POWERSYS RECLOSER User manual

User Manual Document Version 1.5 Feb 28, 2019
http://powersys.kr/
http://www.powersys.kr

Revision History
Revision
Date
Remark
1.0
2013-10-08
the first edition
1.1
2015-08-03
the first update
1.2
2017-01-01
the second update
1.3
2017-10-01
the third update
1.4
2018-02-07
the fourth update
1.5
2019-02-28
the fifth update

1. Safety Information
Please make sure if the product is broken before installing.
Please check if all the control power, current, voltage are off before
connecting or taking apart.
The terminal has a high current and high voltage so it can be
life-threatening when you touch it directly.
The setting should be done along the distribution line configuration.
The machine shows wrong information or malfunction caused by a
different setting from the distribution line configuration.
Connect the side connector along correct connector number with
current/voltage/DO/DI.
The appliance’s earthing terminal should be earthed to ground.
Caution !
Before installing the product, please read the instructions.

CONTENTS
1. Safety Information
2. Introduction ························································································ 1
2.1. Summary ··········································································································· 1
2.2. Main functions and features ······································································· 1
3. Technical Data ··················································································· 3
3.1. Power and Input/Output ·············································································· 3
3.2. Environmental ·································································································· 5
3.3. Communication ······························································································· 6
3.4. Measurements ································································································· 7
3.5. Mechanical Performance and Size ····························································· 8
4. Installation Instructions ···································································· 18
4.1. Front Panel and names of each part ······················································· 18
4.2. LCD Control and Setting ············································································· 21
4.2.1 Button Function ····················································································································· 21
4.2.2 LCD Display during Power Up ·························································································· 22
4.2.3 LCD Menu Operation ·········································································································· 23
4.2.4. LCD Menu Items ·················································································································· 23
4.3. Order of Installation Test Operation ························································ 33
5. LCD Menu ··························································································· 34
5.1. Display ··············································································································· 34
5.1.1. Display operation ················································································································· 34
5.1.2. Display Menu ························································································································ 34
5.2. Protection Setting Menu ·············································································· 35
5.2.1. Operation Principle of Recloser ······················································································· 35
5.2.2. Operation Principle of FI ··································································································· 36
5.2.3. Phase Fault ···························································································································· 38
5.2.4. Ground Fault ························································································································· 41
5.2.5. SEF Fault ································································································································· 42
5.2.6. Trip & Reclose ······················································································································ 43
5.2.7. Auxiliary Func ························································································································ 45

5.2.8. Select Group ·························································································································· 49
5.3. Configuration Menu ······················································································· 50
5.3.1. Analog ····································································································································· 50
5.3.2. DI Debounce Time ·············································································································· 52
5.3.3. DO Pulse Width ··················································································································· 52
5.3.4. Backup Set / Clear ·············································································································· 52
5.3.5. Analog Gain Adjust ············································································································· 52
5.3.6. Waveform ······························································································································· 53
5.3.7. Check Auto Battery ············································································································· 53
5.3.8. V/I Unbalance ······················································································································· 53
5.3.9. Sag/Swell ································································································································ 54
5.3.10. THD Alarm ··························································································································· 54
5.3.11. VI Wear ································································································································ 54
5.3.12. Analog High Alm ··············································································································· 54
5.3.13. Analog Low Alm ················································································································ 55
5.3.14. Misc. Config ························································································································ 55
5.4. Communication Menu ··················································································· 56
5.4.1. SCADA Port ··························································································································· 56
5.4.2. Modem Control ···················································································································· 56
5.4.3. DNP Config ····························································································································· 56
5.4.4. IEC101 Config ························································································································· 57
5.4.5. IEC104 Config ························································································································· 58
5.4.6. TCP/IP Config ·························································································································· 58
5.4.7. PSTN Modem ·························································································································· 58
5.4.8. PPP Config ······························································································································· 58
5.4.9. SMS Config ······························································································································ 59
5.4.10. Time Sync Option ·············································································································· 59
5.5. Time Set Menu ······························································································· 59
5.6. Event View Menu ··························································································· 61
APPENDIX A. COMTRADE File’s Formats ··········································· 62
APPENDIX B. RECLOSER Characteristic Curve ·································· 66
1. TC Curve ·················································································································· 66
2. TC Curve 1~4 ······································································································· 67
3. TC Curve 5~8 ······································································································· 68
4. TC Curve 8*~13 ··································································································· 69
5. TC Curve 14~18 ·································································································· 70
6. TC Curve A~D ······································································································ 71
7. TC Curve E~M ····································································································· 72

8. TC Curve N~T ······································································································ 73
9. TC Curve V~Z ······································································································ 74
10. TC Curve IEC NI~SI ···························································································· 75
11. TC Curve IEEE MI~NI ························································································· 76
12. TC Curve ANSI U8, U2 ······················································································ 77
13. TC Curve ES NI, VI ····························································································· 78
14. TC Curve KEPCO N1~N4 ·················································································· 79
15. TC Curve DEF 1S, 10S ······················································································· 80
APPENDIX C. Remote Control(option) ················································ 81

- 1 -
2. Introduction
2.1. Summary
Reclosers are used in distribution system. In case of line fault, due to temporarily
overcurrent, Reclosers can break and make currents several times, thus avoiding longer
network interruptions due to temporary faults. But, in case of permanent fault, because
fault current is still detected after trip and reclosing actions of pre-set sequences, Recloser
is locked out finally as opened.
The pre-set sequences are available to set five times, and for both phase and ground, the
combined operations are possible within the range of 5 instantaneous or 5 times delayed
operating. The first interruption of a fault regarding instantaneous operation, is done
quickly and instantaneously, so that even the fuses in the system do not operate. After
setting time, it recloses back on. And the next interruption has a definite or inverse time
delay. Thus downstream fuses or other protection devices in the network have the chance
to operate and isolate the affected network section, restoring normal operation in the
remaining work. Therefore reclosers make the range of fault section to be limited.
Mainly Reclosers which are installed in overhead distribution line, provide the measurement
of electric current flowing in the distribution line. In case of load current occurrence and
fault detection, it opens and recloses repeatedly according to setting sequence, and at the
sametime, it transmits the status/receives the command to/from HOST and remote controls
of opening/reclosing to minimize the accident. Besides, it stores the whole events in
distribution line, provides the fault causes, and it performs remote monitoring and controls
by transmitting data through DNP3.0, IEC60870-5-101, IEC60870-5-104 protocols.
2.2. Main functions and features
◆ Protection Function
- Fault Detection about phase and ground fault
- SEF(Sensitive Earth Fault) used on non-grounded network
- Inrush current control function during fault detection
- In case of Cold Load, Fault Pickup Level adjustment
- Phase Loss Detection
- Phase Sync Fail Detection about source and load voltage
- Automatic breaking and reclosing by detecting phase and ground fault
- Detecting fault and monitoring the status in distribution line
- Built-in 50 types of recloser curves including IEC, ANSI/IEEE, McGraw Edison Recloser
curve
- Equiped with 4 types of curves(N1, N2, N3, N4) developed by Korea Electric Power
Research Institute(KEPRI, under KEPCO)

- 2 -
- Additionally user defined 4 types of curves available
- 3 steps protection characteristics implementable, established with definite time elements
and high-current elements
◆ Measuring Function
- Current, voltage magnitude and phase angle
- Symmetrical component about 3-phase voltage and current
- Active, reactive, apparent power, and power factor
- Active and reactive energy
- Frequency
- Power quality information : THD, sag/swell, harmonic 2~32th
◆ Control Function
- Recloser switch Open / Close control
- Battery Test control
- Preparatory control
◆ State Monitoring Function
- Recloser Open / Close status
- Handle locked status
- Gas pressure low status(option)
- External AC low status
- Battery overcharge status
- Door Open
- Spare status 1,2
- Over dischager
- Chager fail
◆ Various Communication Interface
- System Interface Port : RS232C
DNP3.0
IEC60870-5-101
- System Interface Port(option) : Ethernet
DNP3.0 over TCP/IP
IEC60870-5-104
- Maintenance Port : USB-A, Wi-Fi(option)
MODBUS RTU
◆ Various Event Information
◎ Operation Event
It stores and manages events occurred during operation such as control(On, Off, Trip)event
and diagnosis event up to 30,000 cases in time sequence.

- 3 -
◎ Fault Event
It stores and manages various fault information(occurred time, type of fault, operation
relaying element) during distribution line accidents up to 1024 cases in time sequence.
◆ Fault Wave Storage Function
It saves and manages the latest fault 160Cycle(16Sample standard) sample data up to 6
cases. The user can use save fault wave to analyze the cause of faults.
◆ Convenient interface for users
Through RS232 communication port, it is convenient to manage various set values and
stored measuring information search on PC.(using company supplied S/W)
◆ Self-diagnosis and Backup functions during power-off
EPIC-R300 operates self-diagnosis such as CPU check, memory error diagnosis, I/O
diagnosis, and control power diagnosis. It saves warning output and diagnosis event on
occasion of failure. Therefore the user can have a speedy response.
3. Technical Data
3.1. Power and Input/Output
◆ Power Supply
◆ Current Input(Ground System)
◆ Current Input(Non-Ground System)
Voltage input
Power consumption
DC 24V
within 10W
Channel
Rating input
Input burden
4 channels
(Ia,Ib,Ic,I0)
Rated current(Ia,Ib,Ic) : 1A (Max:12A)
Rated current(I0) : 1A (Max:12A)
Under 1VA
Channel
Rating input
Input burden
4 channels
(Ia,Ib,Ic,In)
Rated current(Ia,Ib,Ic) : 1A (Max:12A)
Rated current(In) : 1A (Max:12A)
Under 1VA

- 4 -
◆ Voltage Input
◆ Digital Input
◆ Digital Output
◆ Logic Functions (option)
EPIC-R300 provides logic function. It can output the information about inside device with
DO, DI, etc, which are processed by using the functions of AND, OR, NOT, Timer, SR
Latch, etc, with DO, DI. And it can also be passed to the upper system through
communication.
Basic logic function is as shown below table.
Input Type
Point Number
Input Circuit
Others
Opto-Isolation
10 Port
DC 24V Input Biased
Debounce Delay
(1~500ms)
Control contact (Photomos)
Normal contact
100mA/250VAC
5A/250VAC
2EA
4EA, 8EA(option)
Purpose : Recloser Open / Close
Purpose : Battery Test / Spare
Channel
Rating input
Input burden
6 channels
(Va,Vb,Vc,
Vr,Vs,Vt)
Rated voltage : 4V (Max : ~8V)
Under 0.1VA
Function
Description
Input
Physical input, virtual input,
Output
Physical output, virtual output
AND
For two inputs, AND gate
OR
For two inputs, OR gate
NOT
For one inputs, NOT gate
NAND
For two inputs, NAND gate
XOR
For two inputs, XOR gate
SR
Latch of Set / Reset
Timer
Timer with settings of Set, Reset, On/Off Delay Timer
D Flip-Flop
To maintain froze the input signal for one PLC cycle

- 5 -
3.2. Environmental
Items
Spec
Temperature
Operating
-25 ~ 85℃
Storage
-40 ~ 95℃
Humidity
< 95% RH
Altitude
< 4000m
Insulation Resistance
DC500V, > 100MΩ
Dielectric Withstand
AC 60Hz 2000V/1Min
Impulse
IEC60255-5 6kV : Current
IEC60255-5 4kV : Voltage, Power, DIO
High Frequency
Disturbance
IEC60255-22-1 2.5kV
EFT/Burst
IEC60255-22-4 Class A : 4kV
Radiated -
electromagnetic field
IEC60255-22-4 10V/m
ESD
60255-22-2: Contact(6kV), Air(8kV)
EMI
IEC 60255-25
Vibration
IEC 60255-21-1 class 2

- 6 -
3.3. Communication
◆ System Interface Port1
◆ System Interface Port2(can select RS232c or RS485)
Items
Spec
RS232C
9 Pin Signal
DCD(1), RX(2), TX(3), DTR(4), GND(5)
DSR(6), RTS(7), CTS(8), NC(9)
Speed
1200, 2400, 4800, 9600, 19200, 38400
Opto-Isolation Circuit (Dielectric level : 1kV)
DNP3.0
Protocol
support DNP3.0 Subset Level3
multi-frame transmission
Enable / Disable Unsolicited Response for each class
Save Event which is not transmitted
IEC60870
-5-101
Protocol
support single character NACK
Regular update about measurement data
capable to set address size
Items
Spec
RS232C
9 Pin Signal
RX(2), TX(3), GND(5)
RTS(7), CTS(8),
Speed
1200, 2400, 4800, 9600, 19200, 38400
Opto-Isolation Circuit (Dielectric level : 1kV)
RS485
9 Pin Signal
485+(6), 485-(9)
Speed
1200, 2400, 4800, 9600, 19200, 38400
Opto-Isolation Circuit (Dielectric level : 1kV)
MODBUS-RTU
Slave Mode : To communicate with SCADA

- 7 -
◆ System Interface Port3(option)
◆ Maintenance Port(USB-A, Wi-Fi)
Items
Spec
USB-A
4 Pin Signal
VCC(1), D-(2), D+(3), GND(4)
Speed
38400bps
MODBUS
-RTU
Protocol
setting, measuring, confirmation function of stored information
(failure information, driving information, Wave)
Maximum 120 point Read at once
Supply special SW for Maintenance
Option
Connection via Wi-Fi
3.4. Measurements
Items
Accuracy
Range
Voltage
1%
40kV (Including PT ratio)
Current
1%
12,000A (Including CT ratio)
kW,kVar,kVA
2%
0~99MW
Power Factor
2%
0~±1
Frequency
±0.01Hz
45~65Hz
kWh, kVarh
2%
0~999999999kW
THD
2%
0~200%
Items
Spec
Ethernet
10/100 Base-T
Tr Isolation Circuit
DNP3.0 over
TCP/IP
Protocol
Network Access Protocol for DNP3.0
Using standard TCP/IP network
(connection-oriented secure data transmission)
IEC60870
-5-104
Protocol
Network Access Protocol for IEC60870-5-101
Application layer is based on IEC60870-5-101
Using standard TCP/IP network
(connection-oriented secure data transmission)

- 8 -
3.5. Mechanical Performance and Size
◆ Weight : 3.5 kg
◆ FRONT VIEW
<Figure 3-1> Front View

- 9 -
◆ SIDE VIEW
343.00
310.00
91.00
<Figure 3-2> Side View

- 10 -
◆ TOP VIEW
84.0
260.0
225.0
1.0.0t
<Figure 3-3> Top View

- 11 -
◆ REAR VIEW
180.0
120.0
<Figure 3-4> Rear View

- 12 -
◆ Terminal Arrangement
RS232C(SCADA PORT)
RS232C(SCADA PORT)
Control Source Connector
DI (Status) Connector
DO (Control) Connector
ETHERNETConnector
AI(Voltage) Connector
AI(Current) Connector
<Figure 3-5> Terminal Arrangement

- 13 -
◆ Pin Assignment(Up Side View)
1) Control Power Connector
4
3
24G 24VIN
2
1
FG FG
2) DI (Status) Connector
14
13
12
11
10
9
8
DI_COM3 DI10
(Spare2) DI_COM2 DI9
(Spare1) DI_COM1 DI8
(Gas Low)
DI7
(Handle
Lock)
7
6
5
4
3
2
1
DI6
(Door
Open)
DI5
(Charger
Fail) DI_COM1 DI4
(Batt Low) DI3
(AC Loss) DI2
(Close) DI1
(Open)
3) DO (Control) Connector
12
11
10
9
8
7
DO6-
(Rec
Close)
DO6+
(Rec
Close) DO4- DO4+ DO3-
(Bat Test-) DO3+
(Bat Test+)
6
5
4
3
2
1
DO5-
(Rec
Open)
DO5+
(Rec
Open)
DO2-
(Close-) DO2+
(Close+) DO1-
(Open-) DO1+
(Open+)
4) AI(Voltage) Connector
10
9
8
7
6
V6 V4 V_COM V_COM V2
5
4
3
2
1
V5 V_COM V_COM V3 V1
5) AI(Current) Connector
6
5
4
3
2
1
IN(0)- IN(0)+ Icom IC IB IA

- 14 -
◆ Pin Assignment
FG FG
24VIN24G
DI1
(Open)
DI2
(Close)
DI3
(ACLoss)
DI4
(Batt Low)
DI_COM1
DI5
(Charger Fail)
DI6
(Door Open)
DO1+
(Open+)
IAIBICIcomIN(0)+IN(0)-
DO1-
(Open-)
DO3+
(Bat Test+)
DO3-
(Bat Test-)
DO2+
(Close+)
DO4+
DO2-
(Close-)
DO4-
DO5+
DO6+
DO5-
DO6- DI7
(HandleLock)
DI8
(GasLow)
DI_COM1
DI9
(Spare1)
DI_COM2
DI10
(Spare2)
DI_COM3
V1V3V_COMV_COMV5
V6 V2V_COM V_COMV4
RS232C
(SCADA Port)
RS232C
RS485 Port
<Figure 3-6> Pin Assignment
Table of contents
Popular Industrial Electrical manuals by other brands

Superior
Superior SD23 Operator's manual

Murata
Murata GRM31CR61H106KA12 Series Reference sheet

Murata
Murata GRM1885C1H562JA01 Series Reference sheet

Murata
Murata GQM2195C2A7R5CB01 Series Reference sheet

Moeller
Moeller VHI-NZM 10 installation instructions

Murata
Murata GRM155R72A222KA01 Series Reference sheet

Murata
Murata GRM0225C1C120GA03 Series Reference sheet

Omron
Omron V700-L11 user manual

Murata
Murata GRM1885C1H7R8DA01 Series Reference sheet

Espressif
Espressif ESP32 user guide

Murata
Murata GRM0335C1E750GA01 Series Reference sheet

Rockwell Automation
Rockwell Automation Allen-Bradley MobileView Terminal Application Technique