Philips PM 5132 User manual

Function
generator
O1HZ-2MHz
PM
5132
9445
051
32001
Instruction
manual
provisional
9499
453
00202
g00101/1
Scientific
&
Industrial
equipment
division
PHILIPS

Function
generator
O1Hz-2MHz
PM
5132
9445
051
32001
Instruction
manual
provisional
Geratehandbuch
Mode
demploi
et
d‘entretien
9499
453
00202
gootoi1/
1
PHILIPS

CONTENTS
1.1.
1.2.
1.3.
1.4.
2.1.
2.2.
2.3.
2.4.
2.5.
3.1.
3.2.
4.1.
4.2.
4.3.
4.4.
4.5.
GENERAL
Introduction
Technical
data
Accessories
Operating
principle
INSTALLATION
Safety
regulations
Mounting
Earthing
Dismantling
the
instrument
Mains
connection
OPERATING
INSTRUCTIONS
Control!
and
sockets
Operation
SERVICE
PART
Circuit
description
Access
to
parts
Check
and
adjustment
Check
after
repair
and
maintenance
Parts
list
FIGURES
.
Block
diagram
.
Front
view
.
Rear
view
.
Unit
2
component
layout
.
Unit
1,
component
layout
.
Overall
circuit
diagram
oar
WN
CODING
SYSTEM
OF
FAILURE
REPORTING
FOR
QUALITY
ADDRESSES
FOR
SALES
AND
SERVICE
oo
aa
a
11
12
12
12
12
13
13
14

INHALTSVERZEICHNIS
1.
ALLGEMEINES
1.1.
Einleitung
1.2.
Technische
Daten
1.3,
Zubehor
1.4.
Funktionsprinzip
2.
VORBEREITUNGSANWEISUNGEN
2.1.
Sicherheitstechnische
Hinweise
2.2.
Aufstellen
2.3.
Erden
2.4,
Offnen
des
Gehduses
2.5.
NetzanschluR&
3.
BETRIEBSANLEITUNG
3.1.
Bedienelemente
und
Anschliisse
3.2.
Bedienung
5.
BILDVERZEICHNIS
1.
Blockschaltbild
2.
Frontansicht
3.
Riickansicht
17
17
17
21
22
23
23
24
24
24
24
25
25
26
TABLE
DES
MATIERES
1.
GENERALITES
1.1.
Introduction
1.2.
Caractéristiques
techniques
1.3.
Accessoires
1.4.
Principe
de
fonctionnement
2.
INSTALLATION
2.1.
Consignes
de
sécurité
2.2.
Montage
2.3.
Mise
a
la
terre
2.4.
Démontage
de
|‘appareil
2.5.
Branchement
de
|’appareil
3:
MISE
EN
SERVICE
3.1.
Commandes
et
douilles
3.2.
Fonctionnement
5.
RAPPEL
DES
FIGURES
1.
Schéma
synoptique
2.
Face
avant
3.
Face
arriere
29
29
29
33
34
35
35
36
36
36
36
37
37
38

Operating
manual


1.1.
1.2,
1.2.1.
GENERAL
INTRODUCTION
The
PM
5132
function
generator
is
an
instrument
designed
for
applications
extending
from
the
educa-
tional
to
the
genera!
purpose
area.
It
produces
sinewave,
triangular
and
squarewave
output
signals
as
well
as
positive
and
negative
pulses,
the
frequencies
of
which
are
adjustable
in
seven
linear
sub-ranges
from
0.1
Hz
to
2
MHz.
The
frequency
vernier
allows
the
frequency
setting
to
be
varied
from
-5%
to
+5
%.
The
output
voltage
is
continuously
adjustable
from
3
Vpp
to
30
Vpp
and
can
be
attenuated
in
steps
of
10
dB
to
60
cB.
A
continnously
adjustable
d.c.
output
voltage
can
be
selected
seperately
or
whenever
used
as
d.c.
offset
voltage
added
to
the
selected
output
signal.
The
internal
resistance
of
the
generator
can
be
selected
by
means
at
a
pushbutton
between
50
Q
and
600
2.
The
duty
cycle
can
be
set
to
a
fixed
value
of
50
%
or
is
continuously
adjustable
between
10
%
and
90
%.
The
generator
frequency
is
controllable
in
each
of
the
seven
sub-ranges
(internal
sweep).
The
sweep
period
is
adjustable
within
a
range
of
0.05
s
to
100
s.
Moreover
external
sweep
and
frequency
modula-
tion
can
be
performed.
For
TTL
applications
a
seperate
output
is
available.
The
ergonomic
design
of
controls
and
sockets
serves
for
convenient
operating
of
the
instrument.
TECHNICAL
DATA
General
information:
On
delivery
from
the
factory,
the
instrument
complies
with
the
safety
regulations
of
measuring
and
control
equipment.
The
information
and
warnings
contained
in
this
instruction
manual
must
be
followed
by
the
user
to
ensure
safe
operation
and
to
maintain
the
instrument
in
a
safe
condition.
—
Only
data
with
indicated
tolerances
or
limits
are
guaranteed;
data
without
tolerances
are
given
only
for
guidance.
—
All
specifications
will
be
met
after
a
warm-up
time
of
30
min.,
when
keeping
the
instrument
in
a
constant
mounting
position.
—
Inaccuracies
(absolute
or
in
%)
relate
to
the
indicated
reference
value.
SPECIFICATIONS
Frequency
Frequency
range
0.1
Hz
-
2MHz
Selected
range
|
0.4
Hz
-
2
Hz
i
1
Hz
-
20
Hz
lit
10
Hz
-
200
Hz
IV
100
Hz
-
2kHz
Vv
1
kHz
-
20
kHz
VI
10
kHz
-
200
kHz
Vil
100
kHz
-
2MHz

1.2.2.
Characteristic
Adjustments
Frequency
indication
Setting
error
Vernier
frequency
adjustment
Temperature
coefficient
Short
term
drift
Long
term
drift
Signal
output
Connection
Impedance
Load
capability
Wave
forms
Duty
cycle
Open-circuit
voltage
—
setting
range
maximum
value
DC
(offset)
voltage
—
button
PUSH
FOR
ZERO
pulled,
open
circuit
voltage
—
button
PUSH
FOR
ZERO
or
WAVE
FORM
button
DC
pressed
Attenuation
—
continuous
—
fixed
Distortion
(sinewave)
Linearity
(triangular
wave)
linear
—
seven
range-pushbuttons
—
dia!
with
linear
scale
—
knob
for
fine-adjustment
—
linear
scale
on
the
dial
42%
+0,2
%
of
full
scale
+5
%
of
the
dial
setting
<0,1%/K
ranges
I!
-
VI
<0,15
%/K
ranges
|
-
VII
<0,15%
ranges
Il
-
VI
<0,20%
ranges
|-
Vilwithin
15
min.
<0,25
%
within
7
hours
BNC
socket
50
92/600
2,
selected
by
pushbutton
short-circuit
proof
rv
sinewave
Av
triangular
wave
TL
squarewave
MW
positive
squarewave
ur—
negative
squarewave
DC
d.c.
voltage
without
a.c.
adjustable
from
10
%
to
90
%
when
pushbutton
DUTY
CYCLE
is
pressed
3
Vpp
to
30
Vpp,
continuously
adjustable
1,5
Vpp
to
15
Vpp
for
positive
and
negative
squarewaves
+15
V
-10
to
+10
V,
continuously
adjustable
<50
mV
0
to
20
dB
(output
voltage
adjustable
from
3
Vpp
to
30
Vpp)
0
to
60
dB
in
steps
of
10
dB
<0,5
%
in
ranges
|
to
V
<1
%inrange
VI
<3
%inrange
VII
<1%

1.2.3.
1.2.4.
1.2.4.1.
risetime,
falltime
(squarewave)
overshoot
and
ringing
(squarewave)
Amplitude
response
(sinewave,
reference
value
=
1
KHz;)
TTL-output
Connection
Duty
cycle,
frequency
Fan
out
Frequency
control
Internal
sweep
Sweep
modes
Sweep
characteristic
Start
frequency
Stop
frequency
Sweep
period
Sweep
control
elements
<75
ns
<2%
‘(output
voltage
30
Vpp)
<0,1
dB
in
ranges
|
to
V
<1
dBinranges
|
to
Vil
(output
voltage
3...
30
Vp,
load
50
&,
attenuation
0
dB).
BNC
socket
at
the
rear
side
identical
with
main
output
2
20
TTL
inputs
—
single
sweep
started
by
a
pulse
(SWEEP
TRIG
INPUT)
—
single
sweep
started
by
pressing
the
pushbutton
TRIG
—
continuous
sweep
single
sweep
f
——-—
continuous
sweep
f
STOP
{START
linear
continuously
adjustable
within
the
respective
frequency
range
after
the
pushbutton
STD
BY
/
CONT
is
set
to
STD
BY.
identical
to
the
dial
adjustment
50
ms
to
100
s,
adjustable
in
three
ranges:
—50mstols
—0,5
sto10s
—5
sto
100s
—
pushbutton
to
start
a
single
sweep
—
pushbutton
to
stop
the
running
sweep
immediately
—
pushbutton
for
resetting
to
f
star
Ppuring
the
sweep

1.2.4.2.
1.2.5.
SWEEP
TRIG
INPUT
—
Connection
—
Impedance
—
Max.
input
voltage
—
Release
criterion
SWEEP
VOLTAGE
OUTPUT
~
Connection
—
Impedance
—
Output
voltage
PEN
LIFT
—
Connection
BNC
socket
at
the
rear
side
>10KQ
+15
V
negative
going
edge
of
a
pulse
(from
High
to
LOW);
e.g.
TTL
signal
with
fall
time
<8
ms
BNC
socket
at
the
rear
side
10
KQ
OVtO5V
lteraRr--:tstor
}
BNC
socket
at
the
rear
side
electronic
switch,
open
during
flyback,
closed
during
the
sweep.
max.
current:
200
mA
electronic
switch
output
voltage:
<
0,7
V
4closed
output
voltage:
+15
V
electronic
switch
internal
resistance:
ee
open
External
sweep
or
frequency
modulation
(SWEEP
INPUT)
—
Connection
=
Voltage
vs.
frequency
characteristic
—
Impedance
—
Max.
sweep
range
—
Max.
sweep
frequency
—
Sensitivity
Power
supply
—
Reference
value
—
Nominal
vaues
—
Nominal
operating
range
—
Operating
limits
—
Nominal
frequency
range
—
Power
consumption
BNC
socket
linear
47
KQ
2
1/2
decades
15
KHz
1V/0,2
fe
where
f_.,
represents
the
upper
limit
of
the
corresponding
subrange.
AC
mains
220
V
110
V/128
V
/
220
V
/
238
V,
selectable
by
solder
links
+10
%
of
selected
nominal
value
+10
%
of
selected
nominal
value
50
Hz
to
100
Hz
25W

1.2.6.
1.2.7,
1.3.
1.3.1.
1.3.2.
Environmental
conditions
Ambient
temperature
—
Reference
value
—
Nominal
operating
range
—
Limits
for
storage
and
transit
Relative
humidity
—
Reference
range
--
Nominal
operating
range
oe
Limits
for
storage
and
transit
Air
pressure
—
Reference
value
—
Nominal
working
range
Air
speed
--
Reference
value
—
Nominal
working
range
Operating
position
Warm-up
time
Cabinet
Protection
type
(see
DIN
40
050)
Protection
class
(see
IEC
348)
Overall
dimensions
—
height
—
width
—
dupth
Weight
ACCESSORIES
Standard
Optional
+23°C
#1°C
+
5°C
to
+40°C
-40°
C
to
+70°
C
45
%
to
75%
20%
to
80%
0%
to 90
%
1013
mbar
(=
760
mmHg)
800
-
1066
mbar
(up
to
220
m
height)
0
to
0,2
m/s
0
to
0,5
m/s
normally
upright
on
feet
or
with
handle
fold
down
30
min.
IP
20
class
|,
protective
conductor
140
mm
310
mm
330
mm
approx.
5
kg
Instruction
manual,
fuse
0,4
AT
adhesive
labels
110
V
/
128
V
/
238
V
PM
9585:
50
2
termination
1
W
PM
9075:
Coaxial
connection
cable
BNC
-
BNC

10
1.4.
OPERATING
PRINCIPLE
(see
Fig.
1.,
block
diagram)
The
main
oscillator
of
the
function
generator
comprises
the
switched
integrator
and
the
peak
detector
(comparator).
The
controlled
current
source
of
the
d.c.
control
section
generates
the
charging
current
for
the
integrator.
At
the
integrator
output
a
linear
voltage
ramp
is
fed
to
the
peak
detector.
When
reaching
the
reference
voltage
the
detector
reverses
the
charging
current
of
the
integrator
resulting
in
integration
in
the
opposite
direction.
Integration
down
is
performed
until
reaching
the
negative
reference
level
of
the
peak
detector,
which
again
reverses
the
current
of
the
switched
integrator.
As
both
reference
levels
are
symmetrical
with
respect
to
earth,
a
zero
symmetrical
triangular
wave
is
generated
at
the
output
of
the
integrator.
The
duty
cycle
of
this
wave
is
1:
1
and
can
be
adjusted
continuously
between
10
%
and
90
%
when
push-
button
DUTY
CYCLE
is
pressed.
The
output
current
of
the
controlled
current
source
depends
on
the
positions
of
the
frequency
dial
and
the
FREQUENCY
OFFSET
control.
The
resulting
frequency
of
the
oscillator
is
determined
by
this
current
and
-in
addition-
by
the
integrating
capacitor
in
the
switched
integrator.
Different
capacitors
are
switched
in
by
the
FREQUENCY
Hz
pushbuttons.
External
sweep
and
frequency
modulation
can
be
performed
via
the
SWEEP
INPUT
socket.
The
voltage
to
frequency
relationship
is
linear.
Internal
frequency
control
is
effected
by
the
sweep
oscillator.
Starting
a
single
sweep
can
be
done
by
pressing
the
pushbutton
TRIG,
a
continuous
sweep
is
started
by
setting
the
pushbutton
STD
BY
/
CONT
to
position
CONT.
Moreover
it
is
possible
to
start
a
sweep
by
means
of
an
external
trigger
pulse
connec-
ted
to
the
SWEEP
TRIG
INPUT
socket.
The
sweep
range
is
adjustable
by
means
of
the
knob
START
FREO
and
the
dial
which
represents
the
stop
frequency.
They
are
adjustable
independantly;
the
start
frequency
may
be
set
greater
or
less
than
the
stop
frequency.
Moreover
the
outputs
PEN
LIFT
and
SWEEP
out
are
controlled
by
the
sweep
oscillator.
The
PEN
LIFT
socket
represents
the
output
of
an
electronic
switch
being
closed
during
the
sweep.
The
SWEEP
OUT
socket
gives
the
instantaneous
sweep
voltage
corresponding
to
a
distinct
frequency
of
the
oscillator:
O
V
=
start
frequency,
+5
V
=
stop
frequency
fsrop
.
The
voltage
to
frequency
relationship
is
linear.
The
WAVE
FORM
switch
allows
the
following
wave
forms
to
be
selected:
a
triangular
wave
from
the
integrator,
a
sine
wave
formed
by
the
sine
shaper
circuitry
from
the
triangular
wave,
a
square
wave,
negative
and
positive
pulses
from
the
peak
detector.
The
selected
signal
is
fed
to
the
OUTPUT
socket
via
amplifier
and
attenuator.
The
internal
resistance
can
be
switched
to
600
2
or
to
5022.
By
means
of
the
DC
OFFSET
control
a
d.c.
voltage
can
be
added
to
the
signal,
activated
by
pulling
the
PUSH
FOR
ZERO
switch/turn-knob.
If
d.c.
voltage
only
is
requested,
the
a.c.
part
of
the
output
signal
can
be
switched
off
by
pressing
the
DC
pushbutton
of
the
wave
form
selector.
A
squarewave
signal
of
the
peak
detector
is
fed
to
the
socket
TTL
OUT
via
the
TTL
buffer.
The
stabilized
power
supply
provides
the
d.c.
voltages
for
the
circuitries.

2.1,
2.1.1,
2.1.2.
11
INSTALLATION
SAFETY
REGULATIONS
Upon
delivery,
the
instrument
complies
with
the
required
safety
regulations.
To
maintain
this
condition
and
to
ensure
safe
operation,
it
is
recommended
to
follow
the
instructions
below.
Before
connecting
Mains
voltage
Check
whether
the
instrument
is
adapted
to
the
nominal
mains
voitage.
Protection
This
instrument
is
protected
according
to
class
|
(protective
earth)
of
the
IEC
348
or
VDE
0411.
The
mains
cable
provides
earth
connection.
Outside
specially
protected
rooms,
the
mains
plug
must
be
con-
nected
only
to
sockets
with
earthed
contact.
It
is
not
allowed
to
interrupt
the
earth
connection
inside
or
outside
the
instrument.
Maintenance
and
repair
Failure
and
excessive
stress
If
the
instrument
is
suspected
of
being
unsafe,
take
it
out
of
operation
permanently.
This
is
the
case
when
the
instrument
—
shows
physical
damage
—
does
not
function
anymore
—
is
stressed
beyond
the
tolerable
limits
(e.g.
during
storage
and
transportation)
Dismantling
the
instrument
When
removing
covers
or
other
parts
by
means
or
tools,
live
parts
or
terminals
could
be
exposed.
Before
opening
the
instrument,
disconnect
it
from
all
power
sources.
If
the
open
live
instrument
needs
calibration,
maintenance
or
a
repair,
it
must
be
performed
only
by
trained
personnel
being
aware
of
the
risks.
After
disconnection
from
all
power
sources,
the
capacitors
in
the
instrument
may
remain
charged
for
some
seconds,
oberserve
the
circuit
diagrams.
Fuses
‘
Only
use
the
specified
fuses.
Repair,
Replacing
parts
Repairs
must
be
made
by
trained
personnel.
Ensure
that
the
construction
of
the
instrument
is
not
altered
to
the
detriment
of
safety.
Above
all,
leakage
paths,
air
gaps
and
insulation
layers
must
not
be
reduced.
When
replacing,
use
only
original
parts.
Other
spare
parts
are
only
acceptable
when
the
safety
precautions
for
the
instrument
are
not
impaired.

12
2.2.
2.3.
2.4.
2.5,
MOUNTING
The
instrument
may
be
used
in
any
desired
position.
With
the
handle
fold
down,
the
instrument
may
be
used
in
sloping
position;
for
this
purpose
press
the
buttons
of
the
handle
(Fig.
2).
Do
not
position
the
instrument
on
any
surface
which
produces
or
radiates
heat,
or
in
direct
sunlight.
EARTHING
Before
switching
on,
the
instrument
must
be
earthed
in
conformity
with
the
local
safety
regulations.
The
mains
cable
fixed
to
the
instrument
includes
a
protective
conductor,
which
is
connected
to
the
earth
contacts
of
the
plug.
Thus,
when
connected
to
an
earthed
mains
socket,
the
cabinet
of
the
instru-
ment
is
consequently
connected
to
the
protective
earth.
WARNING:
Connect
the
mains
cable
plug
only
to
a
socket
with
protective
earth
contacts.
This
pro-
tection
must
not
be
made
ineffective,
e.g.
by
using
an
extension
cable
without
earth
protection!
The
circuit
earth
potential
applied
to
the
external
contacts
of
BNC
sockets
is
connected
to
the
cabinet.
The
external
contacts
of
the
BNC
sockets
must
not
be
used
to
connect
a
protective
conductor.
DISMANTLING
THE
INSTRUMENT
—
Unplug
the
mains
connector
—
Fold
up
the
handle
to
the
top.
For
this
push
the
buttons
of
the
handle
—
Loosen
the
central
screw
at
the
rear
—
Remove
the
lead-through
of
the
mains
cable
from
the
cabinet
—
Dismantle
the
cabinet
MAINS
CONNECTION
The
instrument
must
be
connected
only
to
an
AC
supply.
On
delivery
the
instrument
is
set
to
220
V.
Before
mains
connection,
ensure
that
the
local
mains
voltage
ranges
within
the
set
mains
voltage
range
indicated
on
the
plate
at
the
rear
of
the
instrument.
if
the
instrument
is
to
be
used
on
110
V,
128
V,
238
V
supply,
proceed
as
follows:
—
Unplug
the
mains
connector
—
Dismantle
the
instrument,
see
2.4.
—
Resolder
links
on
the
mains
transformer
in
accordance
with
the
stick-on
connection
diagram.
See
also
below.
—
When
switching
to
110
V
or
128
V
insert
the
supplied
fuse
400
mA
delayed
into
the
fuse
holder
instead
of
the
one
built-in
—
Change
the
mains
voitage
plate
at
the
rear
of
the
instrument
in
accordance
with
the
mains
voltage
selected.
The
plates
for
110
V,
128
V,
238
V
are
inserted
into
a
plastic
cover,
as
the
fuse
just
mentioned.
—
Close
the
instrument
Mains
connection
must
be
made
in
accordance
with
the
local
safety
regulations.
This
implies
that
the
instrument
is
connected
to
mains
socket
with
protective
earth
contact
(see
para.
2.3.).

3.1,
OPERATING
INSTRUCTIONS
CONTROLS
AND
SOCKETS
(FIG.
2)
Legend
Position
POWER
251
OON
@
OFF
WAVE
FORM
253/4
to
we
Dei
DC
253/9
FREQUENCY
Hz
253/10
to
x.1
x1
x10
x100
x1K
x10K
253/16
x100K
1...20
648
(Linear
scale)
FREQ
OFFSET
647
DUTY
CYCLE
252/5
DUTY
CYCLE
673
ATTENUATION
253/1
to
10dB
20dB
30dB
253/3
AMPLITUDE
821
3
Vpp
to
30
Vpp
DC
OFFSET
822
—10
V
to
+10
V
PUSH
FOR
ZERO
822
OUTPUT
875
TTL
OUT
874
600
22/50
2
PEN
LIFT
872
SWEEP
INPUT
873
SWEEP
OUT
871
START
FREQ
646
CHECK
IN
STD
BY
13
Function
mains
switch;
white
dot
for
ON
position
pushbuttons
for
the
required
waveform:
sinewave,
triangular-,
square-wave,
positive
or
negative
square
waves,
DC
without
a.c.
portion
pushbuttons
for
selecting
the
frequency
range
0,1
-
2
Hz,
1
Hz
-
20
Hz,
10
Hz
-
200
Hz,
100
Hz
-
2
KHz,
1
KHz
-
20
KHz,
10
KHz
-
200
KHz,
100
KHz
-
2
MHz
dial
for
continuous
coarse
frequency
adjustment
knob
for
continuous
fine
frequency
adjustment
pushbutton
to
switch
on
the
duty
cycle
adjustment
knob
for
duty
cycle
adjustment
pushbuttons
for
setting
the
fixed
attenuation;
40
dB
to
60
dB
by
combination
of
pushbuttons
knob
for
continuous
amplitude
adjustment
of
the
output
signal.
knob
for
continuous
d.c.
voltage
adjustment
pull-switch
for
adding
the
d.c.
voltage
to
the
output
signal.
BNC
socket
for
the
output
signal
BNC
socket
for
TTL
output
signal
(at
the
rear
side)
pushbutton
for
selecting
the
impedance
of
the
main
output.
control
signal
to
control
pen
writing
in
case
of
plotting.
This
BNC
socket
is
positioned
at
the
rear
side.
BNC
socket
at
the
rear
side;
input
of
external
sweep
voltage
BNC
socket
at
the
rear
side;
output
of
the
sweep
voltage
during
internal
sweep
knob
for
adjusting
the
start-frequency

14
3.2.
3.2.1.
3.2.2.
3.2.3.
TRIG
252/4
pushbutton
for
starting
a
single
sweep
STD
BY
252/3
STD
BY
-
for
adjusting
the
start
frequency
and
for
single
sweep
CONT
CONT
-
continuous
sweep
SWEEP
PERIOD
s
256
range
selector
for
the
sweep
period
PERIOD
601
-
knob
for
adjusting
the
sweep
period
HOLD
252/1
pushbutton
for
stopping
the
sweep
immediately
RESET
252/2
pushbutton
for
resetting
the
sweep
to
f,.,,,-
SWEEP
TRIG
870
BNC
socket
at
the
rear
side
—
to
start
a
sweep
by
INPUT
means
of
an
external
signal.
OPERATION
Setting
the
voltage
at
socket
OUTPUT
By
means
of
the
control
AMPLITUDE,
the
amplitude
of
the
output
signal
is
continuously
variable.
Released
button
DC
and
pulled
button
PUSH
FOR
ZERO
enables
a
continuously
adjustable
positive
or
negative
d.c.
voltage
to
be
added
to
the
output
signal.
When
pressing
the
button
DC,
the
a.c.
part
of
the
output
signal
is
switched
off
and
the
d.c.
voltage
only
is
fed
to
the
output.
With
step
attenuator
ATTENUATION,
the
output
signal
and
the
DC
offset
can
be
attenuated
in
steps
of
10
dB
up
to
60
dB.
For
10
dB
to
30
dB
separate
pushbuttons
are
available.
Attenuations
of
40
and
50
dB
are
selected
by
combined
pushbutton
actions.
For
60
dB
all
three
buttons
have
to
be
pressed.
Note:
The
output
amplifier
could
be
overdriven
due
to
adding
signal
and
DC
offset
voltage.
To
avoid
limiting,
the
peak
value
of
the
open-circuit
output
voltage
must
not
exceed
+15
V
(step
attenuator
set
to
0
dB).
Setting
the
frequency
The
PM
5132
offers
three
control
elements
for
setting
the
frequency:
—
a
dial
with
linear
scale
—
a
range
selector
FREQUENCY
Hz
with
seven
ranges
—
vernier
FREQ
OFFSET
control
The
output
frequency
is
represented
by
the
scale
reading
multiplied
by
the
factor
of
the
range
selector
FREQUENCY
Hz.
in
addition
the
frequency
deviation
set
of
the
FREQ
OFFSET
control
must
be
accounted
for.
Setting
the
wave
form
The
required
wave
form
is
selected
by
pressing
the
according
pushbutton
of
the
wave
form
selector.
If
the
duty
cycle
shall
be
set
to
any
value
different
to
50
%,
the
pushbutton
DUTY
CYCLE
must
be
pressed
fo
adjusting
the
duty
cycle
within
10
%
and
90
%
by
means
of
the
knob
DUTY
CYCLE.

3.2.4,
15
Setting
the
internal
sweep
The
internal
sweep
action
of
the
PM
5132
can
be
performed
within
one
subrange.
The
value
of
the
dial
represents
the
stop
frequency,
the
start
frequency
is
set
according
to
the
following
rules:
—
pushbutton
STD
BY
/
CONT
must
be
set
to
STD
BY
—
range
selector
SWEEP
PERIOD
s
must
be
switched
from
OFF
to
the
required
range
—
adjust
the
sweep
period
with
the
knob
PERIOD
—
adjust
the
start
frequency
with
knob
START
FREQ.
This
frequency
can
now
be
measured
at
the
socket
OUTPUT.
The
start
frequency
may
be
set
greater
or
less
than
the
stop
frequency,
a
sweep
can
be
performed
in
both
directions
,
up
and
down.
Starting
a
single
sweep
is
done
by
pressing
the
pushbutton
TRIG
once,
the
continuous
sweep
is
realized
by
setting
the
pushbutton
STD
BY
/
CONT
to
CONT.
In
addition
to
this
a
sweep
action
can
be
started
by
a
triggering
pulse
at
the
SWEEP
TRIG
INPUT
socket.
Starting
criterion
is
the
negative
edge
e.g.
of
a
TTL
signal.
The
SWEEP
OUT
socket
at
the
rear
side
provides
the
instantaneous
sweep
voltage
corresponding
to
a
distinct
signal
frequency
for
controfling
an
oscilloscope
or
x
-
y
plotter.
The
voltage
to
frequen-
cy
relationship
is
linear,
a
sweep-voltage
of
O
V
represents
f+,
7.
4
sweep
voltage
of
+5
V
fstor:
Further
control
elements
for
manual
controlling
are
the
HOLD
pushbutton
to
stop
the
sweep
imme-
diately
and
RESET
for
resetting
to
fstant
during
the
sweep.
Note:
Before
executing
an
internal
sweep,
disconnect
all
cables
from
the
SWEEP
INPUT
socket.
This
input
is
not
switched
off
during
an
internal
sweep.
Utric
SWEEP
TRIG
INPUT
t
f
‘stop
ere
fstop™
dial
reading
.
muiltiptied
by
the
factor
of
the
frequency
eis
range
selector
9
fstaRT
7
adiustment
of
FREQUENCY
Hz
ht
knob
START
START
FREQ
sweep
range
selector
SWEEP
PERIOD
and
knob
PERIOD
time
SWEEP
OUT
Internal
Sweep
Diagram
of
a
sweep
period
with
the
sweep
output-voltage
SWEEP
OUT
and
the
triggering
signal
SWEEP
TRIG
INPUT.

16
3.2.5,
External
sweep
and
frequency
modulation
The
signal
frequency
of
the
generator
can
be
controlled
by
connecting
an
external
voltage
to
SWEEP
iNPUT.
In
order
to
avoid
superpositions
by
the
internal
sweeps,
switch
the
range
selector
SWEEP
PERIOD
s
to
OFF.
The
desired
signal
frequency
(=
basic
frequency)
must
then
be
adjusted
by
means
of
the
dial
and
the
range
selector
FREQENCY
Hz.
By
feeding
a
dc
or
ac
voltage
to
the
sweep
oscilla-
tor
via
SWEEP
INPUT,
the
signal
frequency
is
varied
proportional
to
this
voltage
(the
relationship
between
voltage
and
frequency
is
linear).
The
maximum
variation
should
not
exceed
2
1/2
decades,
where
the
upper
limit
of
the
sub-range
is
the
upper
limit
for
the
sweep
range
too.
Otherwise
you
would
get
signal
distortions
because
of
overdriving
the
controlled
current
source.
DIAL
READING
SWEEP
VOLTAGE
SWEEP
FREQUENCY
Uc
[VOLT]
20
10
External
sweep
Sweep
range
depending
on
the
sweep
voltage
Ue.
Example
for
subrange
V
(1
KHz
-
20
KHz)

Bedienungsanleitung

Other manuals for PM 5132
1
Table of contents
Languages:
Other Philips Portable Generator manuals
Popular Portable Generator manuals by other brands

Valex
Valex EX 5505 operating instructions

ISKCO
ISKCO HAG Series quick start guide

Generac Power Systems
Generac Power Systems XP4000 Professional specification

REM POWER
REM POWER GSEm 1000 SBi owner's manual

Xantrex
Xantrex Freedom Sequence installation guide

Briggs & Stratton
Briggs & Stratton 30255 Illustrated parts list