Oasis OASIS Ci 21 Service manual

SWIMMING POOL HEAT PUMP UNIT
Installation & Instruction Manual

CONTENTS
1. Preface
2. Specifications
2.1 Performance Data of Swimming Pool Heat Pump Unit
2.2 Dimensions for Swimming Pool Heat Pump Unit
3. Installation and Connection
3.1
3.2
3.3 How Close to Your Pool?
3.4 Swimming Pool Heat Pumps Plumbing
3.5 Swimming Pool Heat Pumps Electrical Wiring
3.6 Initial Start-up of the Unit
4. Operation and Use
4.1
4.2
4.3
4.4
5. Maintenance and Inspection
6.Appendix
Installation illustration
Swimming Pool Heat Pumps Location
Color screen wire controller interface introduction
Color screen wire controller function introduction
Parameter list and breakdown table
Interface drawin
6.2 Cable specification
6.1 Caution & Warning
6.3 Explosive view of the unit
1
2
2
4
6
6
7
7
8
9
9
10
10
11
18
20
22
23
23
24
25

CONTENTS
1. Preface
2. Specifications
2.1 Performance Data of Swimming Pool Heat Pump Unit
2.2 Dimensions for Swimming Pool Heat Pump Unit
3. Installation and Connection
3.1
3.2
3.3 How Close to Your Pool?
3.4 Swimming Pool Heat Pumps Plumbing
3.5 Swimming Pool Heat Pumps Electrical Wiring
3.6 Initial Start-up of the Unit
4. Operation and Use
4.1
4.2
4.3
4.4
5. Maintenance and Inspection
6.Appendix
Installation illustration
Swimming Pool Heat Pumps Location
Color screen wire controller interface introduction
Color screen wire controller function introduction
Parameter list and breakdown table
Interface drawin
6.2 Cable specification
6.1 Caution & Warning
6.3 Explosive view of the unit
1
2
2
4
6
6
7
7
8
9
9
10
10
11
18
20
22
23
23
24
25

2
2.SPECIFICATION
2.1 Performance data of Swimming Pool Heat Pump Unit
*** REFRIGERANT : R410A
Rated Heating: Outdoor air temp: 27 , Inlet water temp:26 /28
℃/24.3℃ ℃ ℃
UNIT
Nominal Heating Power
Input By 50Hz
Range
Nominal Running Current
Input By 50Hz
Range
Power Supply
Compressor Quantity
Compressor
Fan Quantity
Fan Power Input
Fan Rotate Speed
Fan Direction
Noise
Water Connection
Water Flow Volume
Water Pressure Drop(max)
Unit Net Dimensions(L/W/H)
Unit Ship Dimensions(L/W/H)
Net Weight
Shipping Weight
kW
Btu/h
kW
Btu/h
kW
A
W
RPM
dB(A)
mm
3
m /h
kPa
mm
mm
kg
kg
Nominal Heating Capacity
By 50Hz
Range
KW
A
OASIS Ci 10
7.1
24140
2.85~12.0
9690~40800
0.21~2.12
0.9~9.2
230V~/50Hz
1
rotary
1
100
400-800
horizontal
42-52
40
4.2
4.5
1051×410×767
1130×470×790
59
69
0.99
4.3
1. PREFACE
In order to provide our customers with quality, reliability and versatility, this product has
been made to strict production standards. This manual includes all the necessary
information about installation, debugging, discharging and maintenance. Please read this
manual carefully before you open or maintain the unit. The manufacture of this product will
not be held responsible if someone is injured or the unit is damaged, as a result of
improper installation, debugging, or unnecessary maintenance. It is vital that the
instructions within this manual are adhered to at all times. The unit must be installed by
qualified personnel.
The unit can only be repaired by qualified installer centre , personnel or an authorised
dealer.
Maintenance and operation must be carried out according to the recommended time and
frequency, as stated in this manual.
Use genuine standard spare parts only.
Failure to comply with these recommendations will invalidate the warranty.
Swimming Pool Heat Pump Unit heats the swimming pool water and keeps the temperature
constant. For split type unit, The indoor unit can be Discretely hidden or semi-hidden to
suit a luxury house.
Our heat pump has following characteristics:
1 Durable
The heat exchanger is made of PVC & Titanium tube which can withstand prolonged
exposure to swimming pool water.
2 Installation flexibility
The unit can be installed outdoors or indoors.
3 Quiet operation
The unit comprises an efficient rotary/ scroll compressor and a low-noise fan motor,
which guarantees its quiet operation.
4 Advanced controlling
The unit includes micro-computer controlling, allowing all operation parameters to be
set. Operation status can be displayed on the LCD wire controller. Remote controller can be
chosen as future option.
1
OASIS Ci 13
9.4
31960
3.8~17.0
12920~57800
0.30~3.02
1.3~13.1
230V~/50Hz
1
rotary
1
120
500-750
horizontal
44-53
40
5.3
5.0
1163×447×868
1210×510×880
77
95
1.30
5.6

2
2.SPECIFICATION
2.1 Performance data of Swimming Pool Heat Pump Unit
*** REFRIGERANT : R410A
Rated Heating: Outdoor air temp: 27 , Inlet water temp:26 /28
℃/24.3℃ ℃ ℃
UNIT
Nominal Heating Power
Input By 50Hz
Range
Nominal Running Current
Input By 50Hz
Range
Power Supply
Compressor Quantity
Compressor
Fan Quantity
Fan Power Input
Fan Rotate Speed
Fan Direction
Noise
Water Connection
Water Flow Volume
Water Pressure Drop(max)
Unit Net Dimensions(L/W/H)
Unit Ship Dimensions(L/W/H)
Net Weight
Shipping Weight
kW
Btu/h
kW
Btu/h
kW
A
W
RPM
dB(A)
mm
3
m /h
kPa
mm
mm
kg
kg
Nominal Heating Capacity
By 50Hz
Range
KW
A
OASIS Ci 10
7.1
24140
2.85~12.0
9690~40800
0.21~2.12
0.9~9.2
230V~/50Hz
1
rotary
1
100
400-800
horizontal
42-52
40
4.2
4.5
1051×410×767
1130×470×790
59
69
0.99
4.3
1. PREFACE
In order to provide our customers with quality, reliability and versatility, this product has
been made to strict production standards. This manual includes all the necessary
information about installation, debugging, discharging and maintenance. Please read this
manual carefully before you open or maintain the unit. The manufacture of this product will
not be held responsible if someone is injured or the unit is damaged, as a result of
improper installation, debugging, or unnecessary maintenance. It is vital that the
instructions within this manual are adhered to at all times. The unit must be installed by
qualified personnel.
The unit can only be repaired by qualified installer centre , personnel or an authorised
dealer.
Maintenance and operation must be carried out according to the recommended time and
frequency, as stated in this manual.
Use genuine standard spare parts only.
Failure to comply with these recommendations will invalidate the warranty.
Swimming Pool Heat Pump Unit heats the swimming pool water and keeps the temperature
constant. For split type unit, The indoor unit can be Discretely hidden or semi-hidden to
suit a luxury house.
Our heat pump has following characteristics:
1 Durable
The heat exchanger is made of PVC & Titanium tube which can withstand prolonged
exposure to swimming pool water.
2 Installation flexibility
The unit can be installed outdoors or indoors.
3 Quiet operation
The unit comprises an efficient rotary/ scroll compressor and a low-noise fan motor,
which guarantees its quiet operation.
4 Advanced controlling
The unit includes micro-computer controlling, allowing all operation parameters to be
set. Operation status can be displayed on the LCD wire controller. Remote controller can be
chosen as future option.
1
OASIS Ci 13
9.4
31960
3.8~17.0
12920~57800
0.30~3.02
1.3~13.1
230V~/50Hz
1
rotary
1
120
500-750
horizontal
44-53
40
5.3
5.0
1163×447×868
1210×510×880
77
95
1.30
5.6

2.2 The dimensions for Swimming Pool Heat Pump Unit
OASIS Ci 10
unit:mm
unit:mm
Water inlet
Φ40
Water outlet
Φ40
350
100
1051
767
435
630
410
396
447
430
868
1163
470 815
Water inlet
Φ40
Water outlet
Φ40
A
100
2.SPECIFICATION
4
OASIS Ci 13
Model
A
OASIS Ci 17
400 470
3
2.SPECIFICATION
2.1 Performance data of Swimming Pool Heat Pump Unit
*** REFRIGERANT : R410A
Rated Heating: Outdoor air temp: 27 , Inlet water temp:26 /28
℃/24.3℃ ℃ ℃
UNIT
Nominal Heating Power
Input By 50Hz
Range
Nominal Running Current
Input By 50Hz
Range
Power Supply
Compressor Quantity
Compressor
Fan Quantity
Fan Power Input
Fan Rotate Speed
Fan Direction
Noise
Water Connection
Water Flow Volume
Water Pressure Drop(max)
Unit Net Dimensions(L/W/H)
Unit Ship Dimensions(L/W/H)
Net Weight
Shipping Weight
kW
Btu/h
kW
Btu/h
kW
A
W
RPM
dB(A)
mm
3
m /h
kPa
mm
mm
kg
kg
Nominal Heating Capacity
By 50Hz
Range
KW
A
OASIS Ci 17
11.5
39100
4.6~19.5
15640~66300
0.37~3.94
1.6~17.1
230V~/50Hz
1
rotary
1
120
500-900
horizontal
45-56
40
6.6
6
1163×447×868
1210×510×880
82
95
1.72
7.5
OASIS Ci 21
14.3
48620
5.7~24.2
19380~82280
0.46~4.8
2.0~20.9
230V~/50Hz
1
rotary
2
200
400-800
horizontal
46-57
40
8.6
11
1163×470×1275
1210×495×1300
110
125
2.1
9.1
OASIS Ci 25T
17.2
58480
6.7~28.3
22780~96220
0.54~5.57
1.34~9.18
380V/3N~/50Hz
1
rotary
2
200
400-800
horizontal
48-58
40
10
15
1163×470×1275
1210×495×1300
113
131
2.5
4.48

2.2 The dimensions for Swimming Pool Heat Pump Unit
OASIS Ci 10
unit:mm
unit:mm
Water inlet
Φ40
Water outlet
Φ40
350
100
1051
767
435
630
410
396
447
430
868
1163
470 815
Water inlet
Φ40
Water outlet
Φ40
A
100
2.SPECIFICATION
4
OASIS Ci 13
Model
A
OASIS Ci 17
400 470
3
2.SPECIFICATION
2.1 Performance data of Swimming Pool Heat Pump Unit
*** REFRIGERANT : R410A
Rated Heating: Outdoor air temp: 27 , Inlet water temp:26 /28
℃/24.3℃ ℃ ℃
UNIT
Nominal Heating Power
Input By 50Hz
Range
Nominal Running Current
Input By 50Hz
Range
Power Supply
Compressor Quantity
Compressor
Fan Quantity
Fan Power Input
Fan Rotate Speed
Fan Direction
Noise
Water Connection
Water Flow Volume
Water Pressure Drop(max)
Unit Net Dimensions(L/W/H)
Unit Ship Dimensions(L/W/H)
Net Weight
Shipping Weight
kW
Btu/h
kW
Btu/h
kW
A
W
RPM
dB(A)
mm
3
m /h
kPa
mm
mm
kg
kg
Nominal Heating Capacity
By 50Hz
Range
KW
A
OASIS Ci 17
11.5
39100
4.6~19.5
15640~66300
0.37~3.94
1.6~17.1
230V~/50Hz
1
rotary
1
120
500-900
horizontal
45-56
40
6.6
6
1163×447×868
1210×510×880
82
95
1.72
7.5
OASIS Ci 21
14.3
48620
5.7~24.2
19380~82280
0.46~4.8
2.0~20.9
230V~/50Hz
1
rotary
2
200
400-800
horizontal
46-57
40
8.6
11
1163×470×1275
1210×495×1300
110
125
2.1
9.1
OASIS Ci 25T
17.2
58480
6.7~28.3
22780~96220
0.54~5.57
1.34~9.18
380V/3N~/50Hz
1
rotary
2
200
400-800
horizontal
48-58
40
10
15
1163×470×1275
1210×495×1300
113
131
2.5
4.48

6
Installation items:
The factory only provides the main unit and the water unit; the other items in the illustration
are necessary spare parts for the water system ,that provided by users or the installer.
3.1 Installation illustration
Attention:
Please follow these steps when using for the first time
1.Open valve and charge water.
2.Make sure that the pump and the water-in pipe have been filled with water.
3.Close the valve and start the unit.
ATTN: It is necessary that the water-in pipe is higher than the pool surface.
3.INSTALLATION AND CONNECTION
Chlorinator cell
Water outlet
Pool
Valve
Water supply
Water inlet Water pump
Sand filter
(or other type filter)
The schematic diagram is for reference only. Please check the water inlet/outlet label on the
heat pump while plumbing installation.
2.SPECIFICATION
5
2.2 The dimensions for Swimming Pool Heat Pump Unit
Water inlet
Φ40
Water outlet
Φ40
470
100
OASIS Ci 21/OASIS Ci 25
unit:mm
1163
1275
790
430
470
447

6
Installation items:
The factory only provides the main unit and the water unit; the other items in the illustration
are necessary spare parts for the water system ,that provided by users or the installer.
3.1 Installation illustration
Attention:
Please follow these steps when using for the first time
1.Open valve and charge water.
2.Make sure that the pump and the water-in pipe have been filled with water.
3.Close the valve and start the unit.
ATTN: It is necessary that the water-in pipe is higher than the pool surface.
3.INSTALLATION AND CONNECTION
Chlorinator cell
Water outlet
Pool
Valve
Water supply
Water inlet Water pump
Sand filter
(or other type filter)
The schematic diagram is for reference only. Please check the water inlet/outlet label on the
heat pump while plumbing installation.
2.SPECIFICATION
5
2.2 The dimensions for Swimming Pool Heat Pump Unit
Water inlet
Φ40
Water outlet
Φ40
470
100
OASIS Ci 21/OASIS Ci 25
unit:mm
1163
1275
790
430
470
447

3.INSTALLATION AND CONNECTION
8
3.4 Swimming Pool Heat Pumps Plumbing
Location: Connect the unit in the pool pump discharge (return) line downstream of all filter
and pool pumps, and upstream of any chlorinators, ozonators or chemical pumps.
Standard model have slip glue fittings which accept 32mm or 50 mm PVC pipe for
connection to the pool or spa filtration piping. By using a 50 NB to 40NB you can plumb 40NB
Give serious consideration to adding a quick coupler fitting at the unit inlet and outlet to allow
easy draining of unit for winterizing and to provide easier access should servicing be
required.
Condensation: Since the Heat pump cools down the air about 4 -5℃, water may condense on
the fins of the horseshoe shaped evaporator. If the relative humidity is very high, this could
be as much as several litres an hour. The water will run down the fins into the basepan and
drain out through the barbed plastic condensation drain fitting on the side of the basepan.
This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by hand
and run to a suitable drain. It is easy to mistake the condensation for a water leak inside the
unit.
NB: A quick way to verify that the water is condensation is to shut off the unit and keep the
pool pump running. If the water stops running out of the basepan, it is condensation. AN
EVEN QUICKER WAY IS to TEST THE DRAIN WATER FOR CHLORINE - if the is no chlorine
present, then it's condensation.
To pool
From pump
PVC COUPLER
RECOMMENDED(Provided)
CONDENSATION
DRAIN
BARB FTG
The Swimming Pool Heat Pumps exclusive rated flow titanium heat exchanger requires no
special plumbing arrangements except bypass(please set the flow rate according to the
nameplate). The water pressure drop is less than 10kPa at max. Flow rate. Since there is no
residual heat or flame Temperatures, The unit does not need copper heat sink piping. PVC
pipe can be run straight into the unit.
7
3.INSTALLATION AND CONNECTION
The unit will perform well in any outdoor location provided that the following three factors are
presented:
1. Fresh Air - 2. Electricity - 3. Pool filter piping
The unit may be installed virtually anywhere outdoors. For indoor pools please consult the
supplier. Unlike a gas heater, it has no draft or pilot light problem in a windy area.
DO NOT place the unit in an enclosed area with a limited air volume, where the units
discharge air will be re-circulated.
DO NOT place the unit to shrubs which can block air inlet. These locations deny the unit of a
continuous source of fresh air which reduces it efficiency and may prevent adequate heat
delivery.
3.2 Swimming Pool Heat Pumps Location
Normally, the pool heat pump is installed within 7.5 metres of the pool. The longer the
distance from the pool, the greater the heat loss from the piping. For the most part ,the piping
is buried. Therefore, the heat loss is minimal for runs of up to15 meters(15 meters to and from
the pump = 30 meters total), unless the ground is wet or the water table is high. A very rough
estimate of heat loss per 30 meters is 0.6 kW-hour,(2000BTU) for every 5 ℃ difference in
temperature between the pool water and the ground surrounding the pipe, which translates to
about 3% to 5% increase in run time.
3.3 How Close To Your Pool?
Air inlet
Air outlet
300mm
700mm
300mm
500mm
700mm

3.INSTALLATION AND CONNECTION
8
3.4 Swimming Pool Heat Pumps Plumbing
Location: Connect the unit in the pool pump discharge (return) line downstream of all filter
and pool pumps, and upstream of any chlorinators, ozonators or chemical pumps.
Standard model have slip glue fittings which accept 32mm or 50 mm PVC pipe for
connection to the pool or spa filtration piping. By using a 50 NB to 40NB you can plumb 40NB
Give serious consideration to adding a quick coupler fitting at the unit inlet and outlet to allow
easy draining of unit for winterizing and to provide easier access should servicing be
required.
Condensation: Since the Heat pump cools down the air about 4 -5℃, water may condense on
the fins of the horseshoe shaped evaporator. If the relative humidity is very high, this could
be as much as several litres an hour. The water will run down the fins into the basepan and
drain out through the barbed plastic condensation drain fitting on the side of the basepan.
This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by hand
and run to a suitable drain. It is easy to mistake the condensation for a water leak inside the
unit.
NB: A quick way to verify that the water is condensation is to shut off the unit and keep the
pool pump running. If the water stops running out of the basepan, it is condensation. AN
EVEN QUICKER WAY IS to TEST THE DRAIN WATER FOR CHLORINE - if the is no chlorine
present, then it's condensation.
To pool
From pump
PVC COUPLER
RECOMMENDED(Provided)
CONDENSATION
DRAIN
BARB FTG
The Swimming Pool Heat Pumps exclusive rated flow titanium heat exchanger requires no
special plumbing arrangements except bypass(please set the flow rate according to the
nameplate). The water pressure drop is less than 10kPa at max. Flow rate. Since there is no
residual heat or flame Temperatures, The unit does not need copper heat sink piping. PVC
pipe can be run straight into the unit.
7
3.INSTALLATION AND CONNECTION
The unit will perform well in any outdoor location provided that the following three factors are
presented:
1. Fresh Air - 2. Electricity - 3. Pool filter piping
The unit may be installed virtually anywhere outdoors. For indoor pools please consult the
supplier. Unlike a gas heater, it has no draft or pilot light problem in a windy area.
DO NOT place the unit in an enclosed area with a limited air volume, where the units
discharge air will be re-circulated.
DO NOT place the unit to shrubs which can block air inlet. These locations deny the unit of a
continuous source of fresh air which reduces it efficiency and may prevent adequate heat
delivery.
3.2 Swimming Pool Heat Pumps Location
Normally, the pool heat pump is installed within 7.5 metres of the pool. The longer the
distance from the pool, the greater the heat loss from the piping. For the most part ,the piping
is buried. Therefore, the heat loss is minimal for runs of up to15 meters(15 meters to and from
the pump = 30 meters total), unless the ground is wet or the water table is high. A very rough
estimate of heat loss per 30 meters is 0.6 kW-hour,(2000BTU) for every 5 ℃ difference in
temperature between the pool water and the ground surrounding the pipe, which translates to
about 3% to 5% increase in run time.
3.3 How Close To Your Pool?
Air inlet
Air outlet
300mm
700mm
300mm
500mm
700mm

4.OPERATION AND USE
10
3.5 Swimming Pool Heat Pumps Electrical Wiring
NOTE: Although the unit heat exchanger is electrically isolated from the rest of the unit, it
simply prevents the flow of electricity to or from the pool water. Grounding the unit is still
required to protect you against short circuits inside the unit. Bonding is also required.
3.INSTALLATION AND CONNECTION
3.6 Initial startup of the Unit
NOTE- In order for the unit to heat the pool or spa, the filter pump must be running to
circulate water through the heat exchanger.
Start up Procedure - After installation is completed, you should follow these steps:
1. Turn on your filter pump. Check for water leaks and verify flow to and from the pool.
2. Turn on the electrical power supply to the unit, then press the key ON/OFF of wire
controller, It should start in several seconds.
3. After running a few minutes make sure the air leaving the top(side) of the unit is
cooler(Between 5-10 ℃)
4. With the unit operating turn the filter pump off. The unit should also turn off automatically,
5. Allow the unit and pool pump to run 24 hours per day until desired pool water emperature is
reached. When the water-in temperature reach setting, The unit just shuts off. The unit will
now automatically restart (as long as your pool pump is running)when the pool temperature
drops more than 2℃below set temperature.
Time Delay- The unit is equipped with a 3 minute built-in solid state restart delay included to
protect control circuit components and to eliminate restart cycling and contactor chatter.
This time delay will automatically restart the unit approximately 3 minutes after each control
circuit interruption. Even a brief power interruption will activate the solid state 3 minute
restart delay and prevent the unit from starting until the 5 minute countdown is completed.
Power interruptions during the delay period will have no effect on the 3 minute countdown.
The unit has a separate molded-in junction box with a standard electrical conduit nipple
already in place. Just remove the screws and the front panel, feed your supply lines in
through the conduit nipple and wire-nut the electric supply wires to the three connections
already in the junction box (four connections if three phase). To complete electrical hookup,
connect Heat Pump by electrical conduit, UF cable or other suitable means as specified (as
permitted by local electrical authorities) to a dedicated AC power supply branch circuit
equipped with the proper circuit breaker, disconnect or time delay fuse protection.
Disconnect - A disconnect means (circuit breaker , fused or un-fused switch) should be
located within sight of and readily accessible from the unit, This is common practice on
commercial and residential air conditioners and heat pumps. It prevents remotely-energizing
unattended equipment and permits turning off power at the unit while the unit is being
serviced.
9
NO. Name
ON/OFF
Parameter
CLOCK
Fault display
LOCK
Water
Inlet Temp.
The button function
Press to start /shut off the unit
Click this button to view the unit state and the
parameter
Press to set the clock, the timer on or timer off.
When the timer was starting,the button is green
Click to turn on/off silent function and to set
timing Low speed function.
①
②
③
④
⑤
⑥
⑦
⑧
Click to view fault history
Temp. curve
Silent setting
⑨Click to lock the screen ,Input "22" to unlock
the screen by press the "lock button"
4.1 Color screen wire controller interface introduction
(1) Main interface
(2) Button Description
Click to enter mode setting and the target temp.
Setting interface
MODE
Click to view the temp. and power curve
② ③ ④ ⑤ ⑥① ⑨
⑧
⑦
Click to enter mode setting and the target temp.
Setting interface

4.OPERATION AND USE
10
3.5 Swimming Pool Heat Pumps Electrical Wiring
NOTE: Although the unit heat exchanger is electrically isolated from the rest of the unit, it
simply prevents the flow of electricity to or from the pool water. Grounding the unit is still
required to protect you against short circuits inside the unit. Bonding is also required.
3.INSTALLATION AND CONNECTION
3.6 Initial startup of the Unit
NOTE- In order for the unit to heat the pool or spa, the filter pump must be running to
circulate water through the heat exchanger.
Start up Procedure - After installation is completed, you should follow these steps:
1. Turn on your filter pump. Check for water leaks and verify flow to and from the pool.
2. Turn on the electrical power supply to the unit, then press the key ON/OFF of wire
controller, It should start in several seconds.
3. After running a few minutes make sure the air leaving the top(side) of the unit is
cooler(Between 5-10 ℃)
4. With the unit operating turn the filter pump off. The unit should also turn off automatically,
5. Allow the unit and pool pump to run 24 hours per day until desired pool water emperature is
reached. When the water-in temperature reach setting, The unit just shuts off. The unit will
now automatically restart (as long as your pool pump is running)when the pool temperature
drops more than 2℃below set temperature.
Time Delay- The unit is equipped with a 3 minute built-in solid state restart delay included to
protect control circuit components and to eliminate restart cycling and contactor chatter.
This time delay will automatically restart the unit approximately 3 minutes after each control
circuit interruption. Even a brief power interruption will activate the solid state 3 minute
restart delay and prevent the unit from starting until the 5 minute countdown is completed.
Power interruptions during the delay period will have no effect on the 3 minute countdown.
The unit has a separate molded-in junction box with a standard electrical conduit nipple
already in place. Just remove the screws and the front panel, feed your supply lines in
through the conduit nipple and wire-nut the electric supply wires to the three connections
already in the junction box (four connections if three phase). To complete electrical hookup,
connect Heat Pump by electrical conduit, UF cable or other suitable means as specified (as
permitted by local electrical authorities) to a dedicated AC power supply branch circuit
equipped with the proper circuit breaker, disconnect or time delay fuse protection.
Disconnect - A disconnect means (circuit breaker , fused or un-fused switch) should be
located within sight of and readily accessible from the unit, This is common practice on
commercial and residential air conditioners and heat pumps. It prevents remotely-energizing
unattended equipment and permits turning off power at the unit while the unit is being
serviced.
9
NO. Name
ON/OFF
Parameter
CLOCK
Fault display
LOCK
Water
Inlet Temp.
The button function
Press to start /shut off the unit
Click this button to view the unit state and the
parameter
Press to set the clock, the timer on or timer off.
When the timer was starting,the button is green
Click to turn on/off silent function and to set
timing Low speed function.
①
②
③
④
⑤
⑥
⑦
⑧
Click to view fault history
Temp. curve
Silent setting
⑨Click to lock the screen ,Input "22" to unlock
the screen by press the "lock button"
4.1 Color screen wire controller interface introduction
(1) Main interface
(2) Button Description
Click to enter mode setting and the target temp.
Setting interface
MODE
Click to view the temp. and power curve
② ③ ④ ⑤ ⑥① ⑨
⑧
⑦
Click to enter mode setting and the target temp.
Setting interface

11 12
4.OPERATION AND USE 4.OPERATION AND USE
4.2 Color screen wire controller function introduction
(2) Mode switch and target temperature Setting
Click the refrigeration mode button , automatic mode button or
heating mode button then you can select the corresponding mode.
① ②
③
Note: when the unit is designed for single automatic mode or single
thermal mode, the mode can not be switched.
(1) Booting and shutdown
In shutdown status, click then the unit will be booted ①
In booting status, click then the unit will be shut down.①
As shown in figure 1.1:
Click the temperature set button , you can set the target temperature.
④
2.2 1 Mode switch
2-2 Target temp. setting
①
④
③
②
In the main interface, click mode button or inlet water temperature setting
button, interface displays as follows:
Click the value to set time directly, the click confirm button to save the
Settings.
In the main interface, click on the clock Settings button,
interface displays as follows:
(3) Clock setting
Click on the time Settings button , interface displays as follows:
①
Note: if the input format is not correct, the wrong time will be saved by
clicking confirm button.
For example: setup time: the 30-11-2016 16:00:00, input 30 11 16 16 00 00 ,
the time change then click confirm button.
3-1The operation of time setting
① ②

11 12
4.OPERATION AND USE 4.OPERATION AND USE
4.2 Color screen wire controller function introduction
(2) Mode switch and target temperature Setting
Click the refrigeration mode button , automatic mode button or
heating mode button then you can select the corresponding mode.
① ②
③
Note: when the unit is designed for single automatic mode or single
thermal mode, the mode can not be switched.
(1) Booting and shutdown
In shutdown status, click then the unit will be booted ①
In booting status, click then the unit will be shut down.①
As shown in figure 1.1:
Click the temperature set button , you can set the target temperature.
④
2.2 1 Mode switch
2-2 Target temp. setting
①
④
③
②
In the main interface, click mode button or inlet water temperature setting
button, interface displays as follows:
Click the value to set time directly, the click confirm button to save the
Settings.
In the main interface, click on the clock Settings button,
interface displays as follows:
(3) Clock setting
Click on the time Settings button , interface displays as follows:
①
Note: if the input format is not correct, the wrong time will be saved by
clicking confirm button.
For example: setup time: the 30-11-2016 16:00:00, input 30 11 16 16 00 00 ,
the time change then click confirm button.
3-1The operation of time setting
① ②

14
13
4.OPERATION AND USE 4.OPERATION AND USE
3-2 The operation of timing setting
Click the timing set button timing setinterface.② to enter
Button function
Click this button to start or end
timing start setting function
Start: green
End: gray
Open: red
End: gray Click this button to start or end
t i m i n g end s ettin g funct ion
Button color
Timing starbtu tton
Timing on setting
Timing end button
Timing off setting Click to set end time of the timing
NO.
①
②
③
④
Click to set start time of the timing
Name
When the timer was starting,the clock button is green in the main interface
①② ③ ④
②
(4) Silent setting and silent timing setting
as follows:
Click the silent setting button ,and the interface displays
4-1 The silent button
①
Click the silent button , the unit will enter the silent mode,
and interface displays as follows:
①
Click the silent button again, to exit the silent mode.①

14
13
4.OPERATION AND USE 4.OPERATION AND USE
3-2 The operation of timing setting
Click the timing set button timing setinterface.② to enter
Button function
Click this button to start or end
timing start setting function
Start: green
End: gray
Open: red
End: gray Click this button to start or end
t i m i n g end s ettin g funct ion
Button color
Timing starbtu tton
Timing on setting
Timing end button
Timing off setting Click to set end time of the timing
NO.
①
②
③
④
Click to set start time of the timing
Name
When the timer was starting,the clock button is green in the main interface
①② ③ ④
②
(4) Silent setting and silent timing setting
as follows:
Click the silent setting button ,and the interface displays
4-1 The silent button
①
Click the silent button , the unit will enter the silent mode,
and interface displays as follows:
①
Click the silent button again, to exit the silent mode.①

16
15
4.OPERATION AND USE 4.OPERATION AND USE
4-2 Timing silent function setting
Start time and end time setting value must be among the range of
and se ttin g v alue can be prec ise to hour digit.
0:00-23:00,
For example above, click "ON"to use timing silent,
the unit will start the silent at 0:00 points and end at 4:00;
click "OFF" to unuse the timing silent, but if the unit
is in timing silent mode, it will exit silent timing immediately.
Click timing silent button , and interface displays as follows:②
Colur
Use:green
Unused:gray
Used: red
Unused:gray
Function
Click to use or unuse timing
on function
Click to use or unuse timing
off function
Click this button to set the timing
silent start time
Click this button to set the timing
silent end time
Timing silent on
Timing silent off
Timing silent start
t i m e
Timing silent end
t i m e
①
②
NO.
③
④
Name
①
③④
②
(5) History of the fault
In the main interface click fault display key, interface displays as follows:
If no failure, main interface displays static " "
After troubleshooting, if you do not check the failure record,
the main interface will display static " "; if you check the
failurerecord, the main interface will displays static " ";
Failure record is in reverse order,according to the happening time.
Press the "Clean" key,you can delete the fault record.
When fault occurs,the fault icon will flash between the " " " ",
the failure interface will record time, code, name of the fault.
Fault time
day - month - year
hour:min
The fault name
Fault code

16
15
4.OPERATION AND USE 4.OPERATION AND USE
4-2 Timing silent function setting
Start time and end time setting value must be among the range of
and se ttin g v alue can be prec ise to hour digit.
0:00-23:00,
For example above, click "ON"to use timing silent,
the unit will start the silent at 0:00 points and end at 4:00;
click "OFF" to unuse the timing silent, but if the unit
is in timing silent mode, it will exit silent timing immediately.
Click timing silent button , and interface displays as follows:②
Colur
Use:green
Unused:gray
Used: red
Unused:gray
Function
Click to use or unuse timing
on function
Click to use or unuse timing
off function
Click this button to set the timing
silent start time
Click this button to set the timing
silent end time
Timing silent on
Timing silent off
Timing silent start
t i m e
Timing silent end
t i m e
①
②
NO.
③
④
Name
①
③④
②
(5) History of the fault
In the main interface click fault display key, interface displays as follows:
If no failure, main interface displays static " "
After troubleshooting, if you do not check the failure record,
the main interface will display static " "; if you check the
failurerecord, the main interface will displays static " ";
Failure record is in reverse order,according to the happening time.
Press the "Clean" key,you can delete the fault record.
When fault occurs,the fault icon will flash between the " " " ",
the failure interface will record time, code, name of the fault.
Fault time
day - month - year
hour:min
The fault name
Fault code

18
17
4.OPERATION AND USE 4.OPERATION AND USE
(6) Temperature curve
In the main interface, click the curve display button,
interface displays as follows:
6-2 The average power curve
2.6.1 Temperature recording curve is as follows:
Temperature curve automatically updates every one hour,
and the curve record can be stored for 60 days;
Start from the latest curve saved time, if power is off and
curve datacollecting time is less than one hour,the data
in this period will not be saved;
4.3 Parameter list and breakdown table
(1) Electronic control fault table
Low temperature protection
Can be judged according to the remote controller failure code and
troubleshooting
Protect/fault
Standby
Normal boot
Amibent Temp. Sensor Fault
Outlet Temp. Sensor Fault
Coil Temp. Sensor Fault
Secondary A nti-freezing P rot.
Anti-freezing Prot
Suction Temp. Sensor Fault
Low Pressure Prot.
Flow Switch Prot.
Inlet and outlet temp. too big
Discharge Temp. Sensor
Fault
High Pressure Prot.
Exhaust Air over Temp Prot.
Comp. Overcurrent Prot.
Communication Fault
Primary Anti-freezing Prot.
Fault
display
Non
Non
P01
P02
P04
P05
P07
E02
E07
E03
E29
E06
P081
Non
E051
E08
E19
E01
P082
Reason Elimination methods
Antifreeze Temp. Sensor Fault
Waterway Anti-freezing Prot.
EC fan feedback Fault
P09
E05
F051
Check the wire connection between
remote wire controller and main board
Check whether the system of the compressor
running normally
Check whether the system of the compressor
running normally
Check the pipe water flow and whether
water system is jammed or not
Check the pipe water flow and whether
water system is jammed or not
Check the pipe water flow and water pump
Check or change the temp. Sensor
Check or change the temp. Sensor
Check or change the temp. Sensor
Check or change the temp. Sensor
Check or change the temp. Sensor
Check the pressure switch and cold circuit
Check or change the temp. Sensor
Check the pressure switch and cold circuit
check and replace this temp sensor
Check whether fan motor is broken or locked
or not
Inlet Temp. Sensor Fault
PP
Pressure sensor Fault
The temp. Sensor is broken
or short circuit
The temp. Sensor is broken
or short circuit
The temp. Sensor is broken
or short circuit
The temp. Sensor is broken
or short circuit
The environment temp. is low
The ambient temp. Is low
Water flow is not enough
and low differential pressure
Water flow is not enough
The temp. Sensor is broken
or short circuit
Low pressure1 protection
No water/little water in
water system
The temp. Sensor is broken
or short circuit
The high-preesure switch is
broken
The compressor is overload
The ambient temp. Is low
Communicat ion failure between
wire controller and mainboard
The compressor is overload
antifreeze temp sensor is
broken or short circuited
water temp.or ambient temp.
is too low
There is something wrong with fan
motor and fan motor stops running
The pressure Sensor is broken
F031
Fan Motor1 Fault
1. Motor is in locked-rotor state
2.The wire connection between
DC-fan motor module and fan
motor is in bad contact
1.Change a new fan motor
2.Check the wire connection and make sure
they are in good contact
Check or change the pressure Sensor
or pressure
This manual suits for next models
4
Table of contents
Other Oasis Heat Pump manuals