
16 17
ENEN
SETTINGS (SETUP) SETTINGS (SETUP)
This menu allows you to change certain settings and to set the heating, temperature safeguard, auto restart and
hysteresis. Pressing the Skey for more than 6 seconds will open the Settings menu. The display will show a capital
D: followed by a number from 01 to 32. Briey pressing the S key allows you to scroll through the settings. The rst
setting is D:01, the second setting is D:02, etc.
Use the
or
key to change a setting. You press the ON/OFF key to conrm. If you do not want to change anything
and exit the menu, press the Rkey. The settings range from D:01 to D:32. Do not adjust settings D:16 to D:22. These
are factory settings.
To restore the factory settings, press and hold the M key until the Settings menu opens. All settings will now be restored
to factory settings. Conrm this with the on/off key.
D:01 Switching the heating elements on/off
Depending on the model, an OptiClimate has 2 or 3 heating elements. The heating elements of 1-phase systems are
connected to 1 phase and the heating elements of 3-phase systems are divided over all phases.
Each of these elements can be switched on and off individually in the Settings menu. If a central heating system is used
for heating, for example, all of these heating elements can also be switched off at the same time.
Setting:
D:1 = 3 means all three elements will heat
D:1 = 2 means two elements will heat
D:1 = 1 means one element will heat
D:1 = 0 means all elements are off
D:02 Temperature safeguard
If the room temperature exceeds 35°C, terminals 15 and 16 on the terminal strip of the unit will switch off the
heating elements in the rooms that have to be cooled. The switch-off temperature can be changed using the D:02
setting. The minimum temperature for switching off is 30°C and the maximum temperature is 40°C. If the temperature
drops below the set temperature for cooling mode again, the safeguard will switch off and restart the heat sources.
The safeguard does not affect the operation of the OptiClimate. However, the display will show the error message
E:15. (also see the fault code list)
D:03 Auto Restart after power interruption
If the power is interrupted when the unit is on and the power is restored, the unit will switch on by default. If you want
the unit to remain off after a power interruption caused by an external fault, you should change the D:03 setting.
Setting:
D:03 = 0 means Auto Restart is off.
D:03 = 1 means Auto Restart is on. This is the default setting. The display will show error code 14 in case of power
interruption. See also the fault code list.
D:04 Night cooling (Cool at Night) on/off.
Using this setting, the night cooling can be switched on.
D:04 = 0 means Cool at Night is off. This is the default setting.
D:04 = 1 means Cool at Night is on.
If in the timer off mode the minimum temperature is, for example, set to 22°C, the unit will cool the room to 22°C in the
night mode. If the room temperature drops below 22°C, the unit will begin to heat the room. This function is useful in
warm climates, in a very well-insulated room or with other sources of heat that cannot be switched off.
When the Cool at Night function is active a moon icon will be shown on the display.
D:05 Pre-Heating on/off.
Pre-heating can be switched on using this setting.
D:05 = 0 means Pre-Heating is off. This is the default setting.
D:05 = 1 means Pre-Heating is on.
If Pre-Heating is switched on, the unit will heat the room up to the set cooling mode (day) temperature one hour before
daybreak (timer is on). At the beginning of the day, the room will be at the right temperature. Besides the advantage of
giving the day temperature a jump-start, this also prevents the cold parts of the unit from becoming wet, which reduces
or prevents mould build-up.
Note: Only works in conjunction with the timer and not in the light cell mode!
D:06 Slow cool-down (post-heating) on/off.
Slow cool-down (post-heating) can be switched on using this setting.
D:06 = 0 means Slow Cool-Down is off. This is the default setting.
D:06 = 1 means Slow Cool-Down is on.
If Slow Cool-Down is switched on, the unit will slowly cool the room until one hour after the end of the day.
Note: Only works in conjunction with the timer and not in the light cell mode!
D:07 Dual Room (cooling two rooms 12h by 12h) on/off.
Using this setting, you can switch on/off the cooling of two rooms alternately.
D:07 = 0 means Dual Room operation is off. This is the default setting.
D:07 = 1 means Dual Room operation is on. If the Dual Room function is active, the display will show the house icon
at the bottom right-hand side.
To use this function, you will have to order a three-way valve and a connection set consisting of a three-way valve,
plenum box, second temperature sensor, external water seal and an extensive installation/user manual.
D:08 Alarm port N.O. (Normally Open) or N.C. (Normally Closed)
Using this setting, the alarm port can be adjusted.
D:08 = 0 means N.C. Normally closed. This is the default setting.
D:08 = 1 means N.O. Normally open.
Refer to the user manual for the correct settings of the SMS (GSM) detector or the alarm system that should be connected.
D:09 Water Valve options
You can opt to open the water valve only if there is a demand for water or only use the water valve if the water leakage
sensor detects a leak. Setting D:09 to 0 will only open the valve during cooling. Setting D:09 to 1 will only open the
valve when a leak occurs.
D:10 Timer port
If D:10=0, ports 15 and 16 will interrupt the High Temperature alarm. If D:10=1, the high temp alarm will not occur
through these contacts. If D:10=1, port 16 is common and ports 16 & 17 will be each other's alternate contacts. The
clock of the OptiClimate (OC) will operate these make-and-break contacts and the clock/timer of the OC can replace
the clock on the control panel. The lamps will operate synchronous with the cooling mode of the OC. To install a High
Temperature safeguard, contact 16 should be aligned with the alarm port on the printed circuit-board. If there is a
High Temperature alarm, this alarm will interrupt the timer’s signal and the temperature safeguard will still operate. The
setting of the alarm port should then be the standard setting (0 = N.C.).
D:11 Hysteresis of the temperature
Using this setting, you can adjust the hysteresis (bandwidth) of the temperature control. This is the temperature difference
required to switch the compressor on and off.
Setting: D:11 = 2 means the hysteresis is 2. This is the default setting.
The hysteresis can be set from 1°C to 4°C in steps of 0.5°C. If, for example, the day temperature is set to 28°C and the
hysteresis to 2°C, the unit will start to cool at 29°C and stop cooling at 27°C. To shorten the hysteresis effectively, the
resting time of the compressor should also be reduced. (D:27)