Parkray Inset Chevin 20B User manual

JINCHW09 Rev A 12/05/14
Inset Chevin 20B
Installation and Operating Instructions

JINCHW09 Rev A 12/05/14
Inset Chevin 20B
Technical Specification
INSET CHEVIN 20B
Trevilla Park, Slaughterbridge,
Camelford, Cornwall, PL32 9TT
BS/EN 13229
UKAS# 0692
Stove Mass: 127.67kg
NOMINAL OUTPUT: 15.8KW
NOMINAL OUTPUT TO WATER: 10.7KW
NOMINAL OUTPUT TO SPACE: 5.1KW
CO Emission at 13% O2: 0.33%
Mean Flue Gas Temperature: 385°C
EFFICIENCY: 69.9%
Flue Gas Mass Flow: 14.1g/s
Maximum operating water temperature in °C: 100°C
Maximum operating pressure in bar: 1.2Bar
Minimum clearance to combustible material
Top of Fire Surround:
150mm
Side of Fire Surround:
75mm
Side Wall:
200mm
This appliance is suitable for intermittent burning
This appliance is not suitable for use in a shared flue
Read and follow the operating instructions
Use only recommended fuels
14

JINCHW09 Rev A 12/05/14
General Guidance
It is important that your stove is correctly
installed as Parkray Ltd cannot accept
responsibility for any fault arising through
incorrect use or installation.
These instructions cover the basic principles to
ensure satisfactory installation of the stove,
although detail may need slight modification to
suit particular local site conditions.
The installation must comply with current Building
Regulations, national and European standards,
Local Authority byelaws and other specifications
or regulations as they affect the installation of the
stove.
The Building Regulations requirements may also
be met by adopting the relevant
recommendations in the current issues of British
Standards BS 8303 and BS EN 15287-1.
COMPETENT PERSONS SCHEME
Parkray Ltd recommend that this stove is installed
by a member of an accredited competent persons
scheme e.g. HETAS.
If the installer is not a member of a competent
persons scheme, it is a legal requirement to notify
your local building control body in advance of any
work starting.
CO ALARMS
Building regulations require that whenever a new
or replacement fixed solid fuel or wood/biomass
appliance is installed in a dwelling, a carbon
monoxide alarm must be fitted in the same room
as the appliance.
Further guidance on the installation of the carbon
monoxide alarm is available in BS EN 50292:2002
and from the alarm manufacturer’s instructions.
Provision of an alarm must not be considered a
substitute for either installing the appliance
correctly or ensuring regular servicing and
maintenance of the appliance and chimney
system.
HEALTH AND SAFETY PRECAUTIONS
Special care must be taken when installing the
stove such that the requirements of the Health
and Safety at Work Act are met.
HANDLING
Adequate facilities must be available for loading,
unloading and site handling.
FIRE CEMENT
Some types of fire cement are caustic and should
not be allowed to come into contact with the skin.
In case of contact, wash immediately with plenty
of water.
ASBESTOS
This stove contains no asbestos. If there is a
possibility of disturbing any asbestos in the course
of installation then please seek specialist guidance
and use appropriate protective equipment.
METAL PARTS
When installing or servicing this stove, care should
be taken to avoid the possibility of personal injury.
MODIFICATION
No unauthorized modification of this appliance
should be carried out.
Safety
WARNING –This appliance will be hot when in
operation and due care should be taken. The
supplied gloves may be used to open the door
and operate the air controls.
AEROSOLS
Do not use an aerosol spray on or near the stove
when it is alight.
FIREGUARDS
Always use a fireguard in the presence of children,
the elderly or the infirm. The fireguard should be
manufactured in accordance with BS8423 –
Fireguards for use with solid fuel appliances.
DO NOT OVER-FIRE
It is possible to fire the stove beyond its design
capacity. This could damage the stove so watch
for signs of over-firing. If any part of the stove
starts to glow red, the stove is in an over-fire
situation and the controls should be adjusted
accordingly. Never leave the stove unattended for

JINCHW09 Rev A 12/05/14
long periods without first adjusting the controls to
a safe setting. Careful air supply control should be
exercised at all times.
FUME EMISSION
Properly installed, operated and maintained, this
appliance will not emit fumes into the dwelling.
The appliance door(s) must be kept closed at all
times, except for when de-ashing and refueling,
during which occasional fumes may occur.
However, persistent fume emission is potentially
dangerous and must not be tolerated.
If fume emission does persist, then the following
immediate action should be taken:-
1. Open doors and windows to ventilate the
room and then leave the premises.
2. Let the fire go out.
3. Check for flue or chimney blockage and
clean if required.
4. Do not attempt to re-light the fire until
the cause of the fume emission has been
identified and corrected. If necessary,
seek expert advice.
The most common cause of fume emission is flue
way or chimney blockage. For your own safety
these must be kept clean at all times.
Adverse weather –In a small number of
installations, occasional weather conditions (e.g.
wind from a particular direction) may cause
downdraught in the flue and cause the stove to
emit fumes. In these circumstances, the stove
should not be used. A professional flue installer
will be able to advise on solutions to this problem
(e.g. anti-downdraught cowl).
CO ALARM
Your installer should have fitted a CO alarm in the
same room as the appliance. If the alarm sounds
unexpectedly, follow the instructions given under
“Warning Note” above.
DO NOT FIT AN EXTRACTOR FAN IN THE SAME
ROOM AS THIS APPLIANCE.
IN THE EVENT OF A CHIMNEY FIRE -
Raise the alarm
Call the Fire Brigade
Close appliance air controls
Move furniture, ornaments etc away
Place a fireguard in front of stove
Check the chimney breast for signs of excessive
heat.
If the wall is becoming excessively hot, move
furniture away. Ensure the Fire Brigade can gain
access to your roof space in order to check for fire
spread.
Installation
APPLIANCE DIMENSIONS
AIR SUPPLY
The room or space containing this appliance
should have purpose provided ventilation (where
necessary) in accordance with Building
Regulations.
Due consideration should be given to air
requirements for any other appliance in the same
room or space.
Any air opening must be kept clear from blockage
or obstruction.
APPLIANCE OPENING
This stove must be fitted on a hearth or base with
adequate load-bearing capacity.
The opening into which this stove is fitted should
be constructed wholly from non-combustible
materials. The dimensions of the opening should
be at least those shown in the diagram.

JINCHW09 Rev A 12/05/14
This appliance will fit into a standard 16” fireplace
opening if the clay fire back is removed.
Any non-combustible walls within 50mm of this
appliance should be at least 200mm thick and
should extend at least 30mm above the top of
the appliance and at least 1.2 metres above the
hearth. Any walls more than 50mm from the
appliance may be reduced to a thickness of
75mm. Ensure the inter-connecting flue pipe also
has adequate clearances to combustible
materials
The walls surrounding the stove will become hot
and should therefore be finished in a heat
resistant plaster.
Do not hang pictures, plasma screen televisions
or ornaments above the stove, as these could be
damaged and could potentially create a fire
hazard.
Please check the suitability of any fireplace /
surround for closed solid fuel appliances before
installation. Parkray Ltd cannot be held
responsible for any fault arising through incorrect
use or installation. Fire surround back panels
suitable for solid fuel are usually in three sections
and slabbed. Many fire surrounds are suitable
only for gas and electric fires and therefore not
suitable for solid fuel.
HEARTH REQUIREMENTS
A constructional hearth with a minimum thickness
of 120mm should be provided. This constructional
hearth should extend to at least 244mm in front
of the stove and 121mm at the sides
The constructional hearth should be made of solid
non-combustible material and can include any
solid non-combustible floor. The boundary of the
hearth must be clearly marked. This can be done
by adding a super-imposed hearth on top of the
constructional hearth –e.g. a slate slab on top of a
solid concrete floor.
FLUE REQUIREMENTS
The flue serving this appliance must be dry, free
from cracks and obstructions and be in accordance
with relevant standards.
The diameter of the flue should not be less than
150mm and not more than 200mm.
If these requirements are not met the chimney
should be lined by a suitable method.
If there is no existing chimney then either a
prefabricated block chimney in accordance with
Building Regulations Approved Document J or a
twin-walled insulated stainless steel flue to BS EN
1856 can be used. These chimneys must be fitted
in accordance with the manufacturer’s instructions
and Building Regulations.
The chimney/flue should have a vertical height of
at least 4.5 meters and should terminate in
accordance with Table 1.

JINCHW09 Rev A 12/05/14
If the chimney is believed to have previously
served an open fire installation, it is possible that
the higher flue gas temperature from the stove
may loosen deposits that were previously firmly
adhered, with the consequent risk of flue
blockage. It is therefore recommended that the
chimney is swept a second time within a month of
regular use after installation.
If you have any doubts about the suitability of
your chimney, consult your local dealer/stockist.
Both the chimney and flue pipe must be
accessible for cleaning and if ANY part of the
chimney cannot be reached through the stove
(with baffle removed), a soot door must be fitted
in a suitable position.
FLUE DRAUGHT
If the draught exceeds the recommended
maximum, a draught stabiliser must be fitted so
that the rate of burning can be controlled and to
prevent over firing.
If the reading is less than the recommended
minimum then the performance of the appliance
will be compromised.
The flue draught should be checked under fire at
high output.
Minimum Draught –1.2mm Water Gauge
Maximum Draught –2.5mm Water Gauge
CLEARANCES TO COMBUSTIBLE MATERIALS
Excluding some fire surround installations (see
below) there should be no combustible material
within 200mm of either side of the stove or
275mm above.
No combustible furniture should be placed any
closer than 700mm from the front of the stove.
FIRE SURROUNDS
Please check the suitability of any
fireplace/surround for closed solid fuel appliances
before installation.
Parkray Ltd cannot be held responsible for any
fault arising through incorrect use or installation.
Fire surround back panels suitable for solid fuel
are usually in three sections and slabbed. Many
fire surrounds are suitable only for use with gas
and electric fires and therefore not suitable for
solid fuel.
Terminal
Position
Clearances to Flue
Outlet
a
At or within
600mm of the
ridge
At least 600mm above the ridge
b
Elsewhere on a
roof (whether
pitched or flat)
At least 2300mm horizontally
from the nearest point on the
weather surface and:
a) At least 1000mm above the
highest point of intersection of
the chimney and the weather
surface or
b) At least as high as the ridge
c
Below (on a
pitched roof) or
within 2300mm
horizontally to an
openable roof
light, dormer
window or other
opening.
At least 1000mm above the top
of the opening.
d
Within 2300mm of
an adjoining or
adjacent building,
whether or not
beyond the
boundary.
At least 600mm above any part
of the adjacent building within
2300mm
Table 1 –Flue Terminal Positions

JINCHW09 Rev A 12/05/14
A combustible fire surround with a depth of up to
100mm requires a minimum clearance of 75mm
from the side of the stove. For combustible fire
surrounds with a depth in excess of 100mm this
clearance must be increased to 200mm.
Removing Internal Components
All internal components must be removed prior
to fitting the stove. This will make handling the
stove easier; allow access to fixings and the flue
outlet; as well as protect the internal
components from damage during the installation
process.
1. Open the door(s) and remove the ashpan.
2. Remove the fuel retainer by lifting off of its
supports and remove from firebox.
3. Remove the catch bar (front plate) by lifting
until the widest section of the keyhole slots
are in line with the catch bar supports. Then
pull forward until clear of the supports and
remove.
Catch Bar / Front
Plate Support

JINCHW09 Rev A 12/05/14
4. Remove the bricks by sliding forward so they
are clear of their supports and tilting the
bottom edge into the fire box.
5. Remove the grate bars by lifting the front up
off the cam bar and sliding forward off the
rear grate support and lifting out of the
firebox. Repeat with remaining grate bars.
6. Remove the baffle by sliding it forward until it
reaches its stop. Then lift and slide forward
until clear of its supports and lower into the
firebox.

JINCHW09 Rev A 12/05/14
Installing the Stove
1. Check positions of pipe connections.
2. Make suitable access holes so you can access
the tapings and infill with vermiculite
concrete.
3. Apply fire cement around the rope seal. This
will help seal the stove when in position.
4. Move the stove into position inside the
fireplace opening, being careful not to
damage the hearth or paintwork on the stove
and making sure that the rope seal is
compressed forming a tight seal between the
stove and fireplace.
5. Connect the boiler –see ‘Installation of boiler
models’.
6. Fill the boiler and check for leaks.
7. Connect the flue –see ‘Flue connection’.
8. Infill the stove with vermiculite concrete.
9. Fill in the access for the boiler pipe
connections.
10. Fill in the top access.
11. Drill hole into hearth through base using a
10mm drill bit.
12. Position anchor bolt provided through base
plate and fix stove in place.
INSTALLATION OF HEATING &HOT WATER SYSTEM
We strongly recommend that a knowledgeable,
experienced and qualified plumbing and heating
engineer is responsible for the design and
installation of the heating and hot water system.
Parkray Ltd cannot accept responsibility for any
consequential loss, however caused, due to under
or over specification of the appliance in any
installation.
Do Not –Under any circumstances connect the
stove to a sealed (pressurised)
heating system or unvented hot water
cylinder.
Do Not –Link the stove into a heating or hot
water system with an existing boiler
without the use of suitable equipment
such as a neutralizer. When fitting this
type of system the neutralizer
manufacturer’s instructions must be
followed.
Do –Fit an open cold feed and expansion
cistern with separate cold feed and
vent pipes. The cold feed and vent
pipes must be unvalved. The open vent
pipe should have a diameter of 22mm
and rise continuously from the boiler.
It is common practice to form the vent
pipe from an extension of the primary
flow (see diagram).
Do –Connect the stove to a double feed,
indirect hot water cylinder via 28mm
copper flow and return pipework,
rising continuously from the boiler to
the cylinder. The cylinder and heat leak
radiator must be sited higher than the
stove.
Semi pumped systems should be used on heating
and hot water systems with gravity circulation to
the hot water cylinder and one unvalved 2 KW
radiator to act as a heat leak when the central
heating is switched off.
All four tappings on wraparound boilers should be
used for systems incorporating separate gravity
and pumped heating loops. Each flow and return
should be taken from diagonally opposite sides of
the boiler.

JINCHW09 Rev A 12/05/14
If a common flow and return is used, these should
also be taken from diagonally opposite sides of
the boiler, and plugs inserted into the sockets not
used.
Systems using a common flow and return to the
boiler should incorporate an injector tee on the
primary return connection from the central
heating pump (see diagram).
A HIGH LIMIT thermostat should be fitted to the
gravity flow pipe close to the boiler and set at
90°C. This should override any pump control,
switching the pump on and dissipating any excess
heat around the radiator circuit.
To prevent boiler corrosion due to condensation it
is necessary to maintain the return water
temperature above 45°C. This can be achieved by
the use of a LOW LIMIT thermostat on the return
pipe from the hot water cylinder, close to the
boiler. The thermostat should make on
temperature rise, preventing the circulating pump
from operating until the gravity circuit is up to
temperature.
FLUE CONNECTION
N.B. An adjustable flue bend may be required for
some installations.
If connecting to a stainless liner, a proprietary
single wall flue adaptor will be required. It is
recommended that a short length of flue pipe is
connected before the liner.
If connecting to an existing masonry chimney it is
recommended that a flue forming pipe (short
length of flue pipe) is used and the void between
the flue forming pipe and the chimney is filled with
vermiculite concrete.
A suitable access hole will need to be made in the
chimney breast to allow the back filling to be
carried out and then filled and sealed once the
installation is complete.
Alternatively a connection can be made using a
register plate although it will be necessary to allow
access for fitting the flue pipe to the register plate,
infilling with vermiculite concrete and sealing all
joints.
RE-ASSEMBLING THE STOVE
Refit all the internal parts by following the
‘removing internal components’ instructions in
reverse orders.

JINCHW09 Rev A 12/05/14
Room Thermostat
High Limit
Thermostat
90°C
Circulating Pump
Low Limit Thermostat (45°C)
Time Switch
Drain Cock
Injector Tee
Room Thermostat
High Limit
Thermostat
90°C
Circulating Pump
Low Limit Thermostat (45°C)
Time Switch
Drain Cock
Wiring Diagram for general guidance only
All electrical work must be carried out by a competent
electrician in accordance with the rules in force and the
instructions provided by the circulating pump and
heating controls manufacturer
Two Tapping System
Four Tapping System

JINCHW09 Rev A 12/05/14
Commissioning and Handover
Upon completion of the installation, allow a
suitable period of time for any fire cement and
mortar to dry out. A small fire may then be lit and
checked to ensure the smoke and fumes are taken
from the stove up the chimney and emitted safely
to atmosphere. Do not run the stove at full output
for at least 24 hours.
On completion of the installation and
commissioning, ensure that the operating
instructions and operating tools for the stove are
left with the customer. Advise the customer on
the correct use of the appliance with the fuels
likely to be used on the stove and warn them to
use only the recommended fuels for the stove.
Advise the user on what to do should smoke or
fumes be emitted from the stove.
The user should be warned to use a fireguard to BS
6539 in the presence of children, aged and/or
infirm persons.
Operating Instructions
Read the ‘General Guidance’ Section at the start
of these instructions before operating your stove
for the first time.
Allow sufficient clearance between the stove and
pictures, plasma screen televisions or ornaments
etc, as these could be damaged and could
potentially create a fire hazard (For more
information read the ‘Material Clearance’ section
of these installation instructions).
WARNING –This appliance will be hot when in
operation and due care should be taken. The
supplied operating tool or gloves may be used to
open the door and operate the air controls.
AEROSOLS
Do not use an aerosol spray on or near the stove
when it is alight.
AIR CONTROLS
Installed and used correctly this stove will burn
cleanly and efficiently. Therefore, to avoid the
disappointment of poor performance, please
familiarize yourself with the controls and their
recommended settings before use.
THERMOSTAT
The thermostat is controlled by the knob on the
side of the stove with settings from 0 - 10. The
thermostat generally operates between 50° to 90°.
Experiment with the settings to find the desired
temperature.
SECONDARY AIR
Secondary air is controlled via the slider above the
door(s), it is this “Airwash” that keeps a clean and
uninterrupted view of the fire.
LOCOMOTIVE GRATE
Your Parkray Ltd Stove is fitted with a locomotive
type grate. So that de-ashing can be carried out
cleanly and easily, it is riddled from the outside of
the stove with the doors closed.
SHUT
OPEN

JINCHW09 Rev A 12/05/14
BAFFLE OPERATION
Your Parkray Ltd Stove if fitted with a sliding
baffle. The baffle needs to be slid into its open
position when lighting and re-fuelling your stove.
This will prevent spillage while the stove door is
open.
To slide the baffle forward you will need to use the
tool provided. Hook the tool onto the tab at the
front of the baffle and pull forward until it hits the
stop. This will create a 30mm gap at the back of
firebox.
The baffle will automatically slide back into its
closed position when the door is closed. This is
achieved by the door pushing onto the fixing on
the baffle arm.
LIGHTING
We recommend that you have two or three small
fires before you operate your stove to its
maximum heat output. This is to allow the paint
to cure in steadily and to give a long service life to
the paint finish. During this curing in process you
may notice an unpleasant smell. It is non-toxic,
but for your comfort we would suggest that
during this period you leave all doors and
windows open.
Slide the baffle into its open position (see Baffle
Operation) and open secondary air control fully
and light one or two firelighters placed centrally
on the grate, allowing the flames to become
established before placing several pieces of small
dry kindling in a criss-cross fashion above the
firelighters, taking care not to smother the fire.
Close the stove door. Once the kindling is well
alight open the door and build the fire by gradually
adding fuel, closing the door afterwards.
Once the fire is established gradually close the
secondary air control until around 20% open
(slide control to your left) and add more fuel as
necessary.
Should the fire fail to light correctly open the door
and use a poker to spread the fuel across the
bottom of the firebox. Close the door and allow
the fuel and stove to cool before attempting to
relight the fire.
When the stove is up to operating temperature
the operating tool or gloves should be used to
operate the air controls.
REDUCED COMBUSTION
In order to shut down the stove, reduce the
thermostat control to ‘0’ and close the secondary
air by sliding control to the left.
If the controls are left in this position, the fire will
be starved of air and will die down.
If you want to revive the fire it is recommended
that the thermostat control is opened first, and
then the secondary air control.
Warning!- The stove will remain hot for a
considerable time after the fire has been
extinguished.
Baffle in Closed
Position. Hook
Tool on Tab.
Baffle in Open Position.
Slide Forward until
Stop.
Baffle Arm.

JINCHW09 Rev A 12/05/14
REFUELLING
When the fuel has burnt down to the fire bed, add
new fuel. The air controls should not need
adjusting while refuelling.
When refuelling it is important to slide the baffle
into its open position to reduce any spillage. (see
Baffle Operation) The baffle will be hot when
refuelling so due care should be taken.
RECOMMENDED FUELS
Parkray Ltd recommends that approved smokeless
fuels are burnt in this appliance.
Only authorised smokeless fuels may be used in
smoke control areas.
Warning! - Petroleum coke fuels or household
waste must not be burnt on this appliance. This
appliance must not be used as an incinerator.
Burning wet or unseasoned wood will create tar
deposits in the stove and chimney and will not
produce a satisfactory heat output.
Should any difficulties arise over fuel quality or
suitability, consult your local approved coal
merchant or:
HETAS Ltd –Telephone 01242 673257 –
www.hetas.co.uk
Solid Fuel Association –Telephone 0800 600 000 –
www.solidfuel.co.uk
General Maintenance
Important! –In order to ensure continued
compliance with current Building Regulations and
Local Authority Byelaws, this appliance requires
regular maintenance of the following –
N.B. Refer to the ‘Removing Internal Components’
section of the installation instructions for details
on how to remove each component.
PERIODS OF PROLONGED NON-USE
If the stove is to be left unused for a prolonged
period, then it should be given a thorough clean to
remove ash and unburned fuel residues. To enable
a good flow of air through the appliance to reduce
condensation and subsequent damage, leave the
air controls fully open.
If the appliance has been unused for a long period,
such as during the spring and summer months, a
competent person should check the chimney for
potential obstructions before lighting the stove i.e.
get the chimney swept before the start of the
heating season.
AS NECESSARY
Baffle-This should be removed and cleaned at
least once a month to prevent any build up of soot
or fly ash that could lead to blocked flueways and
dangerous fume emission.
If the baffle is removed the chimney/flueway can
be swept through the appliance.
Stove body –the stove is finished with a heat
resistant paint and this can be cleaned with a soft
brush. Do not clean the stove whilst it is hot; wait
until it has cooled down. The finish can be
renovated with proprietary stove paint.
Glass Panel(s) - Clean the glass panel when cool
with proprietary glass cleaner.
Highly abrasive substances should be avoided as
these can scratch the glass and make subsequent
cleaning more difficult.
Wet logs on heated glass, a badly aimed poker or
heavy slamming of the door could crack the glass
panel.
The glass will not fracture from heat.
Firebricks -In normal use, these can last for many
years. It is possible however, to crack them if fuel
is continually jammed against them or if they are
frequently struck with a poker.
Check periodically for seriously cracked bricks,
which can be replaced with new, available from
your dealer.
Door Catch -The door catch may require
adjustment to maintain the door seal. To adjust
the catch, follow the procedure below;
Loosen the M6 grub screw.
Rotate the catch shaft one complete turn to
achieve the correct door operation.
Tighten the grub screw.

JINCHW09 Rev A 12/05/14
Rope - Check the rope around the door. If rope is
becoming detached, use Parkray Ltd rope glue to
reattach it. If the rope is in a poor condition, a
replacement rope kit may be ordered from the
Parkray Ltd spares range.
Chimney & Flueways - It is important that the
chimney, flueways and any connecting flue pipe
are swept regularly. This means at least once a
year for smokeless fuels and at least twice a year
for wood and other fuels.
The baffle will need to be removed from its
supports in order to sweep the chimney (see
‘Removing internal components’ instructions).
Only wire-centred sweeps’ brushes fitted with a
guide wheel should be used.
If it is not possible to sweep all parts of the
chimney through the appliance, ensure there is
adequate access to cleaning doors.
Seasonal use - If the appliance has been unused
for a long period of time, such as during the spring
and summer months, the chimney should be
checked for potential obstructions by a competent
person before lighting the stove.
Gaskets - all gaskets used on this appliance are
produced from a heat resistant material called
Manniglas. The glass gasket will have to be
replaced when a new piece of glass is fitted as the
gaskets become brittle after firing the stove. Over
time you may find that the gasket changes colour.
This is due to a reduction in the pigment used in
the manufacture of the product and no cause for
concern.
De-ashing –De-ashing should be carried out on a
regular basis to avoid a build up of ash and ensure
sufficient primary air flow. Empty the ashpan
regularly to prevent ash reaching the underside of
the great bars. When de-ashing ensure the
primary air channel at the front left of the stove is
clear of ash. If necessary this can be periodically
cleared with a vacuum cleaner. The primary air
cover can be removed by undoing the two screws
if required.
Trouble Shooting
FIRE WILL NOT BURN
Check that –
Chimneys and flueway are clear.
A suitable fuel is being used.
There is an adequate air supply into the room.
An extractor fan is not fitted in the same
room.
Flue draught is above minimum level (see
installation instructions).
FIRE BLAZING OUT OF CONTROL
Check that –
The door is tightly closed.
The air controls are in the closed position.
A suitable fuel is being used.
The glass is not loose.
The door rope seal is in good condition.
Flue draught is below maximum level (see
installation instructions).

JINCHW09 Rev A 12/05/14
Spares Information
SINGLE DOOR SPARES
SINGLE DOOR
HCE09/008
DOOR HANDLE
AVA08/029MB
DOOR GLASS
HCE09/102
ROPE SEALING KIT
SCPCB900SDRSK
DOOR CATCH
ASSEMBLY
TDI05/ARRT/011MB
GLASS CLIP
HHR08/046
GLASS CLIP SCREW
FSJM05008SS
GLASS GASKET
HCE09/101

JINCHW09 Rev A 12/05/14
DOUBLE DOOR SPARES
LEFT HAND DOOR
RIGHT HAND DOOR
RIGHT HAND DOOR
HCE09/009
DOOR HANDLE
AVA08/020MB
DOOR GLASS
HCE09/031
GLASS GASKET
HCE09/030
DOOR CATCH
ASSEMBLY
AVI05/ARRT/0012MB
ROPE SEALING KIT
SCPCB900DDRSK
GLASS CLIP SCREW
FSJM05008SS
GLASS CLIP
HHR08/046
LEFT HAND DOOR
TDI05/008
GLASS CLIP
HHR08/046
GLASS CLIP SCREW
FSJM05008SS
ROPE SEALING KIT
SCPCB900DDRSK
GLASS GASKET
HCE09/030

JINCHW09 Rev A 12/05/14
BODY ASSEMBLY SPARES
SLIDER KNOB
HCE05/040M
BAFFLE
HCW09/ARRT/011
REAR GRATE SUPPORT
HCW09/ARRT/021
GRATE BARS
UPPER: 112/032
LOWER: 112/033
OPERATING TOOL
HFR07/040
ASHPAN
HCW09/ARRT/010
CATCH BAR
SINGLE DOOR:
HCW09/ARRT/017
DOUBLE DOOR:
HCW09/ARRT/018
FUEL RETAINER
HCW09/ARRT/025
HINGE PIN
FRRE08-1.75
HINGE
HH06/050
BRICK
LEFT: HCW09/051A
RIGHT: HCW09/051B
BAFFLE SUPPORT
HCW09/ARRT/013
CAM BAR
HCW09/ARRT/020
Table of contents
Popular Burner manuals by other brands

Riello
Riello RL 190 Installation, use and maintenance instructions

Riello
Riello RLS 28 Installation, use and maintenance instructions

Riello
Riello DB 4 LSM C13 Installation, use and maintenance instructions

WLD-TEC
WLD-TEC Flame 100 instruction manual

baltur
baltur TBL 105P instructions

Intertek
Intertek CIR-18 installation manual