Pepperl+Fuchs KCD2-SCD Series User manual

ISO9001
2
Functional Safety
SMART Current Driver
KCD2-SCD-(Ex)1(.SP), HiC2031
PROCESS AUTOMATION
MANUAL

With regard to the supply of products, the current issue of the following document is applicable: The General Terms of
Delivery for Products and Services of the Electrical Industry, published by the Central Association of the Electrical
Industry (Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the
supplementary clause: "Expanded reservation of proprietorship"
Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031

Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Content
2019-03
3
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Content of this Document. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Symbols Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Validity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4 Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.5 Standards and Directives for Functional Safety . . . . . . . . . . . . . . . . . . 8
3 Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.1 System Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.2 Assumptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.3 Safety Function and Safe State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.4 Characteristic Safety Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.5 Useful Lifetime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4 Mounting and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.1 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.1 Proof Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6 Maintenance and Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7 List of Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

2019-03
4
Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Introduction
1Introduction
1.1 Content of this Document
This document contains information for usage of the device in functional safety-related
applications. You need this information to use your product throughout the applicable stages
of the product life cycle. These can include the following:
• Product identification
• Delivery, transport, and storage
• Mounting and installation
• Commissioning and operation
• Maintenance and repair
• Troubleshooting
• Dismounting
• Disposal
The documentation consists of the following parts:
• Present document
• Instruction manual
•Manual
•Datasheet
Additionally, the following parts may belong to the documentation, if applicable:
• EU-type examination certificate
• EU declaration of conformity
• Attestation of conformity
• Certificates
• Control drawings
• FMEDA report
• Assessment report
• Additional documents
For more information about Pepperl+Fuchs products with functional safety,
see www.pepperl-fuchs.com/sil.
Note!
This document does not substitute the instruction manual.
Note!
For full information on the product, refer to the instruction manual and further documentation
on the Internet at www.pepperl-fuchs.com.

Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Introduction
2019-03
5
1.2 Safety Information
Target Group, Personnel
Responsibility for planning, assembly, commissioning, operation, maintenance,
and dismounting lies with the plant operator.
Only appropriately trained and qualified personnel may carry out mounting, installation,
commissioning, operation, maintenance, and dismounting of the product.
The personnel must have read and understood the instruction manual
and further documentation.
Intended Use
The device is only approved for appropriate and intended use. Ignoring these instructions
will void any warranty and absolve the manufacturer from any liability.
The device is developed, manufactured and tested according to the relevant safety standards.
Use the device only
• for the application described
• with specified environmental conditions
• with devices that are suitable for this safety application
Improper Use
Protection of the personnel and the plant is not ensured if the device is not used according
to its intended use.

2019-03
6
Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Introduction
1.3 Symbols Used
This document contains symbols for the identification of warning messages
and of informative messages.
Warning Messages
You will find warning messages, whenever dangers may arise from your actions.
It is mandatory that you observe these warning messages for your personal safety and in order
to avoid property damage.
Depending on the risk level, the warning messages are displayed in descending order
as follows:
Informative Symbols
Action
This symbol indicates a paragraph with instructions. You are prompted to perform an action
or a sequence of actions.
Danger!
This symbol indicates an imminent danger.
Non-observance will result in personal injury or death.
Warning!
This symbol indicates a possible fault or danger.
Non-observance may cause personal injury or serious property damage.
Caution!
This symbol indicates a possible fault.
Non-observance could interrupt the device and any connected systems and plants,
or result in their complete failure.
Note!
This symbol brings important information to your attention.

Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Product Description
2019-03
7
2 Product Description
2.1 Validity
This manual is only valid for devices with a part number greater than #321000.
Contact your Pepperl+Fuchs representative for information about older devices.
2.2 Function
KCD2-SCD-1(.SP)
This signal conditioner provides the galvanic isolation between field circuits
and control circuits.
The device repeats the input signal from a control system to drive SMART I/P converters,
electrical valves, and positioners located on the field side.
Digital signals are superimposed on the analog values at the field side or control side
and are transferred bi-directionally.
The current is transferred via a DC/DC converter and repeated at the output terminals.
An open field circuit presents a high impedance to the control side to allow alarm conditions
to be monitored by the control system.
Test sockets for the connection of HART communicators are integrated into the terminals
of the device.
SP version
The devices are available with screw terminals or spring terminals. The type code
of the versions of the devices with spring terminals has the extension ".SP".
KCD2-SCD-Ex1(.SP)
This isolated barrier is used for intrinsic safety applications.
The device repeats the input signal from a control system to drive SMART I/P converters,
electrical valves, and positioners located in a hazardous area.
Digital signals are superimposed on the analog values at the field side or control side
and are transferred bi-directionally.
The current is transferred via a DC/DC converter and repeated at the output terminals.
An open field circuit presents a high impedance to the control side to allow alarm conditions
to be monitored by the control system.
Test sockets for the connection of HART communicators are integrated into the terminals
of the device.
SP version
The devices are available with screw terminals or spring terminals. The type code
of the versions of the devices with spring terminals has the extension ".SP".

2019-03
8
Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Product Description
HiC2031
This isolated barrier is used for intrinsic safety applications.
The device repeats the input signal from a control system to drive HART I/P converters,
valve actuators, and displays located in a hazardous area.
Digital signals are superimposed on the analog values at the field side or control side
and are transferred bi-directionally.
An open field circuit presents a high impedance to the control side to allow alarm conditions
to be monitored by the control system.
This device mounts on a HiC termination board.
2.3 Interfaces
The device has the following interfaces.
• Safety relevant interfaces: input I, output I
• Non-safety relevant interfaces: none
The HART communication is not relevant for functional safety.
2.4 Marking
2.5 Standards and Directives for Functional Safety
Device specific standards and directives
System-specific standards and directives
Note!
For corresponding connections see datasheet.
Pepperl+Fuchs GmbH
Lilienthalstraße 200, 68307 Mannheim, Germany
Internet: www.pepperl-fuchs.com
KCD2-SCD-1(.SP) Up to SIL 2
KCD2-SCD-Ex1(.SP)
HiC2031
Functional safety IEC/EN 61508, part 1 –7, edition 2010:
Functional safety of electrical/electronic/programmable electronic
safety-related systems (manufacturer)
Functional safety IEC 61511-1:2016+COR1:2016+A1:2017
EN 61511-1:2017+A1:2017
Functional safety –Safety instrumented systems for the process
industry sector (user)

Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Planning
2019-03
9
3 Planning
3.1 System Structure
3.1.1 Low Demand Mode of Operation
If there are two control loops, one for the standard operation and another one for the functional
safety, then usually the demand rate for the safety loop is assumed to be less
than once per year.
The relevant safety parameters to be verified are:
•thePFD
avg value (average Probability of dangerous Failure on Demand)
and the T1value (proof test interval that has a direct impact on the PFDavg value)
• the SFF value (Safe Failure Fraction)
• the HFT architecture (Hardware Fault Tolerance)
3.1.2 High Demand or Continuous Mode of Operation
If there is only one safety loop, which combines the standard operation and safety-related
operation, then usually the demand rate for this safety loop is assumed to be higher
than once per year.
The relevant safety parameters to be verified are:
•thePFHvalue(Probability of dangerous Failure per Hour)
• Fault reaction time of the safety system
• the SFF value (Safe Failure Fraction)
• the HFT architecture (Hardware Fault Tolerance)
3.1.3 Safe Failure Fraction
The safe failure fraction describes the ratio of all safe failures and dangerous detected failures
to the total failure rate.
SFF = (s+ dd) / (s+ dd + du)
A safe failure fraction as defined in IEC/EN 61508 is only relevant for elements or (sub)systems
in a complete safety loop. The device under consideration is always part of a safety loop but
is not regarded as a complete element or subsystem.
For calculating the SIL of a safety loop it is necessary to evaluate the safe failure fraction
of elements, subsystems and the complete system, but not of a single device.
Nevertheless the SFF of the device is given in this document for reference.

2019-03
10
Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Planning
3.2 Assumptions
The following assumptions have been made during the FMEDA:
• Failure rate based on the Siemens standard SN 29500.
• Failure rates are constant, wear is not considered.
• External power supply failure rates are not included.
• The safety-related device is considered to be of type Adevice with a hardware
fault tolerance of 0.
• The device will be used under average industrial ambient conditions comparable
to the classification "stationary mounted" according to MIL-HDBK-217F.
Alternatively, operating stress conditions typical of an industrial field environment
similar to IEC/EN 60654-1 Class C with an average temperature over a long period of time
of 40 ºC may be assumed. For a higher average temperature of 60 ºC, the failure rates
must be multiplied by a factor of 2.5 based on experience. A similar factor must be used
if frequent temperature fluctuations are expected.
• The application program in the programmable logic controller (PLC) is configured to detect
underrange and overrange failures.
SIL 2 Application
• The device shall claim less than 10 % of the total failure budget for a SIL 2 safety loop.
• For a SIL 2 application operating in low demand mode the total PFDavg value
of the SIF (Safety Instrumented Function) should be smaller than 10-2, hence the
maximum allowable PFDavg value would then be 10-3.
• For a SIL 2 application operating in high demand mode the total PFH value
of the SIF should be smaller than 10-6 per hour, hence the maximum allowable PFH value
would then be 10-7 per hour.
• Since the safety loop has a hardware fault tolerance of 0and it is a type Adevice,
the SFF must be > 60 % according to table 2 of IEC/EN 61508-2 for a SIL 2 (sub) system.

Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Planning
2019-03
11
3.3 Safety Function and Safe State
Safety Function
The safety function of the device is fulfilled, as long as the output repeats the input current
(4 mA ... 20 mA) with a tolerance of 2 %.
Safe State
The safe state is present when the output current is < 4 mA.
Reaction Time
The reaction time for all safety functions is < 100 ms.
Note!
See corresponding datasheets for further information.

2019-03
12
Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Planning
3.4 Characteristic Safety Values
The characteristic safety values like PFD, SFF, HFT and T1are taken
from the SIL report/FMEDA report. Observe that PFD and T1are related to each other.
The function of the devices has to be checked within the proof test interval (T1).
Parameters Characteristic values
Assessment type Full assessment
Device type A
Mode of operation Low demand mode or high demand mode
HFT 0
SIL (SC) 2 (2)
Safety function Transfer of the analog signals
s1
1"No effect failures" are not influencing the safety function and are therefore not included in SFF and in the failure rates
of the safety function.
0 FIT
dd 157 FIT
du 37.1 FIT
total (safety function)1194 FIT
not part 7.2 FIT
SFF 180.89 %
MTBF 2
2acc. to SN29500. This value includes failures which are not part of the safety function/MTTR = 24 h.
291 years
PFH 3.71 x 10-8 1/h
PFDavg for Tproof = 1 year 1.66 x 10-4
PFDavg for Tproof = 2 years 3.29 x 10-4
PFDavg for Tproof = 5 years 8.16 x 10-4
PTC 100 %
Reaction time 3
3Time between fault detection and fault reaction
< 100 ms
Table 3.1

Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Planning
2019-03
13
3.5 Useful Lifetime
Although a constant failure rate is assumed by the probabilistic estimation this only applies
provided that the useful lifetime of components is not exceeded. Beyond this useful lifetime,
the result of the probabilistic estimation is meaningless as the probability of failure significantly
increases with time. The useful lifetime is highly dependent on the component itself
and its operating conditions –temperature in particular. For example, the electrolytic
capacitors can be very sensitive to the operating temperature.
This assumption of a constant failure rate is based on the bathtub curve, which shows
the typical behavior for electronic components.
Therefore it is obvious that failure calculation is only valid for components that have
this constant domain and that the validity of the calculation is limited to the useful lifetime
of each component.
It is assumed that early failures are detected to a huge percentage during the installation
and therefore the assumption of a constant failure rate during the useful lifetime is valid.
The standard EN/ISO 13849-1:2015 proposes a useful lifetime TMof 20 years for devices
used within industrial environments. This device is designed for this lifetime. Observe that
the useful lifetime can be reduced if the device is exposed to the following conditions:
• highly stressful environmental conditions such as constantly high temperatures
• temperature cycles with high temperature differences
• permanent repeated mechanical stress (vibration)
As noted in DIN EN 61508-2:2011 note N3, appropriate measures taken by the manufacturer
and plant operator can extend the useful lifetime.
Please note that the useful lifetime refers to the (constant) failure rate of the device.
The effective lifetime can be higher.

2019-03
14
Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Mounting and Installation
4 Mounting and Installation
Mounting and Installing the Device
1. Observe the safety instructions in the instruction manual.
2. Observe the information in the manual.
3. Observe the requirements for the safety loop.
4. Connect the device only to devices that are suitable for this safety application.
5. Check the safety function to ensure the expected output behavior.
4.1 Configuration
A configuration of the device is not necessary and not possible.

Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Operation
2019-03
15
5Operation
Operating the device
1. Observe the safety instruction in the instruction manual.
2. Observe the information in the manual.
3. Use the device only with devices that are suitable for this safety application.
4. Correct any occurring safe failures within 24 hours. Take measures to maintain
the safety function while the device is being repaired.
5.1 Proof Test Procedure
According to IEC/EN 61508-2 a recurring proof test shall be undertaken to reveal
potential dangerous failures that are not detected otherwise.
Check the function of the subsystem at periodic intervals depending on the applied PFDavg
in accordance with the characteristic safety values. See chapter 3.4.
It is under the responsibility of the plant operator to define the type of proof test
and the interval time period.
Equipment required:
• Digital multimeter with an accuracy better than 0.1 %
Use for the proof test of the intrinsic safety side of the device a special digital multimeter
for intrinsically safe circuits.
If intrinsically safe circuits are operated with non-intrinsically safe circuits,
they must no longer be used as intrinsically safe circuits.
• Power supply set to nominal voltage of 24 V DC
• Process calibrator with current source function with an accuracy better than 20 µA
Danger!
Danger to life from missing safety function
If the safety loop is put out of service, the safety function is no longer guaranteed.
• Do not deactivate the device.
• Do not bypass the safety function.
• Do not repair, modify, or manipulate the device.

2019-03
16
Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Operation
Proof Test Procedure
1. Put out of service the entire safety loop. Protect the application by means of other measures.
2. Prepare a test set-up, see figures below.
3. Test the devices. Verify the current values as given in table below.
4. Set back the device to the original settings for the application after the test.
Figure 5.1 Proof test set-up for KCD2-SCD-(Ex)1(.SP)
Usage in Zone 0, 1, 2/Div. 1, 2 only for KCD2-SCD-Ex1(.SP)
Step No. Set input value (mA) Measurement point
Output value (mA)
120.00 20.00 ±0.4
212.00 12.00 ±0.4
34.00 4.00 ±0.4
423.00 23.00 ±0.4
5 0 < 0.3
612.00 –
Table 5.1 Steps to be performed for the proof test
KCD2-SCD-Ex1
Multimeter
(mA)
Multimeter
(V)
Zone 0, 1, 2
Div. 1, 2
Zone 2
Div. 2
5-
1+
2- 6+
Multimeter
(mA )
I
supply
9+
10-
24 V DC
Power
supply
Supply
4 mA to 20 mA 4 mA to 20 mA

Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Operation
2019-03
17
Figure 5.2 Proof test set-up for HiC2031
Termination Board
HiC2031
Zone 0, 1, 2
Div. 1, 2
Zone 2
Div. 2
1a, 1b
2a, 2b
-
+
11
14
+
-
+1
-4
I
supply
SL2
5a
5b
SL1
8a
7a
Multimeter
(mA )
Multimeter
(mA)
Multimeter
(V)
24 V DC
Power
supply
4 mA to 20 mA 4 mA to 20 mA
Tip
The easiest way to test HiC devices is by using a stand-alone HiCTB**-SCT-***-**-**
termination board. In this test, it is not necessary to disconnect the wiring of the existing
application. Faults in a subsequent wiring can be avoided.

2019-03
18
Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
Maintenance and Repair
6 Maintenance and Repair
Maintaining, Repairing or Replacing the Device
In case of maintenance, repair or replacement of the device, proceed as follows:
1. Implement appropriate maintenance procedures for regular maintenance of the safety loop.
2. While the device is maintained, repaired or replaced, the safety function does not work.
Take appropriate measures to protect personnel and equipment while the safety function
is not available.
Secure the application against accidental restart.
3. Do not repair a defective device. A defective device must only be repaired by
the manufacturer.
4. If there is a defect, always replace the device with an original device.
Danger!
Danger to life from missing safety function
Changes to the device or a defect of the device can lead to device malfunction.
The function of the device and the safety function is no longer guaranteed.
Do not repair, modify, or manipulate the device.

Functional Safety KCD2-SCD-(Ex)1(.SP), HiC2031
List of Abbreviations
2019-03
19
7 List of Abbreviations
ESD Emergency Shutdown
FIT Failure In Time in 10-9 1/h
FMEDA Failure Mode, Effects, and Diagnostics Analysis
sProbability of safe failure
dd Probability of dangerous detected failure
du Probability of dangerous undetected failure
no effect Probability of failures of components in the safety loop that have
no effect on the safety function. The no effect failure is not used
for calculation of SFF.
not part Probability of failure of components that are not in the safety loop
total (safety function) Probability of failure of components that are in the safety loop
HFT Hardware Fault Tolerance
MTBF Mean Time Between Failures
MTTR Mean Time To Restoration
PCS Process Control System
PFDavg Average Probability of dangerous Failure on Demand
PFH Average frequency of dangerous failure
PLC Programmable Logic Controller
PTC Proof Test Coverage
SFF Safe Failure Fraction
SIF Safety Instrumented Function
SIL Safety Integrity Level
SIL (SC) Safety Integrity Level (Systematic Capability)
SIS Safety Instrumented System
T1Proof Test Interval

Subject to modifications
Copyright PEPPERL+FUCHS • Printed in Germany
www.pepperl-fuchs.com
Worldwide Headquarters
Pepperl+Fuchs GmbH
68307 Mannheim · Germany
Tel. +49 621 776-0
E-mail: [email protected]
For the Pepperl+Fuchs representative
closest to you check www.pepperl-fuchs.com/contact
PROCESS AUTOMATION –
PROTECTING YOUR PROCESS
DOCT-6394
03/2019
This manual suits for next models
5
Table of contents
Popular Servo Drive manuals by other brands

Beckhoff
Beckhoff AX5000 Series Startup manual

AXOR Industries
AXOR Industries MiniMagnum Series Service manual

Welcon
Welcon WER-D048 Series Hardware manual

Baldor
Baldor UM Series Installation & operating manual

ANTEK
ANTEK ECE863 Series Technical documentation

Bosch
Bosch Rexroth MSK Project planning manual