
20
D: 21 Heat sink too hot
This option can be determined at which temperature the heatsink too warm alarm is activated.
The settings in D: 21, default = 24 ℃, max = 30 ℃, min = 15 ℃.
The temperature must be too high at a certain amount of time to activate the alarm. Time
D 22 is defined by:. D 21 and D 22 together determine when error11 is active.
D: 22 Duration heat sink is too hot
With this option, you can determine how long it should take for a heatsink too Hot alarm is activated.
The settings in D: 22 standard = 30min, max = 40min, min = 20min.
The height of the temperature is determined by D: 21. D 21 and D 22 together define where E: 11
active.
D: 23 Temperature compensation room temperature sensor
With this option, the room temperature sensor can be calibrated. The setting can be changed if the
indication on the display does not match the reality.
The settings in D: 23 standard = 0 ℃, max = 5 ℃, min = -5 ℃and in set by 0.5 ℃.
D: 24 Temperature compensation heatsink temperature sensor
With this option, the heat sink temperature sensor can be calibrated. The settings in D: 24
standard = 0 ℃, max = 5 ℃, min = -5 ℃and 0.5 ℃per set.
D: 25 Temperature compensation Liquid / return temperature sensor
With this option, the temperature sensor can be calibrated.
The settings in D:24 are default = 0 ℃, max = 5 ℃, min = -5 ℃and 0.5 ℃per set.
D: 26 Temperature compensation dual roll room temperature sensor
With this option, the 2nd room temperature sensor in the dual-room configuration is calibrated.
The settings in D: 26 standard = 0 ℃, max = 5 ℃, min = -5 ℃and in set by 0.5 ℃.
D: 27 Compressor rest
In this setting, the rest period between the compressor and the compressor can be adjusted.
Setting: D 27 = 15 means the rest time is 15 seconds. This is the standard institution. The option can be
used as in the time that the compressor is at rest, the values in the space change too much.
D: 28 Not applicable
D: 29 Lighting Display.
With this option, the lighting in the display of the remote control can be powered up or disabled.
0 = Auto (default)
1 = Always on
D: 30 Fan outdoor unit on / off.
This option is determined at the Liquid / return coolant temperature the fan (s) ignite the outdoor
unit.
The default setting is 27 ° C. The setting can be changed to be from 23 ° C to 33 ° C.
D: 31 Latency fan outdoor unit
With this function, the period can be changed after the fan goes on the outdoor unit or run after the
compressor is active.
The default setting is 30 seconds. (3). The time can be changed between 0 and 90 seconds. (0 to 9).
D: 32 High outdoor temperature alarm
In the default setting, an error E: 16 given as the air surrounding the outdoor unit reaches more than
40 ° C. The setting can be changed from 35 ° C to 45 ° C.