317LD user manual

Edimax

Edimax EW-7317LD user manual

Videofied ITR110 installation instructions

Videofied

Videofied ITR110 installation instructions

bauhaus 6361 user manual

bauhaus

bauhaus 6361 user manual

iNels RFSF-100 quick start guide

iNels

iNels RFSF-100 quick start guide

Evikon E2228L user manual

Evikon

Evikon E2228L user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.