OEG DD3 User manual

DD3
ENG User manual
DEU Bedienungsanleitung
ITA Manuale dell'utente
FRA Mode d'emploi
DUT Gebruikershandleiding


English
3
1 - Illuminated display.
2 - Button for increasing a setting or moving forwards.
3 - Button for reviewing data and entering settings.
4 - Light sensor.
5 - Button for turning on/o room heating.
6 - Button for reducing the setting or moving backwards.
7 - Button for turning on/o the Party function.
8 - Button for turning on/o the Eco function.
9 - Button for turning on/o the function for single heating of
domestic hot water and for turning on/o heating of domestic hot
water.
DD3 DESIGN
ENGLISH
1
2
3
5
4
6
7
8
9

4 English
event display symbols
ROOM UNIT DISPLAY
display of measured and set tempera-
tures and other information
display of time, day of the week and
state of time programmes
operating mode display
DESCRIPTIONS OF SYMBOLS ON SCREEN
Event display symbols
Symbol Description
Warning.
If an error occurs in the heating controller, the room unit will
beep twice, and the symbol will ash. The symbol will stop
ashing as soon as the error has been removed. The symbol
disappears as soon as the error has been read.
Indicates whether the safety function of the controller is on.
If a protective function occurs on the controller, the room unit
will beep once, and the symbol will start ashing. The symbol
will stop ashing as soon as the error has been removed. The
symbol disappears as soon as the error has been read.
Notication about the heat tank.
If accumulator temperature does not meet the heating needs,
the room unit make two short beeps, and the symbol starts a-
shing. If the accumulator temperature falls below the minimum
temperature, the room unit make three short beeps, and the
symbol will light up.

English
5
Log or wood chip boiler notication.
If the boiler temperature does not meet the heating needs, the
room unit will make two short beeps, and the symbol will start
ashing. If the boiler temperature falls below the minimum
temperature, the room unit will make three short beeps, and
the symbol will light up.
Information about the pellet store.
If the pellet storage room is nearly empty or empty, the room
unit will make three short beeps, and the symbol will start
ashing.
Key lock.
Manual intervention in controller operation.
Menu for data and settings.
Manual switch-o of liquid fuel boiler.
Room unit address (1-rst or 2-second).
Sound signalling of warnings and notications will be repe-
ated at 20:00 if warnings or notications are still present.
Parameters P1.8 and P1.9 dene which events will be
displayed visually and which by sound.

6 English
Symbols for displaying measured and set temperatures and other
information
Symbol Description
and Measured room temperature.
and Measured outdoor temperature.
and Measured domestic hot water temperature.
Measured relative air humidity in the room.
and Set temperature.
and Set night temperature.
and Set domestic hot water temperature.
and Set temperature for frost protection.
Weather forecast - sunny.
Weather forecast - overcast.
Weather forecast - cloudy.
Weather forecast - rainfall.

English
7
Symbols for displaying the week day and time
Symbol Description
MO - Monday,
TU - Tuesday,
WE - Wednesday,
TH - Thursday,
FR - Friday,
SA - Saturday,
SU - Sunday.
Operation according to program interval - day temperature. *
Operation according to program interval - night temperature. *
Heating up of domestic water according to program interval -
switch-on
interval.
Heating up of domestic water according to program interval -
switch-o
interval.
Time of end of function Party or Eco.
* The number next to the symbol indicates whether the rst or the second heating
circuit are operating.
Symbols for operation mode indication
Symbol Description
Room heating.
Room cooling.
Continuous room heating to the set day temperature.
Continuous room heating to the set night temperature.
Continuous room cooling to the set day temperature.
Continuous room cooling to the set night temperature.
Automatic heating shut-down - summer heating mode.
Party function active.
Eco function active.
Vacation function active.
Heating of consumption water.

8 English
INFO - OVERVIEW OF INFORMATION
The room unit can display information on temperature, micro-climate
and others. Just press the key.
Use the parameters P1.10 to P1.17 to determine the amount
and selection of information for browsing. With parameter
P1.18, you can set that the basic display automatically indica-
tes the selected number of other information you chose to be
displayed in addition to the measured room temperature.
The information indication will change every three seconds.
Continuous switch-on of consumption water heating
Consumption water heated once.
Anti-legionella protection active.
Room heatingis switched o. Frost protection activated.
Symbols for operation mode indication
- Room heating
- Room cooling
- Domestic water heating
- Heating or cooling of rooms o
OPERATION MODE SELECTION
By pressing the key for 2 seconds the room heating is turned on and
o. By pressing the key for 2 seconds the heating of the domestic
water is turned on or o
By pressing the key for 20 seconds the mode will change between
heating and cooling.

English
9
SETTING THE SET DAY AND NIGHT TEMPERATURE, AND
SET DOMESTIC HOT WATER TEMPERATURE
Pressing the key or activates the settings of the set temperature.
The currently active set temperature is displayed.
Keys and change the set temperature. The value ashes whilst
the temperature is being set. For setting other temperatures move by
pressing the key . We can set the day and night temperature, and the
desired domestic hot water temperature. The icon next to the temperatu-
re set desired temperature we are setting.
Press the key again to return to the basic display.
Temperature symbol
- day temperature
- night temperature
- Domestic water temperature
The day and night temperature, as well as the domestic hot
water temperature can only be set when the heating is on
and the functions Party, Eco and Vacation are not active.

10 English
SETTING THE TEMPERATURE FOR FROST PROTECTION
Frost protection can only be active, when the boiler and the
heat generator are turned on!
The frost protection temperature can only be set when the
heating is o and the functions Party, Eco and Vacation are
not active.
We can also change the setting for the room temperature which is con-
sidered when the heating is o.
The heating must be o to press the key or and indicate the set
temperature.
Press the key or iand hold it for at least 2 seconds,
the setting value will begin to ash. Now you can change it by pressing
the keys and .
Press the key to conrm the setting. Press the key i again to return
to the basic display.
PARTY FUNCTION
Use Party function to turn on the heating and set the comfort tempera-
ture at any time.
Activate the function by pressing the key .
Set comfort or party temperature
Time when Party function expires
Party function display
Change the set comfort temperature by pressing and . Change
the setting while the value is ashing. By pressing the or key, you
move to time setting. Use the keys and to set the time for comfort
heatin. The value is ashing during setting. Press the key or to
return to the basic display.

English
11
ECO FUNCTION
Use the Eco function to save energy and set the temperature to a lower
value.
The function can be activated by pressing ECO.
The set Eco temperature can be changed with keys and . Change
the setting while the value is ashing. Press the ECO key, to change to
time setting. Keys and are used to set the time period for the ECO
mode. The value is ashing during setting. Press the ECO or key again
to return to the basic display.
When Eco function is on, the settings can be checked or changed by
pressing keys or .
The Eco function can be turned o before the set time is over by pres-
sing ECO key again.
Set Eco temperature
Time when Eco function expires
Eco function display
When the Party function is on, the settings can be changed by pressing
key or .
The party function can be turned o before before the set time by pres-
sing again the key again.

12 English
HOLIDAY FUNCTION
Use the holiday function to save energy whilst you are away. Set the
temperature you want it to be and the time when you want the heating
to go up again.
The function can be activated by pressing the ECO key for 10 seconds.
Set the holiday temperature with keys and . Change the setting
while the value is ashing. Press the ECO or key, to set the date for
when you return from your holidays. Use keys and to set date
until when vacation heating should operate. The value is ashing during
setting Press of the ECO or key to return to the basic display.
When the holiday function is on, the settings can be changed by pres-
sing the keys or .
The holiday function can be turned o before the set date by pressing
the ECO key for 10 seconds.
Set holiday temperature
Date when holiday function expires
Holiday function display

English
13
ONE-TIME DOMESTIC WATER HEATING FUNCTION
With this function the domestic water can be heated up at any time. The
function is automatically turned o when domestic water has reached
the set temperature or latest after one hour.
The function can be activated by pressing the key .
Set domestic water temperature
Display for one-time domestic water
heating function
The temperature set for domestic water can be changed by pressing
the keys and . Change the setting while the value is ashing. By
pressing the key again, you return to the basic display.
The one-time domestic water function can be turned o before expirati-
on by pressing .
FIREPLACE FUNCTION
The replace function ensures that the actual room temperature does
not eect the heating control. This function is to be used when the re-
place is on. This prevents the system from reducing the temperature in
other rooms due to increase of temperature in the living room.
The function can be activated by pressing the key for 10 seconds.
Operation of the replace function is indicated by the ashing symbol .
The replace function is active for the time set under parameter S1.13.
After expiration of the set time, it will remain being active until until the
measured room temperature is higher than the set room temperature.

14 English
ADDITIONAL AND SERVICE SETTINGS
All additional settings can be accessed through the menu. Data and
parameters are located in ve groups in the menu:
t1 - measured and set temperatures,
d1 - data on room unit and heating controller,
P1 - user settings (parameters),
P2 - user settings (parameters)
S1 - service settings (parameters).
Press the key for 2 seconds, to enter the menu. Move between groups
by using the keys and .
The replace function can be turned o the set time by pressing the key
for 10 seconds.
Press the key , to activate the selected group.
Menu symbol
Information or parameter value
display for setting
Group name display and consecutive
parameter number
By pressing , any setting can be terminated at any time,
and you can return to the basic display.

English
15
Information group t1 - temperatures
No. Description
t1.1 T1 CONTROLLER SENSOR
Measured and calculated temperatures for T1 sensor are displayed alternately.
t1.2 T2 CONTROLLER SENSOR
Measured and calculated temperatures for T2 sensor are displayed alternately.
t1.3 T3 CONTROLLER SENSOR
Measured and calculated temperatures for T3 sensor are displayed alternately.
t1.4 T4 CONTROLLER SENSOR
Measured and calculated temperatures for T4 sensor are displayed alternately.
t1.5 T5 CONTROLLER SENSOR
Measured and calculated temperatures for T5 sensor are displayed alternately.
t1.6 T6 CONTROLLER SENSOR
Measured and calculated temperatures for T6 sensor are displayed alternately.
t1.7 T7 CONTROLLER SENSOR
Measured and calculated temperatures for T7 sensor are displayed alternately.
t1.8 T8 CONTROLLER SENSOR
Measured and calculated temperatures for T8 sensor are displayed alternately.
t1.9 T9 CONTROLLER SENSOR
Measured and calculated temperatures for T9 sensor are displayed alternately.
t1.10 T10 CONTROLLER SENSOR
Measured and calculated temperatures for T10 sensor are displayed alternately.
t1.11 T11 CONTROLLER SENSOR
Measured and calculated temperatures for T11 sensor are displayed alternately.
Use the and keys to change between information and parameters.
Only parameters in groups P1, P2, and S1 can be changed.
If you press , the set value will starts ashing. You can now change
the parameter value by pressing the and keys. Conrm the set
value by pressing the key.
...
By pressing , you move back one level in any setting.

16 English
d1 information group - general information
d1.1 ROOM UNIT TYPE (DD3)
d1.2 ROOM UNIT SOFTWARE VERSION
d1.3
TYPE OF CONTROLLER CONNECTED TO ROOM UNIT
KMS-D = 0 KMS-D+ = 1
KSF-D = 10 KSF-D+ = 11
WHMS = 92
d1.4 SOFTWARE VERSION OF THE CONTROLLER
d1.5 HYDRAULIC SCHEME OF THE CONTROLLER
d1.6 LIGHT SENSOR
Light measured in the room where the room unit is installed is displayed.
t1.12 T12 CONTROLLER SENSOR
Measured and calculated temperatures for T12 sensor are displayed alternately.
t1.13 THE FIRST HEATING CIRCUIT TR1
Measured and desired room temperatures of the rst heating circuit are displa-
yed alternately.
t1.14 THE SECOND HEATING CIRCUIT TR2
Measured and desired room temperatures of the second heating circuit are
displayed alternately.
t1.15 DIRECT CIRCUIT
Calculated temperature of the ow for direct circuit is displayed.
P1 parameter group - basic parameters
No. Description Range
P1.1
TEMPERATURE DISPLAY ROUND-OFF
With this setting, we can determine the value the
measured temperature display will be rounded to.
0 - 0.1 °C
1 - 0.2 °C
2 - 0.5 °C
3 - 1.0 °C
P1.2 AUTOMATIC EXIT TIME
This setting determines the time before the display
returns to basic mode.
3 ÷ 180 s (15)
P1.3 DISPLAY ILLUMINATION SHUT-OFF TIME
This setting determines the time before display
lighting is reduced or shut off.
10 ÷ 180 s (30)

English
17
P1.4
DISPLAY ILLUMINATION OPERATION MODE
This setting determines the type of operation of the
display illumination.
The following settings are available: 0 - no display
illumination.
1- The display has maximum brightness when
entering settings to the room unit. After a period
of time the display illumination is reduced to its
minimum value.
2- Same as 1, but display illumination is adapted to
the amount of light in the room.
3- Same as 2, but room unit display is completely
turned off in standby mode during night temperature
interval between 6pm and 6am.
0 ÷ 3 (2)
P1.5 MINIMUM SCREEN ILLUMINATION
This setting determines minimum display illumina-
tion.
0 ÷ 100 % (5)
P1.6 MAXIMUM SCREEN ILLUMINATION
This setting determines maximum display illumina-
tion.
0 ÷ 100 % (80)
P1.7 DISPLAY CONTRAST
This setting determines display contrast. 1 ÷ 8 (6)
P1.8
SOUND
This setting determines when sound is activated 0 - never
1 - keys
2 - keys and warnings
3 - keys, warnings,
and notications
P1.9
DISPLAYING WARNINGS AND MESSAGES
This setting determines whether warnings and
notications are displayed.
0 - no display
1 - warnings
2 - warnings and
notications
P1.10
BASIC DISPLAY
This setting determines which information will be
displayed on the basic display.
1 - room temp.
2 - auxilliary temp.
3 - d. h. w. temp.
4 - humidity
5 - air pressure
6 - auxiliary sensor
11 - T1 controller sensor
...
22 - T12 controller sensor

18 English
P1.11
FIRST DISPLAY IN THE INFO LINE
This setting determines which information will be
displayed rst in the info line.
0 - no display
1 - room temp.
2 - auxiliary temp.
3 - domestic water temp.
4 - humidity
5 - air pressure
6 - auxiliary sensor (AUX)
11 - T1 controller sensor
...
22 - T12 controller sensor
P1.12
SECOND DISPLAY IN THE INFO LINE
This setting determines which information will be
displayed second in the info line.
Setting range is identical
to parameter P1.11.
Factory setting is:
3 - domestic water
temperature
P1.13
THIRD DISPLAY IN THE INFO LINE
This setting determines which information will be
displayed third in the info line..
Setting range is identical
to parameter P1.11.
Factory setting is:
4 - humidity
P1.14
FOURTH DISPLAY IN THE INFO LINE
This setting determines which information will be
displayed fourth in the info line.
Setting range is identical
to parameter P1.11.
Factory setting is:
5 - air pressure
P1.15
FIFTH DISPLAY IN THE INFO LINE
This setting determines which information will be
displayed fth in the info line.
Setting range is identical
to parameter P1.11.
Factory setting is:
0 - no display
P1.16
SIXTH DISPLAY IN THE INFO LINE
This setting determines which information will be
displayed sixth in the info line.
Setting range is identical
to parameter P1.11.
Factory setting is:
0 - no display
P1.17
SEVENTH DISPLAY IN THE INFO LINE
This setting determines which information will be
displayed seventh in the info line.
Setting range is identical
to parameter P1.11.
Factory setting is:
0 - no display
P1.18 NUMBER OF INFORMATION ON BASIC DISPLAY
This setting determines how many lines of informati-
on will be displayed on the basic display. 1 ÷ 9 (1)

English
19
P2 parameter group - room unit address
No. Description Range
P2.1
ROOM UNIT ADDRESS
This setting determines the room unit address. It
can be 1 or 2.
During initial operation, the room unit address is set
automatically.
0 - auto setting
1 - address 1
2 - address 2
S1 parameter group - service parameters
No. Description Range
S1.2
ROOM TEMPERATURE
This setting determines the sensor used for room
temperature.
Info:
For setting 3, the average value of the installed
and auxiliary sensor is calculated for the room
temperature.
0 - none
1 - built-in sensor
2 - auxiliary sensor (AUX)
3 - built-in and additional
sensor
S1.3
CALIBRATION OF BUILT-IN TEMPERATURE
SENSOR
This setting determines the correction of the tempe-
rature measured by the built-in sensor.
-5,0 ÷ 5,0 °C (0,0)
S1.4
AUXILIARY TEMPERATURE SENSOR (AUX)
CALIBRATION
This setting determines the correction the measured
temperature measured by the auxiliary sensor.
-5,0 ÷ 5,0 °C (0,0)
S1.5 RELATIVE HUMIDITY SENSOR CALIBRATION
This setting determines the correction of the relative
humidity measured in the room.
-10 ÷ 10 % (0)
S1.6 AIR PRESSURE SENSOR CALIBRATION
This setting determines the correction of measured
air pressure.
-100 ÷ 100 mb (0)
S1.7 AIR QUALITY SENSOR CALIBRATION
This setting determines the correction of measured
air quality.
-1000 ÷ 1000 (0)
S1.8 LIGHT SENSOR CALIBRATION
This setting determines the correction of lighting
measured in the room.
0,5÷ 2 (1)

20 English
S1.9 LOCKING THE MENU
This setting limits the access to parameter groups
in the menu.
0 - no lock
1 - S1
2 - P1, P2 and S1
S1.10
LOCKING KEYS
This setting locks key functionality.
Operation of locking keys is described in the chapter
»Locking keys«.
0 - no lock
1 - operation type,
2 - same as 1 and
functions,
3 - same as 2 and desi-
red temp.,
4 - same as 3 and info
browsing and settings.
S1.11 MINIMUM SETTING OF TEMPERATURE
This setting determines the minimum possible
setting of room temperature.
4 ÷ 40 °C (6)
S1.12 MAXIMUM SETTING OF TEMPERATURE
This setting determines the maximum possible
setting of room temperature.
4 ÷ 40 °C (30)
S1.13
PERIOD OF IGNORING ROOM TEMPERATURE
Used with the »replace« function. Operation of re-
place function is described in the chapter »Fireplace
Function«
1 ÷ 12 ur (5)
S1.14 ALTITUTE FOR WEATHER FORECAST
This setting enters the altitude of the room unit. This
improves the weather forecast.
0 ÷ 1999 m (300)
LOCKING SETTINGS
By locking settings, access to individual parameter groups is disabled.
Only unlocked parameter groups are visible. Locked settings can be
temporarily unlocked by pressing the key for 10 seconds, when being
in the last unlocked setting group.
Parameter S1.9 determines the lockings:
S1.9=0 - no lock,
S1.9=1 - group S1 is locked,
S1.9=2 - groups P1, P2 and S1 are locked.