manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. PEERLESS
  6. •
  7. Adapter
  8. •
  9. PEERLESS PUREFIRE PFA-1 User manual

PEERLESS PUREFIRE PFA-1 User manual

1
Peerless®PUREFIRE ®PFA-1 Interface Adapter
Installation, Operation and Maintenance Manual
A. OVERVIEW
The PFA-1 Interface Adapter is designed to allow for
electronic interface between the PureFire®main control
and other electronic devices.
1. Alarm Output:
In the event of a blocking or locking error, the PFA-1
Interface adapter will provide a contact closure to signal
an external device (alarm bell, phone dialer, etc.) of a
problem.
2. Analog Input:
The PFA-1 Interface Adapter will accept an analog input
of 0-10VDC. This analog signal can be used to control
Setpoint Temperature or Gas Input Rate. This signal is


required per cascade system to control the System
Setpoint. If Analog control of Gas Input is required, one
InterFace Adapter is required per boiler.
3. Modbus Interface:
The PFA-1 Interface Adapter allows external access to






equipped with a PFA-1 Interface Control to allow full

a. Temperatures: Supply, Return, DHW and Vent


(cascade) system can be accessed.
b. : The boiler status can be monitored to



water (DHW) demand.
c. : If the boiler is in a lockout or blocking
error, the interface will allow access to the error code.
B. PRE-INSTALLATION
1. PF-200, PF-210, PF-300, and PF-399 boilers come
equipped with pre-wired harnesses to connect to the
PFA-1 Interface Adapter. If modbus is required, two

as shown below.
2. To connect to the PF-50, PF-80, PF-110 or PF-140 boilers,
harnesses (supplied with the PFA-1 Interface Adapter)
are required.
3. For stand alone boilers, one PFA-1 Interface Adapter is

one PFA-1 Interface Adapter will provide Alarm


required, an interface unit is required for each of them.
 
the PureFire®boiler jacket. This manual will provide

C. INSTALLATION
 
PFA-1 Interface Adapter on the PF-50, PF-80, PF-110 and
PF-140 boilers.
• These boilers require a PFA-1 Harness Adapter Kit
(provided) to connect to the boiler.
 
PFA-1 Interface Adapter on the PF-200, PF-210, PF-300,
and PF-399 boilers.
• These boilers come with pre-wired harnesses for


connected as shown below.
 
backed Velcro provided with the kit.
PFA-1
1"
11/16"
1 1/2"
6"
INSIDE VIEW:
LEFT SIDE PANEL
Figure 1
PFA-1
2"
6"
2 1/2"
I
NSIDE VIEW:
LEFT SIDE OF BASE PANEL
Figure 2
D. ELECTRICAL -WIRING
 
PFA-1 Interface Board.
2. PF-200, PF-210, PF-300, and PF-399 boilers are
equipped with harnesses that provide power and

contact output to the boiler terminal strip. Connect
alarm to boiler terminal strip.
3. Analog Input (where used):
a. For the PF-200, PF-210, PF-300, and PF-399,
connect the analog input device to terminals
#15 (-) and #16 (+) on the boiler terminal strip
located behind the remote control display.
b. For the PF-50, PF-80, PF-110, and PF-140 boilers,
connect the analog input device to the red wires
from the J5 connector of the Interface Adapter.
Be sure that these wires are connected with the
proper polarity.
E. OPERATION -ALARM CONTACTS
Alarm Output:
a. The alarm output is a normally open dry contact. If an


b. This output can be used with either line voltage or 24
volts to power a lamp, buzzer, phone dialer or building
management system.
F. OPERATION -ANALOG INPUT
For external control of setpoint temperature or input rate
of a PureFire®Boiler, a 2-10 volt dc analog signal is to be
applied as shown in Figure 3 to the analog input wires.
1. Analog Input at Setpoint:
Input voltage below 2 volts dc will disable boiler

temperature of 60°F and 10 volts corresponds to a boiler
setpoint temperature of 200°F. Input voltage between 2
and 10 volts will result in a boiler setpoint temperature

temperature and the 10 volt temperature. For example,
an input of 6 volts will result in a boiler setpoint
temperature of 130°F.
2
PUREFIRE PFA-1 INTERFACE ADAPTER
If the Analog Input is not connected and there is no
connecon between the red and red/white Analog
Input wire, the default input voltage is 2.5 Vdc.
Therefore, the boiler will likely run without an Analog
Input signal. In this case, all of the standard limits and
safety switches will connue to funcon properly.
NOTICE
Figure 3: Electrical Wiring
PUREFIRE PFA-1 INTERFACE ADAPTER
3
2. Analog Input of Rate:
Input voltage below 2 volts dc will disable boiler

which will display as 1% Input on the RC Display (see

corresponds to maximum boiler input, and voltages in
between will linearly adjust the input rate.
G. OPERATION
-MODBUS INTERFACE
1. Modbus Conguraon:


2. Modbus Holding Registers:

16 bit holding registers). The PFA-1 Interface Adapter
organizes the data in read-only holding registers. Table

and the address of the holding registers. Depending on

addressing range starts at either 0x0000 or 0x0001.



Modbus Conguraon Specicaons
Protocol 
Default Address 
Supported Commands • Read Holding Registers (0x03)*
• Write Single Holding Register (0x06)
Baud Rate 9600 bps
Data Length 8 bits
Parity 
Stop Bits 1
Physical Layer RS485 (2 wire)
 J7-1
 J7-3
 8 Registers Per Frame
Table 1
Modbus Holding Registers (Read Only)
Item Index
Parameter Name
Address & Holding Registers
Notes
Word byte Range Start
0x0000
Range Start
0x0001
0 High byte 0STATE 0x0000 0x0001 See Table 3
0 Low byte 1 0x0000 0x0001 See Table 4
2 High byte 2 0x0002 0x0003 See Table 6A and 6B
2 Low byte 3 0x0002 0x0003 See Table 7
4 High byte 4 0x0004 0x0005
oC = byte value - 10
2
oF = oC x 9 + 32
5
4 Low byte 5 0x0004 0x0005
6 High byte 6 0x0006 0x0007
6 Low byte 7 0x0006 0x0007
8 High byte 8 0x0008 0x0009
8 Low byte 9 0x0008 0x0009
10 High byte 10  0x000A 0x000B —
10 Low byte 11  0x000A 0x000B —
12 High byte 12  0x000C 0x000D —
12 Low byte 13  0x000C 0x000D —
14 High byte 14  0x000E 0x000F —
14 Low byte 15  0x000E 0x000F —

Table 2



shown in Table 4.
4
PUREFIRE PFA-1 INTERFACE ADAPTER
The following example describes how to read the temperature holding registers (byte 4-7 and 14-15). The boiler supply and return



the formula above, this is equivalent to 1.5°C (35°F).
Table 3
Control State Descripons
STATE State Name Descripon
Decimal Hexadecimal
0 0x00  
1 0x01  
2 0x02  
3 0x03  
4 0x04  
5 0x05  
6 0x06  
7 0x07  
8 0x08  
9 0x09  Folllowing Boiler Demand
10 0x0A  
11 0X0B  
12 0x0C  
13 0x0D  
14 0x0E  
15 0x0F  
16 0x10  Error Handling
17 0x11  Error Handling
18 0x12  Controller (re)start
19 0x13  Error Handling
20 0x14  Error Handling
21 0x15  Error Handling
Table 4
Control State Descripons
STATE State Name Descripon
Decimal Hexadecimal
0 0x00  
14 0x0E  Error Handling
10 0x0A  Error Handling
15 0x0F  
16 0x10 CH 
17 0x11  
18 0x12  DHW Demand
19 0x13  
20 0x14  
21 0x15  DHW Demand (Store Warm Hold)
5
PUREFIRE PFA-1 INTERFACE ADAPTER








communicated.
Determinaon of General Control Status
Control Status STATE
Value
ERROR_NUMBER
Value
Control is not
 0x00 0x00

  0xFF

Correctly with Errors  
Table 5
Table 6A
ERROR_NUMBER (Lockout Errors)
Error Number Error Designaon Descripon
Decimal Hexadecimal
0 0x00  
1 0x01  
5 0x05  Gas Valve Relay Problems
6 0x06  Internal Control Error
8 0x08  Incorrect Fan Speed
9 0x09  Internal Control Error
10 0x0A  Internal Control Error
11 0x0B  Boiler Return Tempurature Higher Than Supply
12 0x0C  Internal Control Error
13 0x0D  Internal Control Error
14 0x0E  Internal Control Error
15 0X0F  Internal Control Error
16 0x10  Internal Control Error
17 0x11  Internal Control Error
18 0x12  
19 0x13  Internal Control Error
20 0x14  
21 0x15  
22 0x16  Internal Control Error
23 0x17  Internal Control Error
24 0x18  
25 0x19  
26 0x1A  
27 0x1B  Internal Control Error
28 0x1C  Internal Control Error
29 0x1D  Internal Control Error
30 0x1E  Internal Control Error
6
PUREFIRE PFA-1 INTERFACE ADAPTER
Table 7
WARNING_NUMBER
Error Designaon Descripon
Decimal Hexadecimal
1 0X01  
2 0X02  
3 0X03  DHW Sensor Shorted
4 0X04  
255 0XFF  
Table 6B
ERROR_NUMBER (Blocking Errors)
Error Number Error Designaon Descripon
Decimal Hexadecimal
31 0x1F  
32 0x20  
33 0x21  
34 0x22  
35 0x23  False Flame Detected
36 0x24  
39 0x27  High Vent Temperature
40 0x28  High Return Temperature (>194F; >90C)
41 0x29  Blocked Condensate Drain
43 0x2B  
44 0x2C  
45 0x2D  Frequency ? 60 Hz ? 1.2 Hz
46 0x2E  
47 0x2F  Internal Hardware Error
51 0x33  
52 0x34  
55 0x37  
56 0x38  
57 0x39  
59 0x3B  Supply Sensor Shorted
60 0x3C  Return Sensor Shorted
63 0x3F  DHW Sensor Shorted
64 0x40  System Sensor Shorted
65 0x41  Flue Sensor Shorted
66 0x42  
7
PUREFIRE PFA-1 INTERFACE ADAPTER
If no Modbus command is sensed for more than 4.25 seconds aer the Write Command is issued, the control resets
and the command must be re-issued to change the setpoint.
NOTICE
If an invalid value is wrien aer the Write Command is issued, the control resets and the command must be
re-issued to change the setpoint.
NOTICE
Modbus setpoints are maintained in volale memory. Therefore, if the control must be reset due to an lockout error,
a new value for CH and DHW must be wrien through Modbus. If this is not done, the control will default to the last
value saved for each of these parameters.
NOTICE
The PureFire®main control resets automacally every 24 hours. This will reset the CH and DHW setpoint values to
the last value saved for each of these parameters. A new Modbus command should be issued periodically for each
setpoint to be sure that the control is targeng the correct temperature.
NOTICE
3. Modbus Holding Registers (Read/Write):
The PFA-1 control has holding registers that allow



4. Controlling Main Board Parameters:
a. To change the CH setpoint:
 



- Calculate the scaled setpoint as follows:
(°C+10)x2x256=scaled value
 
to rite the scaled temperature setpoint value to the
0x001E holding register.
b. To change the DHW setpoint:
 


- Calculate the scaled setpoint as follows:
(°C+10) x 2 = scaled value
 
to write the scaled temperature setpoint value to the
0x001E holding register.
Modbus Holding Registers (Read/Write)
Item Index
Parameter Name
Address & Holding Registers
Notes
Word byte Range Start
0x0000
Range Start
0x0001
10 High byte 10  0x001A 0x001B (oC + 10) x 2 = byte value
(oF - 32) x 5= oC
9
10 Low byte 11  0x001A 0x001B
14 High byte 14  0x001E 0x001F
14 Low byte 15  0x001E 0x001F
Table 8
PF8108 R3 (05/23)
Printed in U.S.A.
©2023 PB Heat, LLC. All rights reserved.
PB HEAT, LLC
131 S. CHURCH STREET • BALLY, PA 19503

Other PEERLESS Adapter manuals

PEERLESS ACC630 Guide

PEERLESS

PEERLESS ACC630 Guide

PEERLESS ACC625 Guide

PEERLESS

PEERLESS ACC625 Guide

PEERLESS PAN42 User manual

PEERLESS

PEERLESS PAN42 User manual

Popular Adapter manuals by other brands

Canon Scan Kiosk II user guide

Canon

Canon Scan Kiosk II user guide

Motorola solutions PMLN8334 user guide

Motorola solutions

Motorola solutions PMLN8334 user guide

Sharkoon MOBILE DAC PD manual

Sharkoon

Sharkoon MOBILE DAC PD manual

Amped Wireless UA600 user guide

Amped Wireless

Amped Wireless UA600 user guide

Emulex OneConnect OCm11102-N-X Information

Emulex

Emulex OneConnect OCm11102-N-X Information

Sabrent USB-AVCPT user guide

Sabrent

Sabrent USB-AVCPT user guide

Draytek Vigor600 quick start guide

Draytek

Draytek Vigor600 quick start guide

D-Link DGE-560T - Gigabit PCI-Express SNMP VLAN Flow Control Network... Quick installation guide

D-Link

D-Link DGE-560T - Gigabit PCI-Express SNMP VLAN Flow Control Network... Quick installation guide

Gigaware 2790025 user guide

Gigaware

Gigaware 2790025 user guide

Current WA100-PM installation instructions

Current

Current WA100-PM installation instructions

Renkforce RF-DAB-AP operating instructions

Renkforce

Renkforce RF-DAB-AP operating instructions

Exsys EX-1331 user manual

Exsys

Exsys EX-1331 user manual

Edimax EW-7733UnD user manual

Edimax

Edimax EW-7733UnD user manual

Vicon V896MA Installation & operation manual

Vicon

Vicon V896MA Installation & operation manual

D-Link DVG-5121SP Quick installation guide

D-Link

D-Link DVG-5121SP Quick installation guide

Multi-Contact PV-KBT3 Series Assembly instructions

Multi-Contact

Multi-Contact PV-KBT3 Series Assembly instructions

Sony MSAC-FD2M - MAVICA FLOPPY ADPT WIN NT-MAC MVC-FD85 FD90... operating instructions

Sony

Sony MSAC-FD2M - MAVICA FLOPPY ADPT WIN NT-MAC MVC-FD85 FD90... operating instructions

Intermec 751G instructions

Intermec

Intermec 751G instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.