nVent RAYCHEM HWAT-T55 User manual

HWAT-T55
EN Operation Manual
FR Manuel d’utilisation
DE Bedienungsanleitung
CZ Návod k obsluze
PL Instrukcjaobsługi
Firmware version r0.8or higher

nVent.com/RAYCHEM
|
3
EN
FR
DE
CZ
PL
PRODUCT DESCRIPTION
The nVent RAYCHEM HWAT-T55 thermostat is
designed for nVent RAYCHEM self-regulating cables.
The thermostat is equipped with a pipe line sensor and
is capable of monitoring and controlling
nVent RAYCHEM HWAT-L, M and -R cables for hot
water temperature maintenance in small pipe networks
or branches up to 50 m. The thermostat ensures
maintenance of the desired hot water pipe temperature.
PRODUCT FEATURES
• The HWAT system is monitored and temperature
controlled with a (pipe) line sensor
• DIN-Rail mountable (35 mm)
• Manual ON/OFF
• Easy-to-read digital display for
temperature and alarm
• 3operation modes –ON/ ECO/ OFF
• 3Preset-temperatures : 55°C, 50°C, 45°C; for
an easy selection by the user,
pre-set –temperatures can be modified
• Built-in timer function for ECO mode
• Read-out of actual pipe temperature
• Monitors temperature of hot water pipe
• In the event of an alarm or (sensor) failure, the
heating system is switched off.
FUNCTIONAL DESCRIPTION
If the measured temperature drops below the control
setpoint (minus hysteresis), the control relay K1
switches the heating on. The integrated alarm relay
displays an alarm or error message in case of under
temperature, sensor break or short circuit. In case
of alarm or error, the control relay will automatically
switch off. The alarm relay can be used for external
alarm signaling.

4
|
nVent.com/RAYCHEM
EN
FR
DE
CZ
PL
INSTALLATION
Precautions!
• Electrical installation and Commissioning must
be done by authorized personnel.
• Note: Local electrical codes must be adhered to.
• Do not exceed the maximum ratings for this product.
Mounting thermostat and heating cable:
HWAT-T55 thermostat is compatible with HWAT-L, -M,
-R self regulating cable: maximum 50 m.
HWAT-T55 is intended for mounting in a subpanel
(figure B).
The thermostat must be connected to 230 VAC, and
the heating cable and earth connection need to be
connected according to the circuit diagram. Figure D. If
the current load for K1is greater than 10A, a connection
cable with 2.5mm² cross section must be used.
Sensor installation:
The NTC line sensor tip will be positioned on the
hot water pipe opposite the installed heating cable
(figure C).
Where the pipework has a “T” section and the pipe
splits in 2directions, the sensor should be installed on
the pipe with the lowest usage.
Sensor extension:
If you need to extend the sensor cable, use a shielded
cable type with one end of the shield connected to a
ground terminal near the HWAT-T55. Don‘t install the
cable in parallel to mains voltage wires. The sum of
the wire resistance may not be greater than 7,5Ohm.
After the power has been switched on, the HWAT-T55
will display the actual sensor temperature.

nVent.com/RAYCHEM
|
5
EN
FR
DE
CZ
PL
Step 1Step 2Step 3
A-ECO Mode is activated, when
blinking
B-Heating system ON
C-LED Display (Temperature and
Alarm)
D-
Increase value (change of pre-
set temperature)
E-Reduce value (change of pre-
set temperatures)
F-Programme mode selection
ON/ECO/OFF
Input hour and
press P to continue
Input minute and
press P to continue
Display shows real
temperature and
set temperature
alternating
A
B
D E F
C
P
2 Sec.
GETTING STARTED
DISPLAY INFO

6
|
nVent.com/RAYCHEM
EN
FR
DE
CZ
PL
SELECTING OPERATION MODE
Comfort
The thermostat operates continuously. The thermostat
keeps the selected maintain temperature of 55°C, 50°C
or 45°C as long as the power output of the connected
HWAT heating cable is sufficient.
Eco mode
This mode is to minimize the energy consumption
in times of few or no tap activities, mainly during the
night. The Eco Mode reduces the maintain temperature
to 50°C for a defined time duration.
Factory settings values :
• Eco mode starting time: 23:00
• Eco mode duration: 6hours
These values can be edited in the parameter settings.
The Eco Mode can be activated at any time but it is
only active if the selected maintain temperature is
>= 55°C to ensure minimum maintain temperature of
50°C. It will be indicated by a blinking red light.
Off mode
The thermostat will switch off the heating cable.

nVent.com/RAYCHEM
|
7
EN
FR
DE
CZ
PL
Parameter mode
The factory settings can be changed in the parameter
mode
Values can be changed by pressing arrow button up or down
SELECTING MAINTAIN TEMPERATURE
Maintain temperature
3pre-set temperatures to maintain the pipe temperature
are implemented in the HWAT-T55 thermostat: the 55°C
(default), 50°C and 45°C.
The pre-set temperatures can be changed in the
parameter settings .
6 sec

nVent.com/RAYCHEM
|
9
EN
FR
DE
CZ
PL
SP 2: Timer
Input hour
Input minute
Values can be changed by pressing arrow button up
or down
Values can be changed by pressing arrow button up
or down
PARAMETER SETTINGS
SP 1: Eco mode time block
Start time
Default value is 23:00
Value input for full hour
Duration
Default value: 6hours
Value input from 3up to 8hours

10
|
nVent.com/RAYCHEM
EN
FR
DE
CZ
PL
SP 3: Pre-set-temperatures
3pre-set-temperatures can be modified.
Temperature range: 40°C - 60 °C
SP 4: Sensor temperature correction
The sensor probe output readings can be corrected
from -10 K to +10 K.
Example:
The real pipe temperature, measured with external
thermometer device, is 55°C. The display of the
HWAT-T55 shows only 53°C. A sensor correction of
+2K is needed.
Values can be changed by pressing arrow button up
or down
Values can be changed by pressing arrow button up
or down

nVent.com/RAYCHEM
|
11
EN
FR
DE
CZ
PL
TROUBLE SHOOTING
Display Reasons Remedy
E01 - ALARM 1Sensor defect Sensor contacts and
sensor resistances
need to be checked; 1)
E02 - ALARM 2Pipe temperature
exceeds 66°C
Hot water supply/
storage temperature
needs to be checked
and changed to value
below 66°C; 2)
Measuring
temperature 5K
lower than
the maintain
temperature (after
reaching
one time)
Hot water supply/
storage temperature
needs to be checked
and changed to a
temperature above
maintain temperature
E03 - ERROR 3n/a
E04 - ALARM 4
Internal
temperature of
the thermostat is
too high
Verify that the ambient
temperature for the
thermostat (in the
panel) is below +40°C
and that the heating
cable circuit length
is max. 50m. If so,
replace the unit.
1)
Alarm can be eliminated by pressing P button for 6seconds
or interrupting power supply and connecting the thermostat
again. If the problem still exists, replace the unit.
2)
Alarm is activated, if the reading of the temperature
is higher than 66°C for more than 15 minutes. If the
temperature drops below 65°C, the alarm immediately
disappears.

12
|
nVent.com/RAYCHEM
EN
FR
DE
CZ
PL
TECHNICAL DATA
Technical data
Supply voltage 230 VAC, +10%/–10%, 50 Hz
Relay control heating cable potential-free (max 230 Vac
+10%), max 16A (resistive load)
Relay alarm
potential-free (max 230 Vac
+10%), switchover contact,
max 8A
Power consumption Max. 5VA
Terminal 2,5mm², screwed
Temperature setting range*
*consider local hygienic
standard
40- 60°C; default value is 55°C
Ambient temperature range
during transportation –20°C to +50°C
Switching hysteresis +/–2K
Ambient temperature-range
operation 0°C to +40°C
Accuracy +/- 1,5K including temperature
sensor
Rated impulse voltage 4.000 V
Programmable parameter Factory settings
3pre-set-temperature 40°- 60°C 55°C, 50°C,
45°C
Time clock 24 hour
display;
12:30
1min interval
Eco mode duration 3- 8hours 6(hours)
Eco mode start point 24 hour
display;
23:00
interval per
hour

nVent.com/RAYCHEM
|
13
EN
FR
DE
CZ
PL
Temperature sensor
Type Line sensor TF130 Type 202AT
+/-1% NTC 2.0K @ 25°C
Cable length 10 m ( 2–wire)
Sensor tip size Diameter 5mm, length 20 mm
Cable diameter 4mm
Exposure temperature 0°C to +70°C
Accuracy-line sensor +/–1K
Approvals
CE
RoHS & REACH
Housing
Color: Black
Housing dimensions 52,5mm x 87,5mm x 58mm
(H/W/D)
Material ABS
IP protection IP 20 ( IP 30 in panel)
Installation DIN rail mounted ; 35mm
Minimum installation
temperature 5°C
Control pollution degree 2

14
|
nVent.com/RAYCHEM
EN
FR
DE
CZ
PL
DESCRIPTION DU PRODUIT
Le thermostat nVent RAYCHEM HWAT-T55 a été conçu
pour les systèmes nVent RAYCHEM. Ce thermostat,
qui est équipé d’une sonde de contrôle, est capable
de surveiller et de réguler les rubans nVent RAYCHEM
HWAT-L, M, R pour le maintien en température de
l’eau chaude sanitaire dans les réseaux de tuyauteries
courts ou les tuyauteries de dérivation pouvant
atteindre 50m. Il assure le maintien en température
des tuyauteries d’eau chaude sanitaire.
Description fonctionnelle
Si la température courante baisse en dessous du
point de consigne de régulation (moins l’hystérésis),
le relais de régulation met le ruban chauffant en
MARCHE. Le relais d’alarme intégré (contact SPDT)
permet de transmettre les messages d’alarme ou
d’erreur signalant une sous-température, une panne de
sonde ou un court-circuit en cours. En cas d’alarme ou
d’erreur, le relais de régulation coupe continuellement
le ruban chauffant.
CARACTÉRISTIQUES DU PRODUIT
• Le système HWAT est régulé et surveillé par une
sonde de contrôle (de tuyauterie).
• Régulation de la température au moyen d’une
sonde de contrôle (de tuyauterie)
• Montage sur rail DIN (35mm)
• Fonction MARCHE/ARRÊT manuelle
• Parfaite lisibilité de l’écran d’affichage numérique
de la température et des alarmes
• 3 modes de fonctionnement: MARCHE/ÉCO/
ARRÊT
• 3 températures préréglées: 55°C, 50°C et
45°C; faciles à sélectionner pour l’utilisateur;
températures préréglées modifiables

nVent.com/RAYCHEM
|
15
EN
FR
DE
CZ
PL
• Fonction minuterie intégrée pour le mode ÉCO
• Lecture de la température réelle de la tuyauterie
• Surveille la température de la tuyauterie d’eau
chaude sanitaire.
• En cas de panne de la sonde, le chauffage est
coupé.
INSTALLATION
Précautions
• L’installation électrique et la mise en service
doivent être effectuées par du personnel autorisé.
• Veuillez prêter attention aux consignes de sécurité
locales!
• Veuillez noter les valeurs nominales maximales!
Installation de la sonde
La pointe de la sonde CTN sera positionnée sur la
tuyauterie d’eau chaude en face du ruban chauffant
installé.
Dans le cas d’une dérivation en T, il est recommandé
d’installer la sonde derrière la dérivation en T, sur le
tuyau qui est le plus éloigné du stockage d’eau chaude
sanitaire.
Le thermostat HWAT-T55 est compatible avec les
rubans chauffants HWAT-L, M et R. Les rubans
chauffants autorégulés sont caractérisés par un
courant d’appel au démarrage. Pour garantir la
durabilité du thermostat, la charge maximale des
applications autorégulées, dans les conditions
nominales, est limitée à 50m.

16
|
nVent.com/RAYCHEM
EN
FR
DE
CZ
PL
Rallonge de la sonde
Si vous devez allonger les câbles de la sonde,
utilisez un câble de type blindé dont une extrémité
est raccordée à une borne de terre à proximité du
HWAT-T55. N’installez pas le câble parallèlement
aux conducteurs de tension secteur. La somme de
la résistance des conducteurs ne doit pas dépasser
7,5Ohm. À la mise sous tension, le HWAT-T55 affiche
la température courante de la sonde.
Montage du thermostat et du ruban
chauffant
Le HWAT-T55 est prévu pour être monté dans un
sous-panneau dans un appartement ou un bâtiment.
Le thermostat doit être raccordé à un câble de 230V
c.a., le ruban chauffant et la mise à la terre doivent être
raccordés selon les schémas électriques (Figure D).
Si la charge du contacteur K1 est supérieure à 10A, un
câble de diamètre de 2.5mm² doit être utilisé.

nVent.com/RAYCHEM
|
17
EN
FR
DE
CZ
PL
Étape1Étape2Étape3
A- Le mode ÉCO est activé
B- Le chauffage marche
C- Afficheur à diodes LED
(température
et alarme)
D- Augmenter la valeur
(modification de
la température préréglée)
E- Réduire la valeur
(modification de la
température préréglée)
F- Sélection du mode de
programmation:
MARCHE/ÉCO/ARRÊT
Saisissez les
heures et appuyez
sur P pour conti-
nuer.
Saisissez les mi-
nutes et appuyez sur
P pour continuer.
L’acheur indique
par alternance
la température
réelle et le point de
consigne.
A
B
D E F
C
P
2 Sec.
MISE EN ROUTE
INFORMATIONS DE L’AFFICHEUR

18
|
nVent.com/RAYCHEM
EN
FR
DE
CZ
PL
SÉLECTION DU MODE DE
FONCTIONNEMENT
Confort
Le thermostat fonctionne de manière continue. Il
maintient la température de maintien sélectionnée
(55°C, 50°C ou 45°C) tant que la puissance de sortie
du ruban chauffant HWAT connecté est suffisante.
Mode éco
Ce mode a été développé en vue de minimiser la
consommation d’énergie en l’absence d’activité ou
pendant une période d’activité réduite du robinet,
principalement pendant la nuit. Le mode Éco diminue
la température de maintien à 50°C pendant une durée
définie.
Valeur des réglages en usine:
• Heure de début du mode Éco: 23h00.
• Durée du mode Éco: 6heures.
Vous pouvez modifier ces valeurs dans les réglages
des paramètres.
Vous pouvez activer le mode Éco à tout moment, il
ne sera cependant activé que si la température de
maintien sélectionnée est >= 55°C pour assurer une
température de maintien minimale de 50°C. Ce mode
est indiqué par un voyant clignotant rouge.
Mode arrêt
Le thermostat met le ruban chauffant hors tension.

nVent.com/RAYCHEM
|
19
EN
FR
DE
CZ
PL
Mode paramètre
Vous pouvez modifier les températures préréglées en
mode Paramètre.
Pour modifier les valeurs, appuyez sur le bouton
surmonté d’une flèche vers le haut ou vers le bas.
6 sec
SÉLECTION DE LA TEMPÉRATURE DE
MAINTIEN
Température de maintien
Les 3températures préréglées pour le maintien en
température de la tuyauterie sont implémentées sur
le thermostat HWAT-T55: les valeurs par défaut sont
55°C, 50°C et 45°C.
Vous pouvez sélectionner les températures préréglées
dans les réglages des paramètres.
Table of contents
Languages:
Other nVent RAYCHEM Thermostat manuals
Popular Thermostat manuals by other brands

MegaControls
MegaControls NT10 Series manual

Siemens
Siemens TH 192 S installation instructions

White Rodgers
White Rodgers 1F83-0471 Installation and operating instructions

Robertshaw
Robertshaw RS2110C Series Installation and user manual

Honeywell
Honeywell THP2400A1019 installation guide

thermotouch
thermotouch 4.3dC Installation & user guide

Warmup
Warmup OCC2 user manual

Honeywell
Honeywell TH3110D1008 - Digital Thermostat, 1h user manual

White Rodgers
White Rodgers 90 SERIES Installation and operating instructions

finder
finder 1T.31 installation instructions

Honeywell
Honeywell CT31 owner's manual

Watts
Watts tekmar tekmarNet 2 Quick setup guide