OSC INTELLIMETER A/B Series Guide

Page 1 of 117004-00054-A Rev A.indd 6/6/11
4242 REYNOLDS DRIVE * HILLIARD, OHIO * 43026-1264
PHONE: (614) 777-1005 * FAX: (614) 777-4511
800-853-2537 WWW.OSC-INTELLIMETER.COM
INSTALLATION AND CONNECTION MANUAL
for
INTELLIMETER®
MODELS A-xxx/B, A5-xxx/B, AB-xxx/B, AB5-xxx/B,
AP-xxx/B, AP5-xxx/B, ABP-xxx/B and ABP5-xxx/B
WARNING: Any work on or near energized metering equipment can present
a danger of electrical shock. All work on these products should be performed
only by qualified industrial electricians and metering specialists in accordance
with local utility safety practices and procedures outlined in the Handbook for
Electricity Metering (available from the Edison Electric Institute, 1111 19th
St. NW, Washington, DC 20036). The Information contained within this book is
intended to be an aid to qualified metering personnel. It is not intended to replace
the extensive training necessary to install or remove meters from service.

Page 2 of 117004-00054-A Rev A.indd 6/6/11
TABLE OF CONTENTS
INTRODUCTION.........................................................................................................................3
INSTALLATION AND CONNECTION INSTRUCTIONS..............................................................4
INSTALLATION AND CONNECTION INSTRUCTIONS, cont’d. .................................................5
PULSE OUTPUT CONNECTIONS .............................................................................................6
INPUT AND OUTPUT CONNECTORS (Connector Pin-outs).....................................................7
LOAD CONNECTIONS (Single-Load Meters).............................................................................8
LOAD CONNECTIONS (Two-Load Meters) ................................................................................9
PC BOARD ASSEMBLY............................................................................................................10
MAINTENANCE ........................................................................................................................ 11
Routine Maintenance ........................................................................................................................................ 11
Cleaning............................................................................................................................................................ 11
REPAIRS ................................................................................................................................... 11
REFERENCES.......................................................................................................................... 11

Page 3 of 117004-00054-A Rev A.indd 6/6/11
INTRODUCTION
The Intellimeter models A, A5, AB, AB5, R2 and PM2 are components of a system designed
to measure electrical energy and communicate the measurements to a Central Station using
powerline carrier signals over the power lines. AP, AP5, ABP and ABP5 are similar except they
have pulse output only without the powerline carrier. The models A and AB are single- and
dual-input watthour meters, respectively. The model R2 is a repeater which retransmits system
messages over the powerline. The model PM2 is a dual-channel pulse monitor which accepts
pulse input signals from water meters, gas meters, watthour meters or any other metering device
with a pulse output. The PM2 receives, counts and transmits the pulse information to the system’s
Central Station using powerline carrier communication.
Detailed setup and programming instructions are in the Intellimeter Field Programming Instructions
(Document 7004-00022-A).
Warning: If the equipment described is modified or used in any manner not specified by these
instructions the protection provided by the equipment may be impaired.
0.1A Models 5.0A Models Repeater, Pulse
Monitor Function Elect.
Rating Notes
A-120/B A5-120/B 1-Ch. Wattmeter 120Vac 1
AB-120/B AB5-120/B 2-Ch. Wattmeter 120Vac 1
AP-120/B AP5-120/B 1-Ch. Wattmeter, Pulse Output Only 120Vac 1
ABP-120/B ABP5-120/B 2-Ch. Wattmeter, Pulse Output Only 120Vac 1
R2-120/B Repeater 120Vac 1
PM2-120/B 2-Ch. Pulse Monitor 120Vac 1
A-277/B A5-277/B 1-Ch. Wattmeter 277Vac 2
AB-277/B AB5-277/B 2-Ch. Wattmeter 277Vac 2
AP-277/B AP5-277/B 1-Ch. Wattmeter, Pulse Output Only 277Vac 2
ABP-277/B ABP5-277/B 2-Ch. Wattmeter, Pulse Output Only 277Vac 2
R2-277/B Repeater 277Vac 2
PM2-277/B 2-Ch. Pulse Monitor 277Vac 2
A-346/B A5-346/B 1-Ch. Wattmeter 346Vac 3
AB-346/B AB5-346/B 2-Ch. Wattmeter 346Vac 3
AP-346/B AP5-346/B 1-Ch. Wattmeter, Pulse Output Only 346Vac 3
ABP-346/B ABP5-346/B 2-Ch. Wattmeter, Pulse Output Only 346Vac 3
R2-346/B Repeater 346Vac 3
PM2-346/B 2-Ch. Pulse Monitor 346Vac 3
NOTES: 1. 120Vac (Line to Neutral) for use on the following types of electrical service:
120Vac 1Φ2W
120/208Vac 3-Wire Network
120/240Vac 1Φ3W Edison
120/208Vac 3Φ4W
2. 277Vac (Line to Neutral) for use on 277/480Vac 3Φ4W electrical service
3. 346Vac (Line to Neutral) for use on 346/600Vac 3Φ4W electrical service

Page 4 of 117004-00054-A Rev A.indd 6/6/11
INSTALLATION AND CONNECTION INSTRUCTIONS
Working clearances should comply with NECArticle 110-16. If not, take corrective action.
The Intellimeter is intended for indoor use only. Do not install in damp or wet location.
Wire bending space should be in compliance with NEC Article 373-6. Verify that current
transformer (CT), potential tap and wiring can be installed without crowding subpanel.
Verify that the current transformer can be installed with a minimum 1/2-inch clearance to
uninsulated live parts in subpanel, and without bearing against dead metal parts. Verify
that power is 120/208, 120/240, 277/480 or 346/600Vac.
The Intellimeter PC Board is approved for mounting into a Type 1 enclosure. Mount the1.
Intellimeter PC Board on a panel using the mounting diagram in in Figure 9 as a reference.
Adequate clearance (0.75”) must be given around all sides of the board. Make sure that the
lower left mounting stud is connected to earth ground, either with a separate wire or metal
standoff and screw to the grounded panel.
NOTE: Equipment grounding must be done in accordance with local and national codes
of the authority having jurisdiction. A protective earth terminal is provided for this
function.
Run CT leads, potential leads and neutral lead from cabinet to Intellimeter enclosure. Use2.
a maximum size of #14 AWG THHN stranded wire and make all three wire harnesses a
minimum of 10 inches long, otherwise you will have difficulty plugging in the 4-position and
6-position connectors. (See Figure 8.)
Cut leads to size and strip 1/4” insulation off ends. No uninsulated wire should be showing3.
outside the connector. Identify leads with numbered tags at each end of wire within three
inches of termination and current transformer. ID is to be visible after installation.
Connect voltage leads to the four-position connector PL11 as shown in Figure 1. Label each4.
set of CT leads with the load/tenant ID. Connect single-load meter CTs to PL4 only (PL5 not
used). Two-load meters use both PL4 and PL5. See Figure 2 for CT connections and polarity.
Use Figures 5, 6, 7 and 8 for load connections.
VERY IMPORTANT: Record on the Installation Specification Sheet
(Document 7004-00083-A) and write on the blank label provided for
the enclosure cover, the “load/tenant ID” you are plugging into PL4 (“A
DIAL”) and the “load/tenant ID” you are plugging into PL5 (“B DIAL”). For
the label, use an indelible black marker.
NOTE: Intellimeters use terminal 1 for powerline carrier communications. Whenever possible,
use Phase A for terminal 1 on all meters and low-voltage service couplers. Low-voltage
service couplers are required to establish communication paths around transformers,
between separate services, etc.

Page 5 of 117004-00054-A Rev A.indd 6/6/11
INSTALLATION AND CONNECTION INSTRUCTIONS, cont’d.
Turn off all breakers in cabinet. Check all loads for voltage.5.
Disconnect power to subpanel. Have temporary lighting at hand, if required.6.
Remove feeders from lugs and place feeder cables through current transformers7. withcurrent
flow arrows pointed toward loads.
Replace feeders in the lugs and tightly secure connections.8.
Using wire ties, secure CTs on feeders at least 1/2 inch away from uninsulated live parts and9.
not in contact with dead metal.
Connect potential leads to feeders on line side of current transformers using an approved10.
method for making the tap.
Alternate: Route potential lead from input connector through the current transformer in the
direction of the current flow arrow and connect to voltage on the load side of the
current transformer.
For proper operation observe proper phasing between potential taps and current
transformers.
Connect neutral lead to neutral bus.11.
Use wire ties to bundle Intellimeter wiring harness and route it away from other conductors12.
in cabinet. Also bundle wiring harness in Intellimeter enclosure with wire ties before the
electronic assembly is installed.
Secure cover on subpanel.13.
Install the Intellimeter PC board assembly (See Figure 9.); Ensure electronic assembly is14.
a “-120” meter for 120/208 or a “-277” meter for 277/480 or “-346” meter for 346/600 Volt
service. Adjust tamper switch if necessary. Plug the three input connectors into the proper
headers labeled PL11, PL4 and PL5. Observe the keying of the connectors.
If a local display is to be used (“D” option), install display per Figure 9. Connect to PL13 as15.
shown before power is applied.
Reconnect power to the subpanel. Turn on the circuit breakers.16.

Page 6 of 117004-00054-A Rev A.indd 6/6/11
PULSE OUTPUT CONNECTIONS
The Intellimeter provides a KYZ output pulse for both the A dial and B dial kiloWatthours. These
pulses can be used for load profile or demand side management. Each output is a solid-state,
Form C, contact rated at 350V peak and 0.120A maximum.
The A-dial and B-dial pulses are output on PL1 and PL2, respectively. The following chart shows
the pulse values for the various models using Intellimeter 0.1A-secondary current transformers.
WITH INTELLIMETER 0.1A-SECONDARY CURRENT TRANSFORMERS
Model Kh for 100A Primary
(Wh/Pulse) Kh for 200A Pprimary
(Wh/Pulse) Kh for 400A Primary
(Wh/Pulse)
A(5)-120/B 1.2 2.4 4.8
AB(5)-120/B 1.2 2.4 4.8
AP(5)-120/B 10 20 40
ABP(5)-120/B 10 20 40
A(5)-277/B 2.4 4.8 9.6
AB(5)-277/B 2.4 4.8 9.6
AP(5)-277/B 20 40 80
ABP(5)-277/B 20 40 80
A(5)-346/B 3.36 6.72 13.44
AB(5)-346/B 3.36 6.72 13.44
AP(5)-346/B 30 60 90
ABP(5)-346/B 30 60 90
The multiplier for meters using 5A-secondary rated current transformers with 10-turn prewrap on
100:0.1 Intellimeter current transformers can be calculated by dividing the primary rating by 50.
WITH INTELLIMETER 5A-SECONDARY CTS WITH 10-TURN PRE-WRAP ON 0.1A-SECONDARY CTS
Primary Rating 600 800 1000 1200 1600 2000
Multiplier 12 16 20 24 32 40
The new pulse value is the Kh for the meter used times the multiplier for the 5A-secondary
current transformer used.
Full-load pulse rate output is calculated as follows:
Pulse Rate Max = VNx INx 3 VN= nominal voltage, IN= nominal current
Kh x MULT MULT = multiplier as shown in chart above
= 277 x 600 x 3 For 277/480 Volt service using 600:5 CTs
2.4 x 12
= 17,312.5 Pulses/Hr @ Full Scale of 498,600 Watts
The addition of a potential transformer will require division by a second multplier equal to the
value of the PT ratio (primary/secondary).

Page 7 of 117004-00054-A Rev A.indd 6/6/11
Dwg# 0902-00690-B Rev B
INPUT AND OUTPUT CONNECTORS (Connector Pin-outs)

Page 8 of 117004-00054-A Rev A.indd 6/6/11
LOAD CONNECTIONS (Single-Load Meters)
Dwg# 0902-00690-B Rev B

Page 9 of 117004-00054-A Rev A.indd 6/6/11
LOAD CONNECTIONS (Two-Load Meters)
Dwg# 0902-00690-B Rev B

Page 10 of 117004-00054-A Rev A.indd 6/6/11
Dwg# 0902-00690-B Rev B
PC BOARD ASSEMBLY

Page 11 of 117004-00054-A Rev A.indd 6/6/11
MAINTENANCE
Routine Maintenance
There are no required maintenance operations for the Intellimeters. However, qualified
personnel may wish to perform an annual inspection of wiring connections.
Cleaning
The meters are not suitable for hose-down cleaning. Use only a damp cloth to remove dust
or dirt from the outside of the enclosure.
REPAIRS
It is not recommended that field personnel replace any of the internal components, including
fuses. If it is necessary to replace an Intellimeter, qualified personnel should follow the
procedure below:
Have replacement board available before starting procedure.1.
Disconnect power from the metered load and the meter.2.
Remove the cover from the Intellimeter enclosure.3.
Unplug the connectors. (Intellimeter current transformers have internal electronic4.
shorting switches and will not be damaged by being left in an open-circuit condition.)
Replace the electronic assembly (Refer to installation instructions on page 4).5.
Return the electronics assembly to the dealer or distributor from whom it was purchased6.
for replacement.
REFERENCES
The following documents may be useful when installing an Intellimeter unit:
Intellimeter Field Programming Instructions (Document 7004-00022-A)1.
Intellimeter A and AB Specification Sheet (7004-00046-A)2.
Intellimeter ABP Specification Sheet (7004-00053-A)3.
Intellimeter Installation Data Sheet (Document 7004-00083-A)4.
This manual suits for next models
31
Table of contents
Other OSC Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Veeder-Root
Veeder-Root Mag-FLEX installation manual

Ursalink
Ursalink AM100 Series user guide

Agilent Technologies
Agilent Technologies MXA Series Installation note

GREISINGER
GREISINGER GMI 15 operating manual

Rexnord
Rexnord Smart Condition installation manual

Bender
Bender A-ISOMETER IR1570 Series operating manual