Onan LT II User manual












t>C8 ASSY-TRANSFER
SWITCH
CONTROL
CAUTIOH:
HIGH
Off
OFF VOLTAGE
30J
20
1
AETRANSFERD
11151 DSTOPPING
BYPASS AiS2 BYPASS
li
4
9 7
<:>
K9
Wl
K6
I VOLTAGE
SENSOR
1t>GENERATOA
S1DE
§
PHASE
SENSOA
RELAY
.
rg:-;
:.iiSENSOR
30
•
~m-ET~~
$ENSOR
10
K8
§TRANSFER
RELAY
• TfME DELAY TRANSFER
AANGE: 0.3
lo
30
SECONDS
ON
ENERGfZAT~OH
NORM: 2
SECONDS
"TtME
DEL.AV STOPPING
AfTER
RETRANSFEA
RANGE 3
TO
300
SECONDS
ON
~NERGIZAllON
NOAU' 300SECONDS
K5
ON ON
K7
f
INST
ANT
TRANSFER
TOUNE
"TIME
OELAY
BETRANSFER
RANGE'
21'0
301lllNUT£S
ON
ENERGIZATION
NORM:
15MINUTES
K4
00
3 1
6 4
9 7
oP11
START
RE.LAY
.
nue
DELAY
STARTING
~:
0.1
to 10SECONDS
NORM: 2 SECONDS
K3
C1
H--
FIGURE
2-4.
CONTROLLER
PCB
ASSEMBLY
NORMAL
OPERATION
During normal operation, the commercial power line is
connected to the Load terminals by the transfer switch
contacts
K1.
The
following
briefly
describes
the
required interaction
of
control componentsto closethe
K1
contacts. Refer to Figure 2-S when reviewing this
informationtogainan understandingofcontrol
compo-
nentinteraction.Then refertowiringdiagramspecificto
your
transfer switch to identify where
your
transfer
switch may differ.
When commercial
power
isfirst applied, line voltage is
transformed to 120 volts AC and supplied to voltage
sensor relay
K6.
Energizing the coil of K6 will close its
normally open contacts to complete the circuit to relay
coils
K3,
K4,
KS,
and
K7.
Relay K7 energizes imme-
diately,and ifthecommercial (Normal) linecontactsare
not
closed,the
K1
closingcoil (CC) isenergized. With
K1
closingcoilenergized,thenormallyopen contactsof
K1
between Line and Load will close.
' 2-6
Once the transfer switch is closed to the normal line
side,
it
is held in that position and the closing coil is
de-energized
by
opening of the
K1
cutout switch
(CS).
The
cutout
switch
is
activated bythe mechanical inter-
lock.Contactoperation differsonlyin
how
theyareheld
in position, eitherelectrically
or
mechanically.
Relay K6 can
be
eithera voltagesensorwithan adjusta-
ble
pickup
voltage,
or
a phase loss sensor, when the
voltage feeding the relay coil
drops
below
the relay
holding voltage.
During normal operation when K3 relay isenergized, it
opensitsnormallyclosed contacts
of
thegeneratorstart
circuit,andpreventsautomaticstartingofthegenerator
set
Relays K4 and
KS
(ifequipped) function as described in
the Restoration
of
Commercial Power section.

POWER
OUTAGE
When commercial power outage occurs,
or
voltage
drop~
lower
than
the
setting
relay
K6, K6
de-
energ1zesandopensthecircuittocontrol relays
K3,
K4,
KS,
and
K7.
De-energizing relay
K3
allowsits normally closed
con-
tactsto close and complete the circuitfor generatorset
start-up. Relay K3 can be either immediate
or
time
delayed
(0.1
to 10 seconds) depending on transfer
switch model.
Upon start-up ofthegeneratorset, voltage sensor relay
K9
will energizeandclose itsnormallyopen contactsto
transfer relay
KS
(ifequipped). Relay
KS
will then ener-
gizeand after its adjustable time delayperiod (0.3 to 30
seconds) it will close its normally open contacts to
K1
trip coil
(TC)
and
K2
closing coil
(CC)
circuits.
Because transfer switch
K1
had previously been energized closed,
the normally closed
K1
interlock contacts (IC) to K2 closing coll
wouldnow
be
open,andthenormaHyopen
K1
Interlockcontacts(IC)
to
K1
bip
coll (TC) would
be
closed.
Upon closing of
KS
time delay closed (TDC) contacts,
the
K1
trip coil (TC) would then energize to open
K1.
By
openingtransferswitch
K1,
thenormallyclosed inter-
lock
contacts
(IC)
would then close and complete the
circuit
to
energize K2 closing coil (CC). Energizing
K2
closing coil(CC) then closesitsnormallyopencontacts
to
completethetransfer
of
power,andthegeneratorset
is
connected to the load.
GENERATOR
SET
STARTING
CIRCUITS
Sending startand stop signals
to
the generator set is a
basicfunction
of
thetransferswitch.Thestartingcircuit
function
of
the
transferswitch mustbe compatible with
that
of
thegeneratorsetcontrol.Thetransferswitchwill
be either a
two-wire
or three-wire starting circuit, des-
cribed as follows:
2-7
Two-Wire Starting
In
a
two-wire
starting circuit, battery voltage
(B+)
is
connected by
K3
to the remote (RMT) terminal. When
commercial power fails
or
falls below the holding volt-
age
of
voltage sensor relay
K6,
it de-energizes. This
removes power from
K3;
and after any time delay,
K3
closes the contact between
B+
and RMT terminals to
initiate generator set starting.
Forperiodicexerciseofthegeneratorset, M2exerciser
clock
will close its normally open contacts between
B+
and RMTterminals to initiate startand run command of
thegenerator
set
Thegenerator setwill startand run at
no load for the time set by the exercise clock
M2.
Three-Wire Starting
Normally closed contacts
of
generator voltage sensor
relay
K9,
and cranking limiter relay K10 are in series in
thegeneratorsetstarting circuit. During a poweroutage
ofnormalcommercial powersupply, generatorsetstart-
ing will be initiated by de-energizing relay
K3;
the nor-
mally open contacts for stop command will open, and
the normally closed contacts for start command will
close.
When the generator voltage sensor relay
K9
detects
proper
generator
voltage,
the
contacts
open and
remove ground from relay cranking limiter coil
K10.
If
ground isnotremoved within 60seconds,
K1
Owill time
outandremovethestartsignal from thegeneratorsetby
opening its time delay to open
(TOO)
normally closed
contacts. The cranking limiter (K10) is used only with
three-wire starting systems.