Omega RH62C-MV User manual

OMEGA
RH62C-MV
Humidity Temperature Transducer

OMEGAnetSM On-Line Service
http://www.omega.com
Internet e-mail
For immediate technical or application assistance:
USA and Canada: Mexico and Latin America:
Sales Service: 1-800-826-6342 / 1-800-TC-OMEGASM Tel: (95) 800-TC-OMEGASM
Customer Service: 1-800-622-2378 / 1-800-622-BESTSM FAX: (95) 203-359-7807
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
SM
En Español: (203) 359-7803
TELEX: 996404 EASYLINK: 62968934 CABLE: OMEGA
e-mail: [email protected]
Servicing North America:
USA: ISO 9001 Certified Canada:
One Omega Drive, Box 4047 976 Bergar
Stamford, CT 06907-0047 Laval (Quebec) H7L5A1
Tel: (203) 359-1660 Tel: (514) 856-6928
FAX: (203)359-7700 FAX: (514) 856-6886
Servicing Europe:
Benelux:
Postbus 8034, 1180 LA Amstelveen,
The Netherlands
Tel: (31) 20 6418405 FAX: (31) 20 6434643
Toll Free in Benelux: 06 0993344
e-mail: [email protected]
Czech Republic:
ul. Rude armady 1868, 733 01 Karvina-
Hranice, Czech Repubic
Tel: 420 (69) 6311627 FAX: 420 (69)
6311114
e-mail: [email protected]
France:
9, rue Denis Papin, 78190 Trappes
Tel: (33) 130-621-400 FAX: (33)130-699-120
Toll Free in France: 0800-4-06342
e-mail: [email protected]
Germany/Austria:
Daimlerstrasse 26, D-75392
Deckenpfronn, Germany
Tel: 49 (07056) 3017 FAX: 49 (07056) 8540
Toll Free in Germany: 0800 82 66342
e-mail: [email protected]
United Kingdom: ISO 9002 Certified
One Omega Drive
Riverbend Technology Centre Northbank, Irlam,
Manchester, M44 5EX, England
Tel: 44 (161) 777-6611 FAX: 44 (161) 777-6622
Toll Free in England: 0800-488-488
e-mail: [email protected]
omega.com
TM

1
INTRODUCTION
This instrument is a portable, compact-sized Humidity Temperature Trans-
ducer designed for simple one hand operation. Uses Platinum Resistance
Temperature Detector Pt385/1000W(Alpha=0.00385) as temperature sensor,
and uses thin film polymer capacitive type relative humidity sensor as hygrom-
eter sensor.
SAFETY INFORMATION
It is recommended that you read the safety and operation instructions before
using the humidity temperature transducer.
CAUTION
• Do not immerse the transducer sensor head into liquids since this
causes permanent damage to the sensor.
• The meter when not in use, please use protective metal cap cover the
sensor head and rotate clockwise it to extend sensors life.
The symbol on the instrument indicates that the operator must refer to an
explanation in this manual.

2
SPECIFICATIONS
GENERAL
Low battery indication: The "Red LED" is displayed when the battery voltage
drops below the operating level.
Accuracy: Stated accuracy at 23°C ± 5°C, <75% relative humidity.
Temperature Coefficient: 0.1 times the applicable accuracy specification per
°C from °C to 18°C and 28°C to 50°C.
Operating environment: 0°C to 50°C at <75% relative humidity.
Storage environment: -20°C to 60°C at <80% relative humidity.
Battery: 4 pcs 1.5V (AAA size).
Battery Life: 200 hours typical.
Dimensions: 170mm(H) x 44mm(W) x 40mm(D).
Weight: 200g (including probe and batteries).

3
ELECTRICAL
TEMPERATURE
Temperature Scale: Celsius.
Temperature Sensor: RTD Pt385/1000W.
Measurement Range: -20°C to 100°C.
Temperature Output: 10mV/°C.
Accuracy: ±0.5°C 0°C to 50°C
±1°C -20°C to 0°C, 50°C to 100°C
RELATIVE HUMIDITY
Humidity Sensor: Electronic capacitance polymer film sensor. (The sensor is
unaffected by water condensate, is immune to most reagent vapors)
Measurement Range: 0% to 100%RH.
Relative Humidity Output: 10mV/%RH.
Accuracy: ±2.5%RH (10% to 90%RH)
±5%RH (<10%, > 90%RH)
Sensor Response Time for 90% of Total Range: 60sec typical.
Sensor Stability: ±2%RH, 2 years typical.

4
Sensor Hysteresis (excursion of 10% to 90% to 10% RH): ±1%RH typical.
Sensor Temperature Dependence: Negligible between 0°C to 50°C.
OPERATON
1.PlugthehumiditytemperaturetransducertestleadsintotheVdcinputjackand
common or ground input jack on the DMM. Observe polarity.
2. Set the DMM to the 200mV range.
3. Rotate counter clockwise to remove the protective metal cap.
4. Set the power switch to the desired %RH or °C range.
5. If the DMM display is over-range. Set the DMM to the 2V range.
6. Read the DMM display. (10mV/°C, 10mV/%RH)
7. Cover sensor head to extend sensor life when not in use.

5
SPECIAL CONSIDERATIONS
• Before a reliable measurement can be made, the measuring hygrometer and
medium to be measured must be in temperature and humidity eguilibrium.
• Temperature measurement errors
Due to too short measurement time, sunshine during the measurement,
heating,cold outerwalls, airdraft (e.g. fans), radiating hand and/ or body heat
etc.
• Humidity measurement errors
Due to steam, water splashes, dripping water or condensation (not water
condensate) on the sensor etc. However, repeatability and long-term stability
are not impaired by this.
• Contamination
Bydustintheairormeasurementsin powderysubstances.Thiscanbelargely
avoided by using a corresponding filter. The filter must be cleaned or replaced
periodically depending upon the degree of contamination of the measuring
site.

6
OPERATOR MAINTENANCE
Battery Replacement
Power is supplied by four 1.5V (AAA size) batteries. The "LOW BATT" red LED
lightedwhen replacement is needed. To replace thebatteries, remove the screw
fromthebackofthemeterandliftoffthebatterycover.Removethebatteriesfrom
battery contacts.
Cleaning
Periodicallywipe thecase with adamp clothand detergent,do notuse abrasives
or solvents.

WARRANTY
OMEGA warrants this unit to be free of defects in materials and workmanship and to give satisfactory service for a
period of 13 months from date of purchase.OMEGAWarranty adds an additional one (1) month grace period to the
normal one (1) year product warranty to cover handling and shipping time.This ensures that OMEGA's customers
receive maximum coverage on each product. If the unit should malfunction, it must be returned to the factory for
evaluation. OMEGA's Customer Service Department will issue an Authorized Return (AR) number immediately
upon phone or written request.Upon examination by OMEGA, if the unit is found to be defective it will be repaired or
replaced at no charge.However, thisWARRANTY isVOID if the unit shows evidence of having been tampered with
or shows evidence of being damaged as a result of excessive corrosion; or current, heat moisture or vibration;
improperspecification;misapplication;misuseor other operating conditionsoutsideofOMEGA'scontrol.Components
which wear or which are damaged by misuse are not warranted.This includes contact points, fuses, and triacs.
OMEGA is glad to offer suggestions on the of use of its various products.Nevertheless, OMEGA only warrants
that the parts manufactured by it will be as specified and free of defects
OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER,
EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE AND ALL IMPLIED WARRANTIES INCLUDING ANY
WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY
DISCLAIMED.
LIMITATION OF LIABILITY:The remedies of purchaser set forth herein are exclusive and the total liability of
OMEGA with respect to this order, whether based on contract warranty, negligence, indemnification, strict
liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In
no event shall OMEGA be liable for consequential, incidental or special damages.
Every precaution for accuracy has been taken in the preparation of this manual;however, OMEGA ENGINEERING,
INC.neither assumes responsibility for any omissions or errors that mayappear nor assumes liability for any damages
that result from the use of the products in accordance with the information contained in the manual.
SPECIAL CONDITION: Should this equipment be used in or with any nuclear installation or activity, purchaser will
indemnity OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the
equipment in such a manner.

It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is
constantly pursuing certification of its products to the European New Approach Directives.OMEGA will add the CE
mark to every appropriate device upon certification.
The information contained in this document is believed to be correct but OMEGA Engineering, Inc. accepts no
liability for any errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient connected application.
RETURN REQUESTS / INQUIRIES
Directall warrantyand repairrequests/inquiriesto theOMEGA CustomerServiceDepartment.BEFORE RETURNING
ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM
OMEGA'S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned
AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in
transit.
FOR WARRANTY RETURNS, please have the following
information available BEFORE contacting OMEGA:
1. P.O. number under which the product was
PURCHASED.
2. Model and serial number of the product under
warranty, and
3. Repair instructions and/or specific problems relative
to the product.
FOR NON-WARRANTY REPAIRS, consult OMEGA for
current repair charges.Have the following information
available BEFORE contacting OMEGA:
1. P.O. number to cover the COST of the repair.
2. Model and serial number of product , and
3. Repair instructions and/or specific problems relative
to the product.
OMEGA's policy is to make running changes, not model changes, whenever an improvement is possible. This
affords our customers the latest in technology and engineering. OMEGA is a registered trademark of OMEGA
ENGINEERING, INC.© Copyright 1999 OMEGA ENGINEERING, INC. All rights reserved.This document may not
be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable from, in
whole or in part, without prior written consent of OMEGA ENGINEERING, INC.

Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA...Of Course!
HEATERS
þHeating Cable
þCartridge & Strip Heaters
þImmersion & Band Heaters
þFlexible Heaters
þLaboratory Heaters
PRESSURE/STRAIN AND FORCE
þTransducers & Strain Gauges
þLoad Cells & Pressure Gauges
þDisplacement Transducers
þInstrumentation & Accessories
FLOW/LEVEL
þRotameters, Gas Mass
Flowmeters & Flow Computers
þAir Velocity Indicators
þTurbine/Paddlewheel Systems
þTotalizers & Batch Controllers
TEMPERATURE
þ
Thermocouple, RTD & Thermistor
Probes, Connectors, Panels &
Assemblies
þWire: Thermocouple, RTD &
Thermistor
þ
Calibrators & Ice Point References
þ
Recorders, Controllers & Process
Monitors
þInfrared Pyrometers
ENVIRONMENTAL
MONITORING AND CONTROL
þ
Metering & Control Instrumentation
þRefractometers
þPumps & Tubing
þAir, Soil & Water Monitors
þIndustrial Water & Wastewater
Treatment
þpH, Conductivity & Dissolved
Oxygen Instruments
pH/CONDUCTIVITY
þpH Electrodes, Testers &
Accessories
þBenchtop/Laboratory Meters
þControllers, Calibrators,
Simulators & Pumps
þIndustrial pH & Conductivity
Equipment
DATA ACQUISITION
þData Acquisition & Engineering
Software
þCommunications-Based
Acquisition Systems
þPlug-in Cards for Apple, IBM
& Compatibles
þDatalogging Systems
þRecorders, Printers & Plotters
M-2862/0799
This manual suits for next models
1
Table of contents
Other Omega Transducer manuals
Popular Transducer manuals by other brands

Minebea
Minebea TMOFB-NM Series instruction manual

Humminbird
Humminbird MEGA 360 IMAGING Series installation guide

KYOWA
KYOWA ASH-A-10 instruction manual

Lumel
Lumel P18D User Manual & Quick Start

Honeywell
Honeywell PX2 Series installation instructions

SIAP+MICROS
SIAP+MICROS t027 TP200 User manual and maintenance