Pilz PSSnet GW1 MOD--CAN User manual

PSSnetGW1MODCAN
OperatingManual1002693EN03
Gateways

Preface
Thisdocumentisatranslationoftheoriginaldocument.
AllrightstothisdocumentationarereservedbyPilzGmbH&Co.KG.Copiesmaybemade
forinternalpurposes.Suggestionsandcommentsforimprovingthisdocumentationwillbe
gratefullyreceived.
Pilz®,PIT®,PMI®,PNOZ®,Primo®,PSEN®,PSS®,PVIS®,SafetyBUSp®,
SafetyEYE®,SafetyNETp®,thespiritofsafety®areregisteredandprotectedtrademarks
ofPilzGmbH&Co.KGinsomecountries.
SDmeansSecureDigital

Content
OperatingManualPSSnetGW1MODCAN
1002693EN03 3
Section1 Introduction 5
1.1 Validityofdocumentation 5
1.2 Usingthedocumentation 5
1.3 Definitionofsymbols 5
Section2 Overview 7
2.1 Modulefeatures 7
2.2 Unitview 8
2.2.1 Front 8
2.2.2 Top 9
2.2.3 Righthandside 9
2.2.4 Bottom 10
Section3 Safety 11
3.1 Intendeduse 11
3.1.1 Electromagneticcompatibility 11
3.1.1.1 Connectingtheearthcables 12
3.1.1.2 Cablerouting 13
3.1.1.3 Equipotentialbonding 13
3.1.1.4 Shielding 14
3.1.1.5 Lightinginthecontrolcabinet 14
3.1.1.6 TestingtheEMCcomplianceofaninstallation 15
3.2 Safetyregulations 16
3.2.1 Useofqualifiedpersonnel 16
3.2.2 Warrantyandliability 16
3.2.3 Disposal 16
3.3 Safetyduringinstallation 16
Section4 Functiondescription 18
4.1 Operation 18
4.1.1 Blockdiagram 19
4.2 Modbus/TCP 19
4.2.1 Modbus/TCPdataranges(Serverconnections) 19
4.2.2 Datatransferlimits 20
4.2.3 Functioncodes(Clientconnections) 20
4.3 CANopen 22
4.4 Translationtables 22
4.4.1 Payload 22
4.4.2 Diagnosticdata 23
4.5 Interfaces 26
Section5 Installation 27
5.1 Generalinstallationguidelines 27
5.1.1 Dimensions 28
5.2 Mountingdistances 29
5.3 Supplyvoltage 29
5.4 InstallGateway 30

Content
OperatingManualPSSnetGW1MODCAN
1002693EN03 4
Section6 Commissioning 31
6.1 Generalwiringguidelines 31
6.2 Wiringtheunits 31
6.2.1 Cablerequirements 31
6.2.2 Terminals 32
6.3 Terminalconfiguration 32
6.4 Interfaces 32
6.4.1 CANopeninterface 32
6.4.2 CANopentermination 33
6.4.3 RJ45interface 33
6.4.3.1 RJ45connectioncable 33
6.5 Setaddressesandtransmissionrate 34
6.5.1 SetIPaddress 34
6.5.2 Setdeviceaddress 35
6.5.3 Settingthetransmissionrate 35
Section7 Operation 36
7.1 Displayelements 36
7.1.1 Displayelementsfordevicediagnostics 36
7.2 Webserver 37
7.2.1 Callwebserver 37
7.2.2 Passwordmanagement 37
7.3 Performfirmwareupdate 38
7.4 ExchangeGateway 39
Section8 Technicaldetails 40
Section9 Orderreference 43

Introduction
OperatingManualPSSnetGW1MODCAN
1002693EN03 5
1 Introduction
1.1 Validityofdocumentation
ThisdocumentationisvalidfortheproductPSSnetGW1MODCAN.Itisvaliduntilnew
documentationispublished.
Thisoperatingmanualexplainsthefunctionandoperation,describestheinstallationand
providesguidelinesonhowtoconnecttheproduct.
1.2 Usingthedocumentation
Thisdocumentisintendedforinstruction.Onlyinstallandcommissiontheproductifyou
havereadandunderstoodthisdocument.Thedocumentshouldberetainedforfutureref
erence.
1.3 Definitionofsymbols
Informationthatisparticularlyimportantisidentifiedasfollows:
DANGER!
Thiswarningmustbeheeded!Itwarnsofahazardoussituationthatposes
animmediatethreatofseriousinjuryanddeathandindicatespreventive
measuresthatcanbetaken.
WARNING!
Thiswarningmustbeheeded!Itwarnsofahazardoussituationthatcould
leadtoseriousinjuryanddeathandindicatespreventivemeasuresthatcan
betaken.
CAUTION!
Thisreferstoahazardthatcanleadtoalessseriousorminorinjuryplus
materialdamage,andalsoprovidesinformationonpreventivemeasures
thatcanbetaken.
NOTICE
Thisdescribesasituationinwhichtheproductordevicescouldbedam
agedandalsoprovidesinformationonpreventivemeasuresthatcanbe
taken.Italsohighlightsareaswithinthetextthatareofparticularimport
ance.

Introduction
OperatingManualPSSnetGW1MODCAN
1002693EN03 6
INFORMATION
Thisgivesadviceonapplicationsandprovidesinformationonspecialfea
tures.

Overview
OperatingManualPSSnetGW1MODCAN
1002693EN03 7
2 Overview
2.1 Modulefeatures
ThePSSnetGW1MODCAN
}operatesasaprotocolconverterbetweenModbus/TCPandCANopen,
}canbeusedtoexchangedatabetweenproductsthatsupportModbus/TCPor
CANopen.Forexample,thismaybeacontrolsystemfromtheautomationsystem
PSS4000fromPilzononesideandathirdpartyproductontheother.Thethirdparty
productmustsupportCANopen.
FeaturesofthePSSnetGW1MODCAN:
}CanbeusedwithPilzproductsthatsupportModbus/TCP:
– ControlsystemsfromtheautomationsystemPSS4000(e.g.PSSuH)
– Compact/modular3rdgenerationPSSrangeprogrammablesafetysystems(e.g.
PSSSB30063ETH2,PSS(1)SBCPU3ETH2)
– OperatorterminalsPMIwithModbus/TCPinterface(e.g.PMI5)
– Motioncontrolsystems(e.g.PMCprimoDrive3,PMCprimoDriveP,PMCprimo16+)
}1xRJ45socketforconnectiontoModbus/TCP,
}Canmanageupto8Modbus/TCPconnections
}CanoperateasaModbus/TCPconnectionServer,
}WebserverformanagingandconfiguringtheGateway,
}SupportsCiA301V4.2.0,
}OperatesasaSlaveintheCANopennetwork,
}Transmissionrate10MBit/s(10BaseT)and100MBit/s(100BaseTX),
}1xmale9pinDSubconnectorforconnectiontoCANopen,
}supportsautonegotiating,
}LEDsfordisplayingthecommunicationstatusanderrors,
}input/outputdata
– upto512Bytesacyclicaldata(SDO),
– intotal(RxPDOandTxPDO)max.512Bytes,
– additionallyitispossibletotransferdatabetweenthecontrolsystems,
}supplyvoltage
– 20msbufferincaseofsupplyinterruptions,
– pluginconnectionterminals(eitherspringloadedterminalorscrewterminal).

Overview
OperatingManualPSSnetGW1MODCAN
1002693EN03 8
2.2 Unitview
2.2.1 Front
22,5 (0,88“)
Fig.:Frontview
:LEDsfordisplayingthecommunicationstatusandfaults
:RotaryswitchDRforsettingthetransmissionrate
:RotaryswitchX10forsettingthetensdigitofthedeviceaddress;thisistheaddress
usedtoaddresstheGatewayoftheCANopenMaster.Thisaddressmustbesetinthesoft
warefortheCANopenMaster
:RotaryswitchX1forsettingtheunitsdigitofthedeviceaddressforthisGateway
:CANopeninterface(male9pinDSubconnector)
:Barcodewiththeitemnumber,serialnumberandversionoftheGateway
:MACaddress
:2DcodewiththeMACaddress

Overview
OperatingManualPSSnetGW1MODCAN
1002693EN03 9
2.2.2 Top
OFF ON
IP-ADDRESS
128
64
32
16
8
4
2
1
Fig.:Top
:Modbus/TCPinterface(RJ45)
:DIPswitchforIPaddress
2.2.3 Righthandside
110 (4,33“)
96 (3,78“)
128
64
32
16
8
4
2
1
IP-Address
4,25 (0,17“)
Fig.:Righthandside
:QRcodewithalinktothePilzhomepagewithfurtherinformationontheGateway

Overview
OperatingManualPSSnetGW1MODCAN
1002693EN03 10
2.2.4 Bottom
Fig.:Bottom
:Supplyvoltageconnection

Safety
OperatingManualPSSnetGW1MODCAN
1002693EN03 11
3 Safety
3.1 Intendeduse
TheproductservesasaprotocolconverterbetweenModbus/TCPandCANopen.Itcanbe
usedwithvariousPilzproductsaswellasthirdpartyproducts,providedtheysupportthe
documentedpropertiesandrequirements.
}Modbus/TCP
TheGatewaycanbeusedwithproductsthatoperateasconnectionClientduringdata
exchange.Theproductmustsupportatleastoneofthedocumentedfunctioncodes.
}CANopen
TheGatewaycanbeusedasapassivesubscriber(Slave)inaCANopennetwork.The
basicfunctionsofcommunicationviaCANopencorrespondtotheSystemDescription
publishedbytheCANopenUserGroup.
TheGatewaymaynotbeusedforsafetyrelatedfunctions.
IntendeduseincludesmakingtheelectricalinstallationEMCcompliant.Theproductisde
signedforuseinanindustrialenvironment.Itisnotsuitableforuseinadomesticenviron
ment,asthiscanleadtointerference.
Thefollowingisdeemedimproperuseinparticular:
}Anycomponent,technicalorelectricalmodificationtotheproduct
}Useoftheproductoutsidetheareasdescribedinthismanual
}Useoftheproductoutsidethetechnicaldetails(seechapterentitled“TechnicalDe
tails”)
3.1.1 Electromagneticcompatibility
Toensureelectromagneticcompatibilitythecorrectproceduresmustbecarriedoutduring
installation.
Adeviceiselectromagneticallycompatibleif:
}Itfunctionswithouterrorinagivenelectromagneticenvironment
}Itdoesnotadverselyaffectitsownenvironment.
Electromagneticinterferencecanreachthedevicesthrough:
}Fields
}Powersupplies
}Earthcabling
}Busconnections
}Interfaces
}Inputandoutputcables
Theinterferencecanbetransferredfromtheproducer(source)tothereceiver(interference
sink)viathecouplingroutes.
Interferencereachestheinterferencesink(e.g.thecontrolsystemdevices)invariousways:

Safety
OperatingManualPSSnetGW1MODCAN
1002693EN03 12
}DCcoupling:
DCcouplingoccursifthesourceandsinkofinterferencehavecommoncableconnec
tions.Thecommoncablepresentscomplexresistances,inducingpotentialdifferences.
Typicalsourcesofinterferenceareswitches/relays,runningmotorsorvaryingpoten
tialsforothersystemsonthesamepowersupply.
}Capacitive(electrical)coupling:
Adifferentpotentialbetweenthesourceandinterferencesink(e.g.twocables)creates
anelectricalfield.Couplingisproportionaltotherateofvoltagechange.
Typicalsourcesofinterferencearecontactors,staticdischarge,parallelsignalcables.
}Inductive(magnetic)coupling:
Alivecableproducesamagneticfieldwhichalsosurroundsadjacentcables.Interfer
encevoltageisinduced.Couplingisproportionaltotherateofcurrentchange.
Typicalsourcesofinterferencearemainscablesrunninginparallel,livecables,high
frequencycables,inductors,transformers,motors.
}Electromagneticcoupling:
Acablecanemitasignalasaradiowave.Thiswaveisthenpickedupbyanother
cable.
Typicalsourcesofinterferencearetransmitterssuchasradios,sparksfromspark
plugs,weldingequipment,etc.
NOTICE
PowerfulHFtransmittersshouldonlybeoperatedatadistanceofmore
than0.6m.
}Staticdischarge:
Staticdischargeoccurswherethereareveryhighdifferencesinpotentialbetweentwo
points.Ifthetwopointsarebroughtclosertogetherorifthepotentialdifferenceisin
creased,dischargescanoccurintheairgaps.
Typicalsourcesofinterferencearepeoplewhoarestaticallychargedfromasynthetic
carpet,forexample.
3.1.1.1 Connectingtheearthcables
Pleasenote:
}Aconductorcrosssectionofatleast2.5mm2shouldbeusedfortheconnectiontothe
centralearthbar.Connectionsshouldbekeptasshortaspossible.
}Connectionstotheearthbarshouldalwaysbeinstarform.
}Connecttogetherthe0Vconnectionsonallthe24Vpowersuppliesandearththe0V
mainsatasinglepoint,orensurethatmeasuresareinplacetomonitorforearthfaults.
Earthedsupplyvoltagesofferthebestnoiseimmunity.
}Theconnectionofthe0Vsupplytothecentralearthbarorearthfaultmonitormustbe
inaccordancewithrelevantnationalregulations(suchasEN602041,NFPA79:177,
NEC:Article250).
}Connectionsshouldbeprotectedfromcorrosion.

Safety
OperatingManualPSSnetGW1MODCAN
1002693EN03 13
}Flexibleearthingstrapsshouldbeusedonmovingearthparts(e.g.machineparts,
gates).Ensuretheseearthingstrapsareasshortandwideaspossible.
3.1.1.2 Cablerouting
Itispossibletodifferentiatebetweencablesaccordingtotheirfunction.The
followinggroupsexist:
}Group1:DataandsupplylinesforDCvoltagesbelow60VandACvoltagesbelow25
V
}Group2:DataandsupplylinesforDCvoltagesfrom60Vto400VandACvoltages
from25Vto400V.
}Group3:Supplylinesabove400V
Cablinginsidebuildings:
}Thecablegroupslistedaboveshouldbelaidseparately.
}Cablesofthesamegroupcanbelaidwithinthesamecableduct.
}Cablesfromgroup1andgroup2shouldbelaidinseparategroupsorincableducts
whichareatleast10cmapart.
}Cablesfromgroup1andgroup3shouldbelaidinseparategroupsorincableducts
whichareatleast50cmapart.
}Dataandsignallinesshouldbelaidascloseaspossibletoanearthedsurface.
Cablingtoopenairsystems:
}Asfaraspossibleusemetalconduits.Theseshouldbeelectricallyconnectedand
earthed.
}Ensurethereissufficientprotectionagainstlightningbyusingmetalconduitsearthedat
bothends,orconcretecableductswithreinforcementsconnectedacrossthejoints.
3.1.1.3 Equipotentialbonding
Potentialdifferencescanoccurifthedevicesareconnectedtodifferentearthorground
connections.Evencableshieldsthatareconnectedateitherendandhavedifferentearth
connectionscancausepotentialdifferences.Inordertoavoidinterference,equipotential
bondingcablesmustbeinstalled.
Indoingsoyoumustensurethefollowing:
}Selectalowimpedanceequipotentialbondingcable.
}Selectthefollowingasstandardvaluesforthecrosssectionoftheequipotentialbond
ingcables:
– 16mm2forequipotentialbondingcableupto200minlength
– 25mm2forequipotentialbondingcableover200minlength
}Ifthecontrolsystemdevicesareconnectedwithshieldedsignalcableswhichare
earthedateitherend,theimpedanceiscalculatedasfollows:
– Impedanceequipotentialbondingcable=10%ofshieldimpedance
}Usecopperorgalvanisedsteelequipotentialbondingcable.

Safety
OperatingManualPSSnetGW1MODCAN
1002693EN03 14
}Connectequipotentialbondingcablestotheearthbaroveraswideasurfaceareaas
possible.
}Asshortadistanceaspossibleshouldbekeptbetweentheequipotentialbondingcable
andsignalcable.
3.1.1.4 Shielding
Interferencecurrentsmustbedivertedtocableshieldsviashieldbars.
Indoingsoyoumustensurethefollowing:
}Connecttheshieldswithlowimpedancetotheshieldbarorearthbar.
}Usecableswithbraidedscreening,withaminimumcoverareaof80%.
}Whenlayingcableswithoutequipotentialbondingorusingfoilshields:Connectthe
shieldatoneend.
}Ifpossible,usemetalormetallisedplugstoconnectcablesforserialdatatransfer.Al
waysrefertotheregulationsrelatingtothefieldbussystems.
}Iftheshieldisnottobeconnectedattheendofthecable,itmusthavenoconnection
totheconnectorhousing.
}Iftheshieldistobeconnected,connectittotheshieldbaratthepointwherethecable
entersthecabinet,withoutmakingabreakinthecable.Usemetalcableclampswhich
covertheshieldoverawidesurfacearea.Routetheshieldasfarastheunits,butdo
notconnectittotheunits.
Digitalinputsandoutputsdonotneedshieldedcables.
However,iftheconnectioncableshaveashield,itshouldbeconnectedatoneend.
Analogueinputsandtheincrementalencoderinputsonspeedmonitorsshouldalwaysbe
connectedusingshieldedcables.
3.1.1.5 Lightinginthecontrolcabinet
Uselowinterferencepanellightingforinsidethecontrolcabinet.

Safety
OperatingManualPSSnetGW1MODCAN
1002693EN03 15
3.1.1.6 TestingtheEMCcomplianceofaninstallation
YoucanusethelistbelowtocheckthattheinstallationoftheGatewayisEMCcompliant.
Check Measures Done
Arethereareaswithahigh
probabilityofinterference?
(e.g.computersrunning,
processcontrolareas,dis
tributioncabinets,cable
casing,frequencyconvert
ers,handheldradiosetc.).
EMCprotectionintheseareasshouldbeplanned
withparticularcare.
Areareaswherecom
putersarerunningor
areassuchasprocess
controlroomssufficiently
shieldedfromelectromag
neticcoupling?
Ifnecessaryshieldthewholearea.
Doesthecablelayouttake
intoaccounttheprinciples
ofEMCcompliance?
Someimportantpoints:Laycablesclosetoearth,
keepclearofotherelectricalequipment,keep
cablesinductsseparatefromotherpartsofthe
installation,keepcablesasshortaspossible,
avoidmultiplecrossovers.
Isthesupplyvoltagefree
ofinterference?
Supplieswithinterferencevoltagesshouldbefit
tedwithamainsfilter.
EMCcharacteristicsofin
dividualunits/allunits
testedonceinstalled?
TestEMCcharacteristicsunderoperatingcondi
tions,e.g.whilehandheldradiosareinuse,or
HFfrequencygeneratorsarecloseby.Teststatic
dischargewithoperatingpersonnel,testmutual
interferencebetweenunitsunderdifferentoperat
ingconditions.
Earthedpartsconnected
correctly?
Theconnectionsbetweentheunits,rackingbars,
earthconductorsandshieldbarsareimportant.
Inactivemetalpartsshouldbeconnectedovera
widesurfaceareaandearthedatacentralpoint;
withinsulatedmetal:Removeinsulationoruse
specialcontactfixings;protecttheconnection
fromcorrosion;connectthecabinetdoorstothe
bodyofthecabinetusingearthingstraps.
Cablegroupslaidsepar
ately?
Separatecablesintogroups.Supplyandsignal
leadsshouldbelaidseparately.
Aretheshieldsconnected
correctly?
Useshieldedcablesforanalogueanddataleads;
usemetallicplugs;connectcableshieldstoshield
baratpointofentrytocabinet;connectcable
shieldsoverawidesurfaceareaandwithlowim
pedance.
Equipotentialbondingcar
riedout?
Iftheinstallationextendsoverawidearea:lay
equipotentialbondingcable.
Areinductiveloads
switched?
Sufficientfuseprotectionshouldbeusedwithin
ductiveloads
24VDCpowersupply? PowersuppliesmustconformtoEN
60742:9/1995,EN609501:2006/A11:2009orEN
50178:10/97.

Safety
OperatingManualPSSnetGW1MODCAN
1002693EN03 16
3.2 Safetyregulations
3.2.1 Useofqualifiedpersonnel
Theproductsmayonlybeassembled,installed,programmed,commissioned,operated,
maintainedanddecommissionedbycompetentpersons.
Acompetentpersonissomeonewho,becauseoftheirtraining,experienceandcurrentpro
fessionalactivity,hasthespecialistknowledgerequiredtotest,assessandoperatethe
workequipment,devices,systems,plantandmachineryinaccordancewiththegeneral
standardsandguidelinesforsafetytechnology.
Itisthecompany’sresponsibilityonlytoemploypersonnelwho:
}Arefamiliarwiththebasicregulationsconcerninghealthandsafety/accidentpreven
tion
}Havereadandunderstoodtheinformationprovidedinthisdescriptionunder"Safety"
}Andhaveagoodknowledgeofthegenericandspecialiststandardsapplicabletothe
specificapplication.
3.2.2 Warrantyandliability
Allclaimstowarrantyandliabilitywillberenderedinvalidif
}Theproductwasusedcontrarytothepurposeforwhichitisintended
}Damagecanbeattributedtonothavingfollowedtheguidelinesinthemanual
}Operatingpersonnelarenotsuitablyqualified
}Anytypeofmodificationhasbeenmade(e.g.exchangingcomponentsonthePCB
boards,solderingworketc.).
3.2.3 Disposal
Whendecommissioning,pleasecomplywithlocalregulationsregardingthedisposalof
electronicdevices(e.g.ElectricalandElectronicEquipmentAct).
3.3 Safetyduringinstallation
Theproductrequiresa24VDCsupply.Checkthattheexternalpowersupplyprovidesthis
voltage.
Thetoleranceofthesupplyvoltagemustcomplywiththetechnicaldetails.Safeoperation
cannotbeguaranteedoutsidethisrange.
Protecttheexternalpowersupplybyfittingafusebetweentheexternalpowersupplyand
theproduct.Thesizeofthefusewilldependonthespecificationoftheexternalpowersup
ply,theconductorcrosssectionandonlocalregulations.

Safety
OperatingManualPSSnetGW1MODCAN
1002693EN03 17
WARNING!
Riskofelectrocution!
Safeelectricalisolationmustbeensuredfortheexternalpowersupplythat
generatesthesupplyvoltage.Failuretodosocouldresultinelectricshock.
ThepowersuppliesmustcomplywithEN609501:2006/A11:2009,EN
6155826:11/1997.
WARNING!
Riskofelectrocution!
Whenvoltageisapplied,contactwithlivecomponentscouldresultinseri
ousorevenfatalinjuryfromanelectricshock.

Functiondescription
OperatingManualPSSnetGW1MODCAN
1002693EN03 18
4 Functiondescription
4.1 Operation
TheGateway
}operatesasaprotocolconverterbetweenModbus/TCPandCANopen,
}operatesontheModbus/TCPsideasconnectionServerandontheCANopensideas
Slave,
}UsesanLEDtoindicatewhetherthereisdatatrafficviatheconnection
}UsesanLEDtoindicatetheinterfaceusedforthisdatatraffic
}IftheconnectiontoCANopenortoModbus/TCPisnolongeravailable,thepayloadis
retainedwiththecurrentvalues
}isexclusivelydesignedforexchangingnonsafetyrelateddata
TheGatewayisinterposedinthedataflowbetweentheconnecteddevices.
Fig.:Protocolconversion,Modbus/TCPtoCANopen
}SignalpathfromCANopenenabledproducttoModbus/TCPenabledproduct:
CANopenenabledproduct >CANopeninterfaceontheGateway >Protocolcon
version >Datainput/outputModbus/TCPinterface >Modbus/TCPenabled
product
}SignalpathfromModbus/TCPenabledproducttoCANopenenabledproduct:
Modbus/TCPenabledproduct >Datainput/outputModbus/TCPinterface >Pro
tocolconversion >CANopeninterfaceontheGateway >CANopenenabled
product

Functiondescription
OperatingManualPSSnetGW1MODCAN
1002693EN03 19
4.1.1 Blockdiagram
Connection to
Modbus/TCP
1x CANopen
24 V 0 V
Mapping
Power
Fig.:Blockdiagram
4.2 Modbus/TCP
TheGatewaycanmanageamax.of8Modbus/TCPconnections.TheGatewayisalways
theconnectionServer.TheconnectionClientsmaybevariousdevices,e.g.PC,control
system,displayunit.TheycanaccesstheGatewaysimultaneously.
Portnumber"502"intheGatewayissetasthedefaultfordataexchangeviaaModbus/
TCPconnection.
4.2.1 Modbus/TCPdataranges(Serverconnections)
TheproductsupportsthefollowingModbus/TCPdataareas:
Dataarea Modbussyntax Example
Coils(Bit)
0x00000…0x65535
[read/write]
0x[xxxxx] 0x00031
DiscreteInputs(Bit)
1x00000…1x65535
[readonly]
1x[xxxxx] 1x08193
InputRegister(Wort/16Bits)
3x00000…3x65535
[readonly]
3x[xxxxx] 3x00002
HoldingRegister(Wort/16
Bits)
4x00000…4x65535
[read/write]
4x[xxxxx] 4x00805
Modbus/TCPdataareas

Functiondescription
OperatingManualPSSnetGW1MODCAN
1002693EN03 20
INFORMATION
AddressingforPilzsystemsstartsat"0".Ondevicesfromothermanufactur
ers,addressingmaystartat"1".
Pleaserefertotheoperatingmanualprovidedbytherelevantmanufacturer.
4.2.2 Datatransferlimits
Thistablecontainsthemaximumdatalengthssupportedpertelegram:
Datatransfer
Max.datalengthpertele
gram
Readdata(Bit) FC01(ReadCoils) 1…2000
FC02(ReadDiscreteIn
puts)
Readdata(Word) FC03(ReadHoldingRe
gisters)
1…125
FC04(ReadInputRegister)
Writedata(Bit) FC05(WriteSingleCoil) 1Bit
FC15(WriteMultipleCoils) 1…1968
Writedata(Word) FC06(WriteSingleRe
gister)
1Word
FC16(WriteMultipleRe
gisters)
1…123Words
Readandwritedata(Word) FC23(Read/WriteMultiple
Registers)
Read1…125Words
Write1…121Words
Datatransferlimits
INFORMATION
Theremaybesomerestrictionsindatalength,dependingonthedevicethat
isused.Pleaserefertotheinformationstatedintheoperatingmanualofthe
relevantunit.
4.2.3 Functioncodes(Clientconnections)
TheconnectionClientcanaccesstheGateway'sdataareasusingthefollowingfunction
codes(FC):
Other manuals for PSSnet GW1 MOD--CAN
1
Table of contents
Other Pilz Gateway manuals
Popular Gateway manuals by other brands

Sierra Wireless
Sierra Wireless Airlink Raven XE H2225E manual

ABB
ABB RER601 Technical manual

Polygon Technologies
Polygon Technologies Micro Commander GC0101 user manual

IFM Electronic
IFM Electronic AC5225 Original Device Manual

Honeywell
Honeywell NetAXS-123 Startup guide

NetModule
NetModule NG800 user manual