POWER
OUTAGE
When commercial power outage occurs,
or
voltage
drop~
lower
than
the
setting
relay
K6, K6
de-
energ1zesandopensthecircuittocontrol relays
K3,
K4,
KS,
and
K7.
De-energizing relay
K3
allowsits normally closed
con-
tactsto close and complete the circuitfor generatorset
start-up. Relay K3 can be either immediate
or
time
delayed
(0.1
to 10 seconds) depending on transfer
switch model.
Upon start-up ofthegeneratorset, voltage sensor relay
K9
will energizeandclose itsnormallyopen contactsto
transfer relay
KS
(ifequipped). Relay
KS
will then ener-
gizeand after its adjustable time delayperiod (0.3 to 30
seconds) it will close its normally open contacts to
K1
trip coil
(TC)
and
K2
closing coil
(CC)
circuits.
Because transfer switch
K1
had previously been energized closed,
the normally closed
K1
interlock contacts (IC) to K2 closing coll
wouldnow
be
open,andthenormaHyopen
K1
Interlockcontacts(IC)
to
K1
bip
coll (TC) would
be
closed.
Upon closing of
KS
time delay closed (TDC) contacts,
the
K1
trip coil (TC) would then energize to open
K1.
By
openingtransferswitch
K1,
thenormallyclosed inter-
lock
contacts
(IC)
would then close and complete the
circuit
to
energize K2 closing coil (CC). Energizing
K2
closing coil(CC) then closesitsnormallyopencontacts
to
completethetransfer
of
power,andthegeneratorset
is
connected to the load.
GENERATOR
SET
STARTING
CIRCUITS
Sending startand stop signals
to
the generator set is a
basicfunction
of
thetransferswitch.Thestartingcircuit
function
of
the
transferswitch mustbe compatible with
that
of
thegeneratorsetcontrol.Thetransferswitchwill
be either a
two-wire
or three-wire starting circuit, des-
cribed as follows:
2-7
Two-Wire Starting
In
a
two-wire
starting circuit, battery voltage
(B+)
is
connected by
K3
to the remote (RMT) terminal. When
commercial power fails
or
falls below the holding volt-
age
of
voltage sensor relay
K6,
it de-energizes. This
removes power from
K3;
and after any time delay,
K3
closes the contact between
B+
and RMT terminals to
initiate generator set starting.
Forperiodicexerciseofthegeneratorset, M2exerciser
clock
will close its normally open contacts between
B+
and RMTterminals to initiate startand run command of
thegenerator
set
Thegenerator setwill startand run at
no load for the time set by the exercise clock
M2.
Three-Wire Starting
Normally closed contacts
of
generator voltage sensor
relay
K9,
and cranking limiter relay K10 are in series in
thegeneratorsetstarting circuit. During a poweroutage
ofnormalcommercial powersupply, generatorsetstart-
ing will be initiated by de-energizing relay
K3;
the nor-
mally open contacts for stop command will open, and
the normally closed contacts for start command will
close.
When the generator voltage sensor relay
K9
detects
proper
generator
voltage,
the
contacts
open and
remove ground from relay cranking limiter coil
K10.
If
ground isnotremoved within 60seconds,
K1
Owill time
outandremovethestartsignal from thegeneratorsetby
opening its time delay to open
(TOO)
normally closed
contacts. The cranking limiter (K10) is used only with
three-wire starting systems.