humidity in living areas. The surface temperature of the components must lie above the dew point
temperature of the indoor air (at least about +15°C).
In normal operation, germs or mould cannot form inside the device unit since the humidification water is
continuously treated and disinfected during operation.
Mounting
The device is intended for horizontal mounting. It may deviate a maximum of +/-1° from the horizontal
position and must be mounted to a massive wall that can bear the load. The intrinsic operating weight of
the air humidification unit must be taken into consideration for the suspension. No shocks or jolts may
affect the device. For mounting and setup, the national and local regulations must be observed. The
device may be installed only in compliance with the national installation regulations.
Electrical connection
The electrical connection of the supply and sensor line should be performed by an electrician
according to the local regulations. Before the device is opened, the voltage supply must be shut
off at all poles and secured against reactivation. If the mains connecting line of the device is damaged or
defective, it must be repaired or replaced immediately to prevent risks. This work may be performed only
by authorised expert personnel.
Water connections
The water, heating, and waste water connections must be established by an expert. For the connection to
the water supply, only the original connecting hoses provided in delivery may be used. Pay attention to the
seal tightness of the lines. The maximum water pressure of the mains water supply of 0.7 MPa and of the
water heater battery of 1 MPa may not be exceeded.
Water quality
Only mains water that corresponds with the local mains water ordinance may be used for the water supply.
The water inlet pipe to the air humidification unit should be established using optionally available
connection sets.
In case of a chlorine content over 0.1 mg/l, the standard water filter (5 μm) must be replaced by a dual
filter (5 μm/carbon). If the iron content of the mains water exceeds a value of 0.1 mg/l, an iron filter should
also be built into the water inlet pipe.
The device can be used for a maximum hardness of water of 26°dH. When this value is exceeded, the
service life of the reverse osmosis membrane is considerably reduced.
Operation of the device
Every working method that impairs the safety of the device is prohibited. All warning and safety devices
should be regularly checked for proper function. Safety devices may not be disassembled or
decommissioned.
Mounting, disassembly, maintenance, and servicing of the device
If maintenance work or repairs are performed, the device should be de-energised. The attachment or
installation of additional equipment is not permitted. In this case, please consult with the manufacturer.
Electrical system/electronics Work on the electrical plant parts may be performed only by
electricians. If maintenance work or repairs are performed, the device should be de-energised.
In case of faults in the electrical voltage supply, shut down the device immediately. Use only
original fuses with the required current strength. Check the electrical equipment of the device regularly.
Discovered defects like loose connections or scorched cables must be eliminated immediately. After the
electrical work or servicing has been performed, the safety measures should be tested (e.g. earthing
resistance).
Requirement on the installation site
The installation of the air humidification unit may take place only in rooms that have an existing water
outlet. In addition, safety measures that automatically close the water supply to the air humidification unit
in case of leakage (e.g. safety valve/water connection set) must be taken within the room. The air
humidification unit is designed in IP20 type of protection.