Panduit NET-ACCESS S-Type User manual

STOP
READ ALL OF THE FOLLOWING INSTRUCTIONS BEFORE
REMOVING CABINET FROM SKID
CM599L
N
ET
-A
CCESS
S-Type Server Cabinets
-Phillips screwdriver
-Flatblade screwdriver
-22mm socket wrench
-15mm socket wrench
-13mm socket wrench
-8mm socket wrench
-48” level
-7mm socket wrench
-T30 Torx bit
-T25 Torx bit
-6mm Allen key
-2.5mm Allen key
-Wire cutter
TOOL LIST

FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS CM599L
© Panduit Corp. 2016
Page 2 of 27
N
ET
-A
CCESS
S-Type Server Cabinets
(Server Configurations
)
Disclaimer:
The information contained in this manual is intended as a guide for use by persons having technical
skill at their own discretion and risk. The recommended practices are based on average conditions.
Panduit makes no representation or warranty, express or implied, nor assumes any responsibility for
the accuracy or completeness of these installation instructions. Panduit does not guarantee any
favorable results nor assume any liability for damages, improper installation, system failures, or any
other problems that could arise in connection with the use of these installation instructions.
NOTE: Some views in this document may vary
slightly from your actual cabinet configuration.

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 3 of 27
Safety Notes:
The maximum static weight load of the cabinet is 3000 lbs. [1361 kg]. The maximum weight load when
the cabinet is rolling on casters is 2500 lbs. [1134 kg]. The weight load should be evenly distributed
across the height of the cabinet, with the heaviest components mounted at the bottom of the cabinet.
The maximum weight load on the integral cabinet top cable routing system is 200 lbs. [91 kg].
The maximum weight load on the following shelves: RSHLF, RSHLF23, RSHLF36 is 275 lbs. [125 kg].
The maximum operating temperature is 50º C; so that the installer is able to determine acceptability of
use of accessories and components in the operating state.
The equipment shall be installed or serviced by trained service personnel in accordance with the appli-
cable requirements of the National Electric Code, ANSI/NFPA 70 or Canadian Electrical Code and the
applicable sections of ANSI C2, the National Electrical Safety Code. The instruction shall not result in
the risk of fire, electric shock, or injury to persons.
UL Listing covers enclosure cabinet only
IMPORTANT SAFETY INFORMATION
CABINET TIPPING HAZARD
This cabinet can easily be tipped. Use extreme caution when unpacking or moving the cabinet.
Use at least [2] persons to remove cabinet from pallet and move cabinet into position (refer to
page 5).
After the cabinet has been removed from the pallet, ensure that the leveling legs are in the fully-
retracted position (refer to pages 5-6) before rolling the cabinet on casters. It is recommended to
add at least 300 lbs. of equipment to the bottom 10 RU of the cabinet to provide extra stability
before rolling the cabinet.
When rolling the cabinet on its casters, gaps in the floor, including elevator thresholds, should be
covered with a rigid plate capable of bearing the cabinet’s load.
When rolling the cabinet on casters, push the cabinet from the front or rear only, to prevent
the cabinet from tipping on its side.
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN LEAD TO SERIOUS INJURY, DEATH, OR
DAMAGE TO YOUR EQUIPMENT.
WARNING

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 4 of 27
TABLE OF CONTENTS-NET ACCESS S-TYPE SERVER CABINETS
General Cabinet Operation
Packaging Material Removal ......................................................................................................... 5
Leveling.......................................................................................................................................... 6
Floor Mounting .............................................................................................................................. 7
Ganging (front of cabinet).............................................................................................................. 8
Ganging (rear of cabinet) ............................................................................................................... 9
Grounding .................................................................................................................................... 10
Equipment Rail Adjustment......................................................................................................... 11
Equipment Rails (Zero RU QuickNet™ Patching Adapter Installation)..................................... 12
Overhead Cable Openings............................................................................................................ 13
Cable Management Fingers (SN15F, SN25F) ............................................................................. 14
CCL3 - Combination Lock Swing Handle Installation................................................................ 15
Single Hinge Door (Removal and Installation)............................................................................ 16
Single Hinge Door (Door Handle Direction Reversal) ................................................................ 17
Rear Split Doors (Removal and Installation) ............................................................................... 18
Side Panel - (Distinguishing Features -- also reference instructions V00029CM)...................... 19
Hinged Side Panels (Removal/Installation and Adjustment - optional) ...................................... 20
PDU Bracket Adjustment............................................................................................................. 21
Cable Management/PDU Bracket Adjustment (optional)............................................................ 22
Cabinet Sealing ............................................................................................................................ 23
Front and Rear Floor Seal Installation (Vertical Exhaust Duct ONLY)...................................... 24
Top of Cabinet Cable Manager Installation ................................................................................. 25
Top of Cabinet Cable Manager Installation (for vertical exhaust ducts) ..................................... 26

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 5 of 27
[2] M14 Hex Nuts
(use 22mm socket wrench)
Front Door
Shipping
Brackets
[8] M10 Hex Head Screws
(use 15mm socket wrench)
Pallet
[4] Shipping
Hold Down
Brackets
Note: Doors, side panels, and other components are removed for clarity
IMPORTANT:
Leveling Legs must be fully retracted before the cabinet is moved into place. Sliding cabinet on leveling legs may result in
damage to the leveling legs. (Leveling Legs ship in retracted position)
Packaging Material Removal
“Shipping Hold Down Bracket” Doubles as Floor Mounting Bracket. Retain bracket if floor mounting is desired. (see Page 7)
• Remove all stretchwrap and protective cardboard from outside of cabinet
• Remove all Shipping Brackets (if necessary)
• Remove [4] Hold Down Brackets at front and rear of cabinet
• Use at least [2] persons to carefully lift and remove cabinet from pallet

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 6 of 27
Front-to-Back Cabinet Leveling
Side-to-Side Cabinet Leveling
Leveling
• Ensure that [4] Leveling Legs are fully retracted
• Slide Cabinet into final position
• Lower the [4] Leveling Legs until the cabinet weight is fully supported by only the leveling legs
• Adjust the [4] Leveling Legs so that the cabinet is level front-to-back and side-to-side
Note: When ganging multiple cabinets together, ensure that adjacent cabinets are adjusted to the same height.
[4] Leveling Legs
(use 6mm Allen Key)
6mm Allen Key
Clockwise to RAISE cabinet
Counter-clockwise to LOWER cabinet
[4] Leveling Legs

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
159mm
[6.26”]
DIM A
2X 216mm
[8.50”]
DIM B
4X 14mm DIA
[0.55”]
Page 7 of 27
Floor Mounting
• Ensure that [4] Leveling Legs are fully retracted
•If Necessary, secure [4] “Shipping Hold Down Brackets” at front and rear of cabinet
• See Floor Mounting View below for floor mounting dimensions
[4] M10 Hex Head Screws
(use 15mm socket wrench)
Floor Mounting View
DIM A:
-1070mm deep cabinets: 726mm [28.58”]
-1200mm deep cabinets: 878mm [34.57”]
[4] Shipping
Hold Down
Brackets
DIM B:
-600mm wide cabinets: 191mm [7.52”]
-700mm wide cabinets: 241mm [9.48”]
-800mm wide cabinets: 291mm [11.46”]
CABINET TIPPING HAZARD
Mount cabinet to floor before equipment is installed in cabinet.
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN LEAD TO SERIOUS INJURY, DEATH, OR DAMAGE TO YOUR EQUIPMENT.
WARNING

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 8 of 27
IMPORTANT:
Ensure cabinets are level by following the guidelines on page 6. Leveling the cabinet prior to
ganging is important to ensure proper door operation.
Ganging (front of cabinet)
• Ensure cabinets are level
• Secure Ganging Brackets to cabinets at [2] front locations shown below
[2] Front Ganging
Brackets
[4] M6 Torx Screws
(use T25 Torx bit)
FRONT OF CABINETS
CABINET TIPPING HAZARD
Ganging of cabinets only provides limited stability to the cabinets, and is not a substitute for proper leveling or floor mounting of cabinets.
Ensure that cabinets are properly mounted to floor before equipment is installed in cabinet. (See page 7)
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN LEAD TO SERIOUS INJURY, DEATH, OR DAMAGE TO YOUR EQUIPMENT.
WARNING

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 9 of 27
IMPORTANT:
Ensure cabinets are level by following the guidelines on page 6. Leveling the cabinet prior to
ganging is important to ensure proper door operation.
Ganging (rear of cabinet)
• Ensure cabinets are level
• Secure Ganging Brackets to cabinets at [2] rear locations shown below
• Do not use Ganging Brackets to cinch cabinets together
• Holes for screws are not tapped. Apply force to drive screws.
REAR OF CABINETS
[2] Rear Ganging
Brackets
[4] M5 Torx Screws
(use T25 Torx bit)
CABINET TIPPING HAZARD
Ganging of cabinets only provides limited stability to the cabinets, and is not a substitute for proper leveling or floor mounting of cabinets.
Ensure that cabinets are properly mounted to floor before equipment is installed in cabinet. (See page 7)
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN LEAD TO SERIOUS INJURY, DEATH, OR DAMAGE TO YOUR EQUIPMENT.
WARNING

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 10 of 27
[6] Grounding Lug Locations
(Front and Rear of Beams)
Grounding
• Attach Grounding Lug or Grounding Bar to Common Bonding Network (CBN) at any of the [6] location(s) shown below
• Grounding location is indicated by universal ground symbol near grounding lug locations
• Remove factory-installed masking tape at grounding lug location to expose unpainted surface of cabinet frame. Grounding lug or
grounding bar must assembled onto this unpainted surface (per NEC NFPA 70 Article 250.12)
• Use [2] M5 bonding screws to fasten grounding terminal to cabinet frame (torque screws to 5.1 N-m (45 in-lb)
Note: top cap removed for clarity.
Masking Tape
Masking Tape
ELECTRICAL SHOCK HAZARD
Each cabinet must be connected to the Common Bonding Network (CBN).
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN LEAD TO SERIOUS INJURY, DEATH, OR DAMAGE TO YOUR EQUIPMENT.
DANGER

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 11 of 27
Equipment Rail Adjustment
• Loosen M10 Hex Head Screw at top and bottom of rear equipment rail
• Adjust equipment rail to desired positon
• Tighten M10 Hex Head Screw to 30.0 +/- 5.0 N-m [22.1 +/- 3.7 Ft-lbs]
NOTE: Front equipment rails are in a fixed position
Uninstall/Re-install and Move Equipment Rails (Top and Bottom Locations)
• Remove [2] M10 Hex Screws at top and bottom of Equipment Rail
• Remove [2] Equipment Rail Mount Nuts through slots of Front-to-Back Beam
•REVERSE STEPS to re-install Equipment Rails (insert Equipment Rail Mount Nuts through slots of Front-to-Back beam while holding
finger grip of mount nut; ensure that barbed surface of Equipment Rail Mount Nut faces outside of cabinet)
TOP AND BOTTOM
M10 Hex Head Screw
(use 15mm socket wrench)
UNINSTALL/RE-INSTALL AND MOVE EQUIPMENT RAILS
M10 Hex Head Screw
(use 15mm socket wrench)
Equipment Rail
Mount Nut
Slot of Front-to-Back Beam
Equipment Rail
Mount Nut
(Finger Grip Area)
Barbed Surface
(face to outside
of cabinet)
FALLING EQUIPMENT HAZARD
Remove all equipment installed onto equipment rails before performing any adjustments to equipment rail spacing.
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN LEAD TO SERIOUS INJURY, DEATH, OR DAMAGE TO YOUR EQUIPMENT.
WARNING

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 12 of 27
Equipment Rails (Zero RU QuickNet™ Patching Adapter Installation)
• Insert plastic Patching Adapters by snapping adapter into rear-facing surface of rear equipment rails.
• Patching Adapters accommodate Panduit QuickNet™ Copper and Fiber Cabling Systems (optional)
• Included on select 600mm wide S-Type cabinet configurations
Insert Patching Adapters
(snap into equipment rails)

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Removable Insert
Overhead Cable
Opening Bezel
Page 13 of 27
Overhead Cable Openings
• Remove Bezel Insert to allow for overhead cable entry
• Cut [8] tabs with wire cutter to open large cable openings - OPTIONAL
• Install M10 threaded rod into [6] tapped holes for 1070mm deep cabinets or [9] tapped holes for 1200mm deep cabinets, if desired
• [2] 165.1mm x 165.1mm [6.5” x 6.5”] openings can be used to route power overhead
• PANDUIT
C
OOL
B
OOT
TM products can be used to seal around cables/fiber to prevent hot air recirculation
[6] M10 Threaded Holes
Bezel
OPTIONAL
use wire cutters to remove
sheet metal blanks.
[2] 165.1mm x 165.1mm Openings
[6.5” x 6.5”]

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 14 of 27
Cable Management Fingers (SN15F, SN25F)
• Insert tabs of Cable Management Finger into mounting slots of cabinet post
• Slide Cable Management Finger inward to lock into place
Cable Managment Finger
-Insert tabs into cabinet post
-Slide inward to lock in place

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
CCL3 - Combination Lock Swing Handle Installation
Combination Lock Swing Handle Operation
• Default combination: “0,0,0”
• Set [3] dials to correct combination, or use key to open handle
SET NEW COMBINATION
• Open swing handle
• Rotate handle insert counter-clockwise 30º (from unlocked position) or
210º (from locked position)
• Set [3] dials to desired combination
• Return handle insert to original position
• Close swing handle
[3] Dials
Handle Insert (from unlocked)
(rotate counter-clockwise 30º
from unlocked position to set
new combination)
Handle Insert (from locked)
(rotate counter-clockwise 210º
from locked position to set new
combination)
NOTE
Entire handle assembly
must be removed from door
prior to installation of CCL3
Page 15 of 27

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 16 of 27
Single Hinge Door (Removal and Installation)
•VIEW 1 Pull down Compression Sleeve at top door hinge
•VIEW 1 Pull Single Hinge Door away from cabinet so that Top Hinge Screw fits through cutout of door
•VIEW 2 Lift bottom of door off Bottom Hinge Pin
Compression Sleeve (Pull down)
Top Hinge Screw
Bottom Hinge Pin
VIEW 1
VIEW 2
VIEW 3
Plastic Washer

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 17 of 27
Top Hinge Bracket
[2] M5 Torx Screw
(use T25 Torx bit) Bottom Hinge Bracket
M6 Torx Screw
(use T30 Torx bit)
[2] Hex Nuts
(use 8mm socket wrench)
PANDUIT Label
Door
Handle
Backing
Plate
Door Handle
(rotate 180º)
VIEW 1
VIEW 2
VIEW 6
VIEW 5
Door Catch
VIEW 3
Door Cam
(reposition to
outside edge
of door)
Single Hinge Door (Door Handle Direction Reversal)
•VIEW 1, 2 Remove Top and Bottom Hinge Brackets from current location (remove top hinge screw, if necessary)
•VIEW 1, 2 Install Top and Bottom Hinge Brackets on opposite side of cabinet (re-install top hinge screw, if necessary)
•VIEW 3 Move Door catch to opposite side of cabinet frame
•VIEW 4, 5 Remove Horizontal Grounding Bracket and reinstall on opposite side of door.
Door Handle Reversal (Lay door on a flat surface) - VIEW 5, 6
• Remove Door Handle Backing Plate and rotate position of Door Handle 180º
• Loosen Cam Screw to reposition Door Cam and Cam Stop to outside of door. Tighten Cam Screw
• With Door Handle repositioned, secure Door Handle Backing Plate to Door Handle
• Remove PANDUIT label and re-attach in correct orientation near top of door
• Reinstall Single Hinge Door per instructions on Page 15
VIEW 4
M5 Torx Screw
(use T25 Torx bit)
Horizontal
Grounding
Bracket

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 18 of 27
Rear Split Doors (Removal and Installation)
• Open Rear Split Doors to approximately 90º
• Lift Rear Split Doors up pull doors away from cabinet frame
•REVERSE STEPS to install Rear Split Doors

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 19 of 27
Side Panel - (Distinguishing Features -- also reference instructions V00029CM)
CURRENT VERSION
Backstop feature
on bottom beam
CURRENT VERSION
[2] Adjustable
bushings
ORIGINAL VERSION
No backstop feature
on bottom beam
ORIGINAL VERSION
[2] Plastic
bushings
ORIGINAL VERSION
Overlapping flange
on rear side panel
(outside)
CURRENT VERSION
Overlapping flange
on front side panel
(inside)
Original Cabinet Current Cabinet
S21SPS, S22SPS, S51SPS, S52SPS
S81SPS, S82SPS, S11SPS, S12SPS
S21SPSE, S22SPSE, S51SPSE, S52SPSE
S81SPSE, S82SPSE, S11SPSE, S12SPSE
MUST USE THESE
PART NUMBERS:
MUST USE THESE
PART NUMBERS:

INSTALLATION INSTRUCTIONS
For Technical Support: www.panduit.com/resources/install_maintain.asp
CM599L
© Panduit Corp. 2016
Page 20 of 27
Hinged Side Panels (Removal/Installation and Adjustment - optional)
• Pull [2] Spring Loaded Hinge Pins to release Rear Side Panel from cabinet frame
• Pull [4] Spring Loaded Hinge Pins to release Front Side Panel from cabinet frame
•REVERSE STEPS to install In-Row Side Panels
IMPORTANT: Install Front Side Panel First
Spring Loaded Hinge Pin
(Top and Bottom)
Move Finger Pull into
Slot to Lock Hinge Pin
in OPEN position
Spring Loaded Hinge Pins
[2] Locations
Front Side Panel
Adjust Fit of Side Panels
Use included wrench to raise
or lower adjustment bushings
Rear Side Panel
Spring Loaded Hinge Pins
[2] Locations
Adjustment
Bushing
Adjustment
Wrench
(included)
Side panels removed
from view to add clarity
Table of contents
Other Panduit Server manuals
Popular Server manuals by other brands

CyberData
CyberData 11146 Operation guide

NEC
NEC NECCare Gold Express5800/320Fd Service manual

Stratus
Stratus ftServer 2900 Series Planning and installation guide

Lenovo
Lenovo ThinkServer TS430 warranty and support information

Hitachi
Hitachi DS225 Hardware guide

Lantronix
Lantronix xPico XPW100A003-01-B Integration guide