manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Ormandy
  6. •
  7. Boiler
  8. •
  9. Ormandy Rycroft Evoplate CP-B25 Assembly instructions

Ormandy Rycroft Evoplate CP-B25 Assembly instructions

Evoplate Vessel
Installation, Operating &
Maintenance Instructions
Ormandy Rycroft
Heating & Cooling Solutions
Running 1Page 2
VERY IMPORTANT - PLEASE READ CAREFULLY
Safety Points 1.1 Page 2
Start Up 1.2 Page 3
Working Principles 1.3 Page 3
Installation 2Page 4
Sizing and Selection 2.1 Page 4
Installation 2.2 Page 7
Operation and Set Up 2.3 Page 9
Health 3Page 16
Maintenance 3.1 Page 16
Service 3.2 Page 16
Spares 3.3 Page 16
Information 4Page 17
Specification 4.1 Page 17
Installation, Operating and Maintenance Instructions Page 1
1
Lifting
Evoplate - Installation, Operating & Maintenance Instructions
Lifting lugs are fitted on the top of the vessel. These should be used
when lifting the vessel into position. Ensure the vessel remains in a
vertical position (for vertical vessels) and horizontal position (for
horizontal vessels) throughout.
Foundations
Level foundations should be prepared for the buffer vessel. Uneven
foundations can cause airlocks within the vessel and the vessel could
be unstable when maintenance work is carried out.
The vessel should be attached to the foundations using bolts through
the bolt holes on the vessel foot pads.
Flanges and Bosses
PTFE should be used when fitting
screwed connections to the
vessel bosses.
When fitting flange connections,
ensure mating flanges are square
and that the weight of the
pipework is supported by
external supports and not the
vessel connections.
Expansion of pipes should be
considered for the application
and measures put in place if
necessary.
Filling and Draining
Tighten any bolts on the vessel prior to filling as these may have
become loose during transit. Ensure bolts are tightened diametrically
and to the correct Torque. (if in doubt contact Ormandy Limited
technical department).
When filling the vessel ensure the vent connection on the top dished
end is open. When the vessel is full the vent boss should be plugged.
When draining the vessel ensure the vessel is released of pressure
slowly and that the vent is then open before draining commences.
Relief Valve
Ensure that the relief valve is
fitted with a discharge pipe (on
the valve outlet). The pipe should
open to atmospheric pressure
and run to a low level suitable
drainage area.
Inspection
Internal inspection of the vessel should take place after the first 3
months. The inspection should involve looking for signs of corrosion
or local pitting cells. If any is found then a specialist should be
consulted. If after the first inspection the vessel appears sound then
a further inspection should be made after 6 months.
Again, on satisfactory review, inspection can be limited to annually.
When inspecting the internal side of the vessel ensure that the vessel
is first drained of its contents in accordance with the procedures
detailed above.
Before removing the inspection cover ensure that the cover is first
supported by use of the coverplate lifting lug. When re-fitting the
cover, the bolts should be tightened diametrically.
Evoplate Package shown below
2
1.1 Safety Points
1. Running
• During operation, the unit may have very hot or very cold
surfaces.
• The temperature probe is installed directly in the secondary flow.
Do not remove when the system is hot, full or under any pressure.
• The equipment has danger from electricity. Do not remove covers
or allow any exposed live parts. Isolate before working on the
unit.
• Take care when lifting. Only use the designated lifting point.
Use only certified lifting equipment capable of lifting the weight.
Water may also be present and spillage could occur.
• Never lift the HT breeze by any associated pipework or pipe
connections.
• Take care when handling, as some of the edges may be sharp.
• Electrical and Mechanical functionality must be considered prior
to connecting any none factory fitted equipment. E.g. Pumps,
Valves / Actuators etc.
Switch on via switch (16)
The front panel will illuminate. After
a few seconds of self checks, the
displays will settle to the Day (1)
(Time-clock only), Time (2) and
Temperature (3). The pumps will
start (11) and the valve will open
(15) and the system healthy
indicator (13) will illuminate.
In the majority of applications,
the resulting control and running
will be perfectly satisfactory. The
standard temperature setting is
60C and the unit will run
continuously (24 hour operation).
To change any of the default
settings, see section (2.3).
13 System Healthy Indicator
14 System Fault Indicator
15 Valve Position Bar Display
16 On/Off switch
1 Day/Mode Display
2 Time/Alarm Display
3 Temperature/Parameter Display
4 High Temperature Alarm Indicator
5 Reset Push Button
6 Step Left Push Button
7 Value Increase Push Button
8 Step Right Push Button
9 Value Decrease Push Button
10 Mode Select Push button
11 Pump Energised Indicator
12 Power On Indicator
1 2 3
45
6
7
8
9 10
11
12
13
15
14
16
✓
✘
100
50
0
Ormandy Rycroft
Heating & Cooling Solutions
1
3
6
2
54
7
3
1.3 Working Principles
The HT Breeze comprises of a Supapac Plate Heat Exchanger, either a
3 port or 4 port control valve, primary pump, temperature sensor and
PID controller, all mounted on a skid base.
The motorised 3 or 4 port control valve, allows rapid adjustment of the
primary heat input to match changes in secondary hot water demand.
The HT Breeze requires no insulation and the design ensures that the
outlet temperature does not fall below the set point (60°C default but can
be adjusted to suit customer requirements) and consequently reduce the
risk of legionnaires disease.
Providing the class of accommodation and details of the number and
type of fixtures are known, Rycroft will be pleased to recommend the
optimum size of HT Breeze.
1. Running continued
With buffer vessel to form a semi-instantaneous water heater
3 Port Valve
Primary
Flow
Primary
Return
Secondary
Inlet
Secondary
Outlet
Control
Stat
PHE
4 Port Valve
Primary
Flow
Primary
Return
Secondary
Inlet
Secondary
Outlet
Control
Stat
PHE
Secondary Flow
Temperature Gauge
Pressure Gauge
Expansion
Vessel
Expansion
Relief
Valve
Lockshield
Valve
Cold Feed
Non-Return
Valve
Circulating
Pump
Secondary
Shunt Pump
Drain
Pressure/Temp
Relief Valve
Temperature
Sensor
Commissioning
Valve
Drain
Plug
Two Way
Valve
Primary Return
Actuator
Primary Feed
Primary
Pump
1.2 Start Up - Checks
Checks Complete (✓)
Check that electrical installation is complete.
Check that the mechanical installation is complete.
Check that the system has been flushed and that there are no leaks.
Check that any air has been eliminated from the system.
Check that valves are opened in the required sequence.
4
2.1 Sizing and Selection
2. Installation
To size a stand alone HT Breeze, use the following demand factors.
Facility
Private
Hand
Basin
Public
Hand
Basin
Shower Bath Slop
Sink
Bar
Sink
Kitchen
Sink
Washing
Machine
Lab
Sink
Dish
Washer
Hospital 1 2 4 4 4 10 10 3 10
Residential
Hall & Hotel 1 2 4 4 4 12 10 10 10
School 0.5 3 10 - 3 10 3 3 10
Sports Centre
/Barracks 0.5 2 10 - 3 12 10 - - 10
Restaurant 0.5 4 - - 12 12 19 - - 10
University 0.5 3 10 - 3 - 10 - 3 10
Offices 0.5 3 3 - 3 - 10 - 3 10
Factory 0.5 3 4 - 3 - 10 - 3 10
Apartments 1 - 4 4 3 - 3 3 - 2
Careful consideration must be given to the sizing of stand alone instantaneous water heaters. Standard
demand units incorporate a degree of diversification that would be inappropriate for continuous use
applications.
A more desirable method of sizing for continuous applications is to complete a fixture count and allocate an
appropriate flow for each fitting.
It should also be noted that shower demands for Schools, Sports Centres and Universities should only be
used for medium to large installations. Please refer to our design department for further information.
Table 1
42 single person showers 42 x 4 = 168
55 private hand basins 55 x 1 = 55
9 public hand basins 9 x 2 = 18
3 slop sinks 3 x 4 = 12
15 baths 15 x 4 = 60
Total Demand Units = 313
The shower factors are based upon
intermittent use.
Where certain activities may result
in all showers operating together,
please contact our sales department
for advice.
Example
From Table 1. A 173 bed Hospital ward with showers, hand basins and sinks.
Sizing Considerations
5
2.1 Sizing and Selection continued.
2. Installation continued
The correctly sized HT Breeze can now be selected from Table 2.
HT Breeze Model Maximum
Demand Units
Max Continuous Duty
@ 60°C (litres/sec)
Boiler
Power (kw)
Min Secondary
Volume (litres)
CP-B25 15 0.25 52 45
CP-B50 23 0.50 105 75
CP-B75 45 0.75 157 85
CP-B100 70 1.00 209 125
CP-B125 90 1.25 261 135
CP-B150 130 1.50 313 150
CP-B200 210 2.00 418 200
CP-B250 320 2.50 522 250
CP-B300 480 3.00 627 300
CP-B350 640 3.50 732 350
CP-B400 820 4.00 836 400
CP-B450 1050 4.50 935 450
CP-B500 1300 5.00 1040 500
These sizes represent the standard range of HT Breeze instantaneous water heaters.
For larger requirements for both single and three phase, please contact our technical department.
Both standard and special designs can be offered, to suit your specific requirements.
Table 2
6
To size a HT Breeze and Buffer Vessel use the following maximum demand rates.
Facility
Private
Hand
Basin
Public
Hand
Basin
Shower Bath Slop
Sink
Bar
Sink
Kitchen
Sink
Washing
Machine
Lab
Sink
Dish
Washer
Load
Factor
Hospital 10 15 70 60 50 80 100 40 150 0.7
Residential
Hall & Hotel 10 15 50 50 50 100 80 100 150 0.5
School 5 20 180 40 80 40 40 150 0.8
Sports Centre
/Barracks 5 15 220 40 100 80 100 1
Restaurant 3 25 100 100 140 150 1
University 5 20 220 40 80 40 150 0.8
Offices 5 10 180 40 40 40 100 1
Factory 5 20 120 50 80 40 100 1
Apartments 5 50 50 40 20 40 20 0.7
Table 3
2. Installation continued
42 single person showers 42 x 70 = 2940
55 private hand basins 55 x 10 = 550
9 public hand basins 9 x 15 = 135
3 slop sinks 3 x 50 = 150
15 baths 15 x 60 = 900
Total Volume = 4675
Load Factor from Table 3 = 0.7
Total Demand Rate 4675 x 0.7 = 3273 litres/hr
Example of a Hospital Facility
The HT Breeze and Buffer Vessel combination should be sized as follows:-
The Buffer Vessel Capacity = 25% of the total hourly demand. Therefore the required storage capacity
= 3273 x 0.25 = 818 litres. The nearest standard Buffer Vessel sizes are 800 and 900 litres. It is
recommended to go up in size and therefore a 900 litre Buffer Vessel should be selected.
The HT Breeze can be selected as follows:-
Continuous hourly demand = 3273 litres
Specific Heat Capacity of Water = 4.187 kj/kg, °C
Cold Feed Temperature = 10°C
Secondary Flow Temperature = 60°C
Therefore the required kw rating = 3273 x 4.187 x (60-10)
The nearest standard HT Breeze is a CP-B100 which is rated at 209 kw
3600 = 190.3 kw
7
A HT Breeze and Buffer Vessel combination is used when water demand is not constant but high flow
frequently occurs. Boiler power requirements are reduced by storing hot water in the buffer vessel for
peak demands.
The HT Breeze should always be installed with a secondary return line coming back from the system and
into the cold feed line prior to the HT Breeze or Buffer Vessel. This will remove nuisance high limit tripping
due to temperature overshoot, which would occur if the unit was installed on a ‘dead end’ system, when an
outlet was closed. To ensure full heat dissipation, the secondary volume should not be less than that shown
in Table 2.
For larger capacities contact the sales department for advice.
2.1 Sizing and Selection continued.
2. Installation continued
2.2 Installation
Foundations
The HT Breeze should be mounted on prepared foundations that are level.
Lifting
One lifting hole is provided on the top of the HT Breeze control panel.
Avoid the use of chains as screwed connections may be damaged by
the links.
Caution: Never lift the HT Breeze by its pipework or pipe connections.
Pipework
Make sure that the pipework flanges are square and correctly spaced
before bolting up. See that the weight of the pipework is taken by external
supports and not by the HT Breeze. Allowances should be made for
expansion of the pipes either by suitable bends or flexible joints.
Tighten flange bolts in a diametrically opposite sequence and not
consecutively round each flange.
Connections
Threaded connection may be sealed with PTFE tape. Flanged connections
should be sealed with a suitable gasket and sealing agent.
Liquid Expansion
Changes in volume with temperature must not be overlooked. The system
pressure will rise dramatically if there is nowhere for water to expand. It is
not advisable to use a relief valve as a means of releasing the excess water.
Vented systems use the atmospheric vent as an expansion pipe with
discharge back into the tank. Unvented systems require a separate
expansion tank.
Venting
Vent valves must be fitted at the highest point in the connecting pipework so
that the HT Breeze can be bled of air for initial operation. It is essential that
the flooded can type pump motors which are commonly used for all
HT Breeze pumps are bled of air and flooded before starting.
See the pump manufacturer’s instructions.
Filling
Before filling the system
check that the drain valve is
closed and all air vents are
open.
Flush out the system before
installing the HT Breeze to
remove any foreign matter.
Close any manual air vents
and run the HT Breeze.
Crack the vents to release
air
Caution: Do not fill the
system too quickly,
otherwise pockets of air
may become trapped.
8
2.3 Operation and Set Up
2. Installation continued
13 System Healthy Indicator
14 System Fault Indicator
15 Valve Position Bar Display
16 On/Off switch
1 Day/Mode Display
2 Time/Alarm Display
3 Temperature/Parameter Display
4 High Temperature Alarm Indicator
5 Reset Push Button
6 Step Left Push Button
7 Value Increase Push Button
8 Step Right Push Button
9 Value Decrease Push Button
10 Mode Select Push button
11 Pump Energised Indicator
12 Power On Indicator
Electrical Connections
Terminal Block
The Electrical connections are located in the terminal compartment.
A description of the terminals can be found on the inside of the terminal compartment cover.
Connect a single phase 230V 50Hz supply to the Mains Input terminals. Max full load current is 16A with
the majority of units being considerably less.
If the unit is to be controlled remotely, connect the remote control switch or contacts to the ‘Remote Enable
Terminals’. If the unit is to be controlled locally fit a link between these terminals.
Do NOT apply voltage to the terminals of these contacts!
Voltage free fault relay contacts are provided for Remote Fault Indication.
1 2 3
4 5
6
7
8
9 10
11
12
13
15
14
16
✓
✘
100
50
0
Ormandy Rycroft
Heating & Cooling Solutions
1
3
6
2
54
7
9
2.3 Operation and Set Up Continued.
2. Installation continued
Operation
The HT Breeze is a self-contained unit, which controls up to two primary and two secondary pumps,
together with a three/four-port valve to provide hot water. When the system is fitted with two primary pumps
they are operated on a shared duty-standby cycle with automatic changeover on pump failure.
The HT Breeze can be energised by its own internal time clock function, by a remote switch or Building
Management System or by a combination of the two.
a) Remote Switch or Building Management System Control
The HT Breeze will be turned on when contacts connected to the Remote Enable terminals are
closed. This allows the user to control the time of day when hot water will be available.
When the contacts are open the system is turned off.
b) Internal Time Clock Control
For this function to work the Time clock function should be turned on (see Set Up) and the Remote
Enable terminals should be linked.
Under Time clock control the HT Breeze will be automatically turned on and off at preset times of the
day. Up to two on and two off times can be programmed for each day of the week.
The system can be re-activated after it has automatically switched off by pressing the
Value Increase (7) push button. Each press of this push button will add 30-minute increments to a
total, which is shown in the Time/Alarm window. Pressing the Value Decrease (9) push button will
subtract 30-minute increments from the total time.
The time value counts down and when the time shown has elapsed, the unit will revert to normal time
clock operation.
c) Remote Switch and Internal Time Clock Control
For this function to work the Time clock function should be turned on (see Set Up) and a remote
Control switch should be connected to the Remote Enable terminals.
Under Time clock control the HT Breeze will be automatically turned on and off at preset times of the
day. Up to two on and two off times can be programmed for each day of the week. When contacts
connected to the Remote Enable terminals are opened the HT Breeze will be turned off.
When the system has turned off under time clock control it can be re-activated by pressing the Value
Increase (7) push button. Each press of this push button will add 30-minute increments to a total,
which is shown in the Time/Alarm window. Pressing the Value Decrease (9) push button will subtract
30-minute increments from the total time.
The time value counts down and when the time shown has elapsed, the unit will switch off and revert
to normal time clock operation. However, when the system has been turned off under remote control
it cannot be re-activated by pressing the Value Increase (7) push button.
10
2.3 Operation and Set Up Continued
2. Installation continued
Set Up
The HT Breeze control unit is factory programmed with temperature and control settings that will suit most
applications. However, we would recommend that the unit is commissioned to ensure correct operation and
maximum efficiency. Contact our Service Department for details.
All the values are adjustable so that you can customise the unit to exactly match your system.
The set up routine is entered by pressing and holding the Mode (10) push button for three seconds.
Press the Step Right (8) and Step left (6) push buttons to move forwards and backwards through the sequence.
Press the Value Increase (7) or Value Decrease (9) push buttons to alter the value shown in the display.
Press and hold the Mode (10) push button for 3 seconds to exit the set up routine.
Figure 1 - Set Up Sequence
Press and hold for 3 seconds to enter
Set Up routine.
Press Step Right to move to first value.
Press Value Increase or Value Decrease
push buttons to alter water temperature.
Press Value Increase to turn Time
clock function on or off.
Press Value Increase or Value Decrease
to change Day number.
Press Value Increase or Value Decrease
push buttons to change time. Press and hold
push button for rapid change.
Press Value Increase or Value Decrease
push buttons to change the time of the first
timed on and off period. Press and hold
push button for rapid change.
Press Value Increase or Value Decrease
push buttons to change the time of the
second timed on and off period. Press and
hold push button for rapid change.
Press Step Right push button to set the on-off
times for day 2, day 3, day 4 etc. Press and
hold Value Select push button for 3 seconds
to exit Set Up routine.
The system continues to control when the controller is in the set up routine allowing
adjustments to be made on the fly
11
2.3 Operation and Set Up Continued
2. Installation continued
System Faults
When a fault situation is detected the System Fault (14) indicator will be lit and the internal Fault relay will be
energised. The normal time and temperature display will be replaced by an alarm message. The messages
and meanings are shown in Figure 2 below. If a system fault occurs when the controller is in the set up
routine the System Fault (14) indicator will be lit but the display will not be replaced by an alarm message.
The alarm message can be viewed by leaving the Set Up routine.
Figure 2 - Alarm Messages
First High temperature level detected.
Second High temperature level detected -
buzzer sounds and the system is automatically
shut down.
Low temperature detected.
Primary Pump No 1 failure - if two primary
pumps are fitted Primary Pump No 2 will be
energised.
Primary Pump No 2 failure - Primary Pump
No 1 will be energised.
Secondary Pump No 1 (shunt) failure - system
is automatically shut down.
Secondary Pump No 2 (re-circulation) failure
-system is automatically shut down.
Thermo-couple failure - the system is
automatically shut down.
System has been remotely disabled
The Second High temperature level alarm will automatically shut the system down and sound a warning
buzzer. The buzzer can be silenced by pressing the Reset (5) push button. When the fault has been
diagnosed and corrected the system can be re-activated by pressing the Reset (5) push button again.
This can only be performed when the temperatures have returned to near normal. All the other alarms will
automatically reset when the problem has been corrected. Alarms constantly re-occurring could indicate that
the system is incorrectly configured.
Advanced Set Up Routine
The system is supplied with default settings, which suit most applications. The advanced set up feature
allows Installers and Engineers to tailor the settings to suit particular installations. The system continues
to control when the controller is in the advanced set up routine so that the results of adjustments can
be seen immediately. In addition manual control of the valve position is available.
12
2.3 Operation and Set Up Continued
2. Installation continued
The set up routine is entered by simultaneously pressing and holding the Mode (10) , Step Left (6) and Value
Decrease (9), Push buttons for three seconds.
Press Step Right (8) and Step Left (6) push buttons to move forwards and backwards through the sequence.
Press the Value Increase (7) or Value Decrease (9) push buttons to alter the value shown in the display.
Press and hold the Mode (10) push button for 3 seconds to exit the set up routine.
Figure 3 - Advanced Set Up
Press and hold for 3 seconds to enter Advanced
Set Up routine.
Press Value Increase or Value Decrease push
buttons to alter Proportional Band.
Press Value Increase or Value Decrease push
buttons to alter Integral Time.
Press Value Increase or Value Decrease push
buttons to alter Derivative time.
Press Value Increase or Value Decrease push
buttons to alter First level High temperature limit.
Press Value Increase or Value Decrease push
buttons to alter Low Temperature Limit.
Press Value Increase or Value Decrease push
buttons to alter High Temperature Limit Time Delay.
Press Value Increase or Value Decrease push
buttons to alter Lower Temperature Limit Time Delay.
Press Value Increase or Value Decrease push buttons
to vary valve position. Figure shows percentage open.
Press Value Increase or Value Decrease push
buttons to alter Primary Pump over-run time.
Press Value Increase or Value Decrease push
buttons to alter Primary Pump over-run temperature.
Press Value Increase or Value Decrease push
buttons to alter Secondary Pump over-run time.
Press Value Increase or Value Decrease push
buttons to alter Secondary Pump over-run temperature.
Press Value Increase or Value Decrease push buttons
to alter the Night Set-back/Pasteurisation temperature.
Press Value Increase or Value Decrease push
buttons to alter Primary Pump duty - standby time.
Press and hold Mode push button for 3 seconds to
exit Set Up routine.
Press Step Right push button to move to the first
setting value.
13
2.3 Operation and Set Up Continued
2. Installation continued
Night Set Back / Pasteurisation
When the DIP switch for Night set-back/Pasteurisation is set to the on position and the unit into standby.
When set back/pasteurisation value (S Sb to) is set to above normal set temperature (S SET To) the
controller assumes pasteurisation and raises the temperature to the set back/pasteurisation value for one
hour, before returning to standby. Alternatively, when it (S Sb To) is set to below normal set temperature, the
controller assumes set back and lowers the temperature to this value until normal day running begins.
Manual Control
The Advanced Set Up routine allows engineers to position the control valve manually. This feature is active
while this set up window is visible. This feature can be disabled and control restored to automatic by pressing
the Step Left (6), or Step Right (8) push buttons to display another parameter or pressing and holding the
Mode (10), push button to exit the advanced set up routine.
Remote Set Point Adjustment
When a 4 - 20mA signal is connected to the remote input, the set point can be varied between
20 deg c = 4mA and l00 deg c = 20mA. It should be noted that BMS control of the unit starts as soon as the
external signal of above 2mA is detected. Conversely if the controller loses signal, or the signal drops below
2mA it will revert back to it’s own internal set point.
DIP Switch Settings
The physical configuration of the system and the Night Set-back function are programmed into the controller
by setting the position of eight switches. Switches are located on the display printed circuit board.
To change the position of these switches:
1) Isolate the mains supply to the controller.
2) Open the hinged door.
3) Remove the four black fixing screws and slide the control facia out of the enclosure taking care not to
pull the connecting cable.
4) Turn the facia over. DIP switches are located on the bottom edge of the circuit board.
5) Change the switch positions as required (see table below)
6) Replace facia, close hinged door and switch on the mains supply.
1 2 3 4 5 6 7 8 Function
On No Operation
Off No Operation
On No Operation
Off No Operation
On Fault Relay Operates During Remote Disable
Off Fault Relay, No Operation During Remote Disable
On Valve Output 2-10V
Off Valve Output 0-10V
Off Night Setback OFF
On Night Setback ON
Off Off No Secondary Pumps Fitted
Off On 1 Secondary Pump Fitted (SHUNT)
On Off 1 Secondary Pump Fitted (RECIRC)
Off 1 Primary Pump Fitted
On 2 Primary Pumps Fitted
The following table shows the switch controls. (Bold positions are factory default values).
14
2.3 Operation and Set Up Continued
2. Installation continued
Set Up:
Alternative setting record (Date) ............. ............. .............
Set Point = 60 ............. ............. .............
Time Clock = Off ............. ............. .............
Day (Set) = 1 = Mon 7 = Sunday
Clock (Set) = Time
Day 1 ON 1 = 0000 ............. ............. .............
Day 1 OFF 1 = 0000 ............. ............. .............
Day 1 ON 2 = 0000 ............. ............. .............
Day 1 OFF 2 = 0000 ............. ............. .............
Day 2 ON 1 = 0000 ............. ............. .............
Day 2 OFF 1 = 0000 ............. ............. .............
Day 2 ON 2 = 0000 ............. ............. .............
Day 2 OFF 2 = 0000 ............. ............. .............
Day 3 ON 1 = 0000 ............. ............. .............
Day 3 OFF 1 = 0000 ............. ............. .............
Day 3 ON 2 = 0000 ............. ............. .............
Day 3 OFF 2 = 0000 ............. ............. .............
Day 4 ON 1 = 0000 ............. ............. .............
Day 4 OFF 1 = 0000 ............. ............. .............
Day 4 ON 2 = 0000 ............. ............. .............
Day 4 OFF 2 = 0000 ............. ............. .............
Day 5 ON 1 = 0000 ............. ............. .............
Day 5 OFF 1 = 0000 ............. ............. .............
Day 5 ON 2 = 0000 ............. ............. .............
Day 5 OFF 2 = 0000 ............. ............. .............
Day 6 ON 1 = 0000 ............. ............. .............
Day 6 OFF 1 = 0000 ............. ............. .............
Day 6 ON 2 = 0000 ............. ............. .............
Day 6 OFF 2 = 0000 ............. ............. .............
Day 7 ON 1 = 0000 ............. ............. .............
Day 7 OFF 1 = 0000 ............. ............. .............
Day 7 ON 2 = 0000 ............. ............. .............
Day 7 OFF 2 = 0000 ............. ............. .............
Alternative setting record (Date)
............. ............. .............
Proportional Band = 60% ............. ............. .............
Integral Time = 4 mins ............. ............. .............
Derivative Time = Off ............. ............. .............
High Limit = 78C ............. ............. .............
Low Temperature Warning = 35C ............. ............. .............
High Temperature Limit Time Delay = 1 min ............. ............. .............
Low Temperature Limit Time Delay = 1 min ............. ............. .............
Factory Default Settings
Set Set:
15
2.3 Operation and Set Up Continued
2. Installation continued
Manual Valve Operation =00% (Not presetting)
Primary Pump Overrun Time = 5 mins ............. ............. .............
Primary Pump Overrun Temperature = 40C ............. ............. .............
Secondary Pump Overrun Time = 5 mins ............. ............. .............
Secondary Pump Overrun Temperature = 40C ............. ............. .............
Night Set-back/Pasteurisation Temperature = 68C ............. ............. .............
Primary Pump Duty Changeover Time = 9 hrs ............. ............. .............
By pressing the reset (5)and mode (10)buttons simultaneously for a few seconds, the time clock settings will
be returned to the factory default settings.
By pressing the reset (5) and decrease (9)buttons, the control and alarm parameters will be returned to the
factory default settings.
16
3.1 Maintenance
3. Health
A detailed inspection of the HT Breeze should be made after six months.
This provides an insight into future requirements for efficient maintenance. If
the HT Breeze is cleaned and there is no sign of corrosion, it can be safely
assumed an annual inspection will be sufficient for future servicing.
All electrical connections should be checked and tightened if necessary.
Caution:- Maintenance should only be performed by qualified personnel
only. Electrical work should be carried out by a qualified electrician in strict
conformance to the latest requirements.
In order to maintain the HT Breeze unit you will require as a minimum the
following tool kit:
• Set of Metric allen Keys up to M16
• Set of Metric spanners
• Set of Screwdrivers
• A pipe wrench to suit a maximum 50mm nominal pipe size.
• M16 friction ratchet and M16 deep ring spanner (CP-B25 to CP-B250)
Controller
The controller is run via an EPROM that stores all the changes to the time
programmes and other data.
After the first six months, all connections in the panel should be checked
and tightened if necessary.
Temperature Thermocouple
Ensure that the Thermocouple connections are satisfactory.
Refer to the manufacturer’s instructions.
Control Valve and Actuator
Check that the valve will open and close by using the manual facility on the
controller. Electrical connection should be checked at the actuator. The
linkage should also be tightened to ensure good mechanical contact.
Refer to the manufacturer’s instructions.
Hi-Limit Valve and Actuator (if fitted)
Check that the valve opens and closes by turning the power on and off.
Electrical connection should be checked at the actuator. The linkage should
also be tightened to ensure good mechanical contact.
Refer to the manufacturer’s instructions.
Primary Pump
Ensure that the pump is on the correct speed setting and that wiring
is secure at all terminals.
Plate Heat Exchanger
A series of contoured plates with ports form a plate pack with flow
channels. The hot water flows down alternate channels, while the cold water
flows up alternate channels, creating a 100% counter flow.
Ormandy offers a full and
comprehensive range of
service and support.
This encompasses the
maintenance, commissioning
and repair of general water
heating equipment, including
heat exchangers, boilers,
pressurisation units, booster
sets and calorifiers.
All HT Breeze component
parts are available as
replacement/spare items.
Each unit carries a unique
serial number (12345/6)
and should be quoted when
ordering spares.
Contact our Sales
Department -
[email protected]
3.2 Service
3.3 Spares
17
4.1 Specification
4. Information
Power Supply Requirements
Voltage: 230 Volts, 50Hz.
Nominal current: Maximum 16Amps (Pump and Duty dependant).
Inputs
Temperature probe: Type J thermocouple (Grounded) via a 12 bit A/D
converter (minimum 0.1 °C resolution). Display range: 0 - 250°C
Volt Free Contacts
To enable from remote source (Time-clock, SCADA,BMS, boiler
controls etc).
For connection of a supplementary high limit contact or thermostat as a
second alarm Pump (s) fault contact.
Signal
4-20mA remote set point adjustment. 4mA = 20°C. 20mA = 100°C
Outputs
• Two primary (lDuty, !Standby) single phase 230v SA Maximum
(Resistive load).
• Two secondary (1 circulation, 1 shunt ) single phase 230v SA Maximum
(Resistive load)
• Hi - Limit and Control actuator supply, 24 v.a.c 50 VA Max. Combined.
• Control signal 2 - 10 v, 0 - 10.d.c 0. lmA, Max.
• The effective control setting range 0 - 87°C
Volt Free Contacts
Changeover fault contact for remote alarm on fault, to SCADA, BMS,
Annunciator etc.
Signal
4 - 20mA remote indication of process variable. 4mA = 0° C.20mA = 100°C
Enclosure
The enclosure is Polystyrene based, with a clear polycarbonate hinged lid
ingress protection rated at IP65. The lid has a snap lock and can be fitted
with the screwdriver slotted locking catch (Supplied loose)
*NOTE: The volt free contact terminals must not have voltage
applied to them
18
Duncombe Road,
Bradford, England BD8 9TB.
Telephone: +44 (0) 1274 490911. Email: s[email protected]
Ormandy Rycroft
Heating & Cooling Solutions
www.ormandygroup.com

This manual suits for next models

12

Other Ormandy Boiler manuals

Ormandy Commodore Plus Guide

Ormandy

Ormandy Commodore Plus Guide

Ormandy Optimajor GLP S 4.0 Manual

Ormandy

Ormandy Optimajor GLP S 4.0 Manual

Ormandy 2000 Series User manual

Ormandy

Ormandy 2000 Series User manual

Ormandy SCP PLUS 3000 User manual

Ormandy

Ormandy SCP PLUS 3000 User manual

Popular Boiler manuals by other brands

Prestige 75 Installation, operating and maintenance instructions

Prestige

Prestige 75 Installation, operating and maintenance instructions

CHAFFOTEAUX NIAGARA C 25 Installation & servicing instructions

CHAFFOTEAUX

CHAFFOTEAUX NIAGARA C 25 Installation & servicing instructions

Sime benchmark Planet Super 4 W. M. User instructions

Sime

Sime benchmark Planet Super 4 W. M. User instructions

Bosch Greenstar FS operating instructions

Bosch

Bosch Greenstar FS operating instructions

Curtis WB5GT user guide

Curtis

Curtis WB5GT user guide

Crown Boiler 32 Series and Installation and operating instructions

Crown Boiler

Crown Boiler 32 Series and Installation and operating instructions

Crown CRN30 Operating & installation instructions

Crown

Crown CRN30 Operating & installation instructions

Garanterm Ravi HM 24 Installation and user manual

Garanterm

Garanterm Ravi HM 24 Installation and user manual

Keston HEAT 45 instruction manual

Keston

Keston HEAT 45 instruction manual

AMW 815 Specification sheet

AMW

AMW 815 Specification sheet

Truma B 10 installation instructions

Truma

Truma B 10 installation instructions

Solarbayer HVS Series instruction manual

Solarbayer

Solarbayer HVS Series instruction manual

Immergas EOLO Superior PLUS 24 Technical documentation

Immergas

Immergas EOLO Superior PLUS 24 Technical documentation

Patterson-Kelley DVSCM-02 owner's manual

Patterson-Kelley

Patterson-Kelley DVSCM-02 owner's manual

Westen Star Digit 240 Fi Instructions for the User and the Installer

Westen

Westen Star Digit 240 Fi Instructions for the User and the Installer

Potterton Performa System 12e Installation and servicing instructions

Potterton

Potterton Performa System 12e Installation and servicing instructions

Beretta EXCLUSIVE R installer and user manual

Beretta

Beretta EXCLUSIVE R installer and user manual

Lamborghini Caloreclima ERA 31 BS 60 Installation and maintenance manual

Lamborghini Caloreclima

Lamborghini Caloreclima ERA 31 BS 60 Installation and maintenance manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.