8
3OPERATION
Ensure that the NMEA2000® network cable is securely attached and that the Device Instance
rotary switches have been set to a valid and unique Device Instance on the network. The
switches are marked with a Hexadecimal notation, so each switch has 16 possible positions. The
combination of the two switches can be set from “00” being Device Instance 0 through to “FC”
being the equivalent of decimal 252 being the highest valid Device Instance address.
Attach 12 or 24 Volt LED Navigation Light power feeds to the Primary and Secondary power
connection block taking care to get the polarity correct. A local green LED will light for each
power feed that is connected.
Connect the LED navigation lights to the terminal blocks taking care to get the polarity correct.
Each output circuit has a 750mA resettable fuse included for protection.
The unit is controlled by issuing PGN 127502 Switch Bank Control messages with the rst byte
of the message matching the Device Instance value. Switch 1 control eld controls channel 0 on
the Controller through to Switch 8 control eld controlling channel 7 on the controller. Switch 9
through Switch 16 control eld operate the next eight channels on an Expansion unit and Switch
17 through 24 operate the next eight channels on the second expansion unit. Switch 25 through
28 control elds do not operate and channel switches.
The unit will transmit PGN 127501 Binary Status Report PGN every 2.5 seconds to advise
navigation LED status including any error conditions. This Binary Status Report PGN rst byte
will contain the Device Instance as set on the rotary switches followed by the status of each
navigation light channel shown as pairs of bits in subsequent bytes with values as follows:
The unit will also transmit a proprietary PGN 131009 upon receipt of an ISO Command PGN
60928 or a Complex Command PGN 126208 requesting PGN131009. This PGN contains detailed
status information, current calibration values and LED total power on hours for each channel.
PGN131009 Contains the following data structure:
Byte 6 = Channel 0 Status
Byte 7 and 8 = Channel 0 LSB and MSB LED Power On Hours
Byte 9 and 10 = Channel 0 LSB and MSB Channel milliwatts
Byte 11 and 12 = Channel 0 LSB and MSB Calibration milliwatts
These are repeated for channels 1 to 23.
Status byte Bit 0 = LED on, Bit 1 = fault, Bit 5 = calibrated, Bit 6 = watts <85% or >115% of
calibration and Bit 7 = LED Hours over 50,000
Dibit Value Meaning
00 Channel set OFF
01 Channel set ON
10 Channel Error (See LED status lamp on Controller)
11 Channel Error (See LED status lamp on Controller)