PR electronics 5531 User manual

5531
SIGNALS THE BEST
PENDING
Loop powered
LCD indicator
No. 5531V105-UK
From ser. no.:
121288001-108 & >121350001

(1330)
PR electronics A/S tilbyder et bredt program af analoge og digitale
signalbehandlingsmoduler til industriel automation. Programmet
består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere,
Universaltransmittere m. Vi har modulerne, du kan stole på i selv
barske miljøer med elektrisk støj, vibrationer og temperaturudsving,
og alle produkter opfylder de strengeste internationale standarder.
Vores motto »Signals the Best« er indbegrebet af denne loso –
og din garanti for kvalitet.
PR electronics A/S offers a wide range of analogue and digital
signal conditioning devices for industrial automation. The product
range includes Isolators, Displays, Ex Interfaces, Temperature
Transmitters, and Universal Devices. You can trust our products
in the most extreme environments with electrical noise, vibrations
and temperature uctuations, and all products comply with the
most exacting international standards. »Signals the Best« is the
epitome of our philosophy – and your guarantee for quality.
PR electronics A/S offre une large gamme de produits pour le
traitement des signaux analogiques et numériques dans tous
les domaines industriels. La gamme de produits s’étend des
transmetteurs de température aux afcheurs, des isolateurs aux
interfaces SI, jusqu’aux modules universels. Vous pouvez compter
sur nos produits même dans les conditions d’utilisation sévères,
p.ex. bruit électrique, vibrations et uctuations de température.
Tous nos produits sont conformes aux normes internationales les
plus strictes. Notre devise »SIGNALS the BEST« c’est notre ligne
de conduite - et pour vous l’assurance de la meilleure qualité.
PR electronics A/S verfügt über ein breites Produktprogramm
an analogen und digitalen Signalverarbeitungsgeräte für die in-
dustrielle Automatisierung. Dieses Programm umfasst Displays,
Temperaturtransmitter, Ex- und galvanische Signaltrenner, und
Universalgeräte. Sie können unsere Geräte auch unter extremen
Einsatzbedingungen wie elektrisches Rauschen, Erschütterungen
und Temperaturschwingungen vertrauen, und alle Produkte von
PR electronics werden in Übereinstimmung mit den strengsten
internationalen Normen produziert. »Signals the Best« ist Ihre
Garantie für Qualität!
DK
UK
FR
DE

5531V105-UK 3
EC declaration of conformity ............................................. 4
Application ......................................................................... 5
Technical characteristics.................................................... 5
Mounting / installation........................................................ 6
Technical specifications ..................................................... 7
Special conditions for safe use.......................................... 9
Field enclosure type 8501.................................................. 10
Ordering codes for 5531 .................................................... 11
Accessories........................................................................ 11
Block diagram .................................................................... 11
Programming...................................................................... 12
Routing diagram................................................................. 12
LOOP-POWERED LCD INDICATOR
PREVIEW TYPE 5531
Table of contents

4 5531V105-UK
EC DECLARATION OF CONFORMITY
As manufacturer
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
hereby declares that the following product:
Type: 5531
Name: Loop-powered LCD indicator
is in conformity with the following directives and standards:
The EMC Directive 2004/108/EC and later amendments
EN 61326-1 : 2006
For specification of the acceptable EMC performance level, refer to the
electrical specifications for the module.
The ATEX Directive 94/9/EC and later amendments
EN 60079-0 : 2009, EN 60079-11 : 2007,
EN 60079-26 : 2007
ATEX certificate: KEMA 05ATEX1044 X (5531A/B1)
ATEX certificate: KEMA 05ATEX1105 X (5531B/B2)
Notified body:
DEKRA Certification B.V. (0344)
Utrechtseweg 310, 6812 AR Arnhem
P.O. Box 5185, 6802 ED Arnhem
The Netherlands
Rønde, 19 November 2012 Kim Rasmussen
Manufacturer’s signature

5531V105-UK 5
LOOP-POWERED LCD INDICATOR 5531
• 4digit1/8DIN(48x96mm)loop-poweredLCD
display
• Easypush-buttonconfiguration
• BacklitLCDdisplayisreadableinlowlight
conditions
• DisplaycanbemountedinthesafeorExarea
• Availablewiththe8501fieldenclosure
Application
• The5531indicatorispoweredbythe4to20mAcurrentloopandiseasily
scaled to display the correct process value.
• Becauseitdoesnotrequireseparatepowerwiring,the5531isperfectfor
remote display of process loops.
• The5531Adisplaycanbepanel-mountedinthesafeareaorExZone2(gas).
• The5531B1Exdisplayincludesthe8501enclosureandcanbemountedin
ExZone2or22(gasordust).
• The5531B2includesthe8501enclosureandcanbemountedinExZone1,
2, 21 or 22 (gas or dust).
Technical characteristics
• Withafullmeasurementrangeof3.6to23mA,the5531isNAMURNE43
compliant.
• Thedisplaycanbepush-buttonscaledtoanyrangebetween-9999to9999,
and reverse display action is possible.
• TheLCDbacklightcanbesettohalforfullintensityforeasyviewinginlow
light conditions.

6 5531V105-UK
• Withthebacklightturnedoff,thedisplayonlyrequires1.5VDC,
(75 Ω loop load).
• TheinputisHART®transparent.
• Thefrontpush-buttonscanbedisabledtopreventunauthorizedadjustment.
Mounting / installation
• Oncepanel-mountedwiththeincludedgasket,the5531providesIP65
ingress protection.

5531V105-UK 7
Technical specifications
Environmental conditions:
Specifications range.................................... -20°C to +60°C
Storage temperature ................................... -20°C to +60°C
Calibration temperature............................... 20...28°C
Relative humidity......................................... <95%RH(non-cond.)
Protection degree, from front...................... IP65
Mechanical specifications:
Dimensions(HxWxD),5531A,5531B.......... 48 x 96 x 120 mm
Cut-outdimensions(HxW) .......................... 44.5 x 91.5 mm
Weightapprox.,5531A,5531B ................... 200 g
Dimensions(HxWxD),5531B1,5531B2 ..... 92 x 112 x 143 mm
Cable glands / cable diameter.................... 2x M16 x 1.5 / Ø 5...8 mm
Dimensions, 8501 backplate....................... 112 x 112 mm
Weightapprox.,5531B1,5531B2 ............... 900 g
Wiresize,connectorterminal1-4 ............. 0.13...2.08 mm2/
AWG26...14strandedwire
Screw terminal torque................................. 0.5 Nm
Common electrical specifications:
Supply ......................................................... Input loop-powered
Signal / noise ratio ...................................... > 60 dB
Response time (0...90%, 100...10%) .......... < 1 s
Updating time.............................................. 500 ms
Input and output specifications:
Input range .................................................. 4...20 mA
Measurement range .................................... 3.6...23 mA
Input voltage drop, without backlight ......... < 1.5 V @ 20 mA
Input voltage drop, with full backlight......... < 10.5 V @ 20 mA
Loop error detection, 4...20 mA:
Low detection (InLo) ............................... ~ < 3 mA
Highdetection(InHi) ............................... ~ > 24 mA
Display readout ........................................... ± 9999 (4 digits)
Digit height .................................................. 16 mm
Accuracy values
Input Absolute
accuracy Temperature
coefficient
4...20 mA ≤±0.1% of span ≤ ±0.01% of span / °C
EMC immunity influence .................................. < ±0.5% of span

8 5531V105-UK
Approvals:
NI:
5531A:
KEMA 05ATEX1044 X.................................. II 3 G Ex ic IIC T6 Gc
(-20°C≤ Ta≤ +60°C)
IECEx DEK 12.0036X .................................. Ex ic IIC T6 Gc
(-20°C≤ Ta≤ +60°C)
5531B1:
KEMA 05ATEX1044 X.................................. II 3 G Ex ic llC T6 Gc
(-20°C≤ Ta≤ +60°C)
II 3 D Ex ic IlIC T85°C Dc
(-5°C ≤Ta≤ +60°C)
IECEx DEK 12.0036X .................................. Ex ic IIC T6 Gc
(-20°C≤ Ta≤ +60°C)
Ex ic IlIC T85°C Dc
(-5°C ≤Ta≤ +60°C)
IS:
5531B:
KEMA 05ATEX1105X................................... II 2 G Ex ia IIC T6 Gb
(-20°C≤ Ta≤ +60°C)
IECEx DEK 12.0036X .................................. Ex ia IIC T6 Gb
(-20°C≤ Ta≤ +60°C)
5531B2:
KEMA 05ATEX1105 X.................................. II 2 G Ex ia IIC T6 Gb
(-20°C≤ Ta≤ +60°C)
II 2 D Ex ia IIIC T85°C Db
(-5°C≤ Ta≤ +60°C)
IECEx DEK 12.0036X .................................. Ex ia IIC T6 Gb
(-20°C≤ Ta≤ +60°C)
Ex ia IIIC T85°C Db
(-5°C≤ Ta≤ +60°C)
Ex data:
Ui.................................................................: 45 VDC
Ii.................................................................: 120 mA
Pi.................................................................:0.9W
Ci.................................................................: 0 nF
Li.................................................................:0mH
PENDING
PENDING
PENDING
PENDING

5531V105-UK 9
Approvals:
EMC 2004/108/EC ...................................... EN 61326-1
GOST R
Ex:
ATEX 94/9/EC, 5531A and 5531B1............. KEMA 05ATEX1044 X
ATEX 94/9/EC, 5531B and 5531B2............. KEMA 05ATEX1105 X
IECEx........................................................... Pending
GOST Ex (5531B)
Special conditions for safe use
For applications in explosive dust atmospheres, the Loop Powered LCD
Indicator shall be installed in such a way that the risk of mechanical danger is
low, and that it shall be protected from exposure to UV light.
Electrostatic charging of the plastic display and the label shall be avoided.
Year of manufacture can be taken from the first two digits of the serial number.

10 5531V105-UK
Field enclosure type 8501
The field enclosure type 8501 complies with industrial standards for efficient
protectionofprocessequipmentinwetareasuptoIP65.When8501is
delivered with a built-in PReview 5531, the assembled unit is approved
for installation in explosive gas atmospheres as well as in explosive dust
environments. The technical specifications of the field enclosure can be found
in the 8501 data sheet.

5531V105-UK 11
Block diagram
2
1
4
3
CPU
E E P R OM
A /D
5531
DP 1
DP 1
1
3
2
Ex
circuit
Only
version:B
Front buttons
Backlight
input+
4...20mA
input -
Ordering codes for 5531
Type Input signal area classification Field enclosure
5531A 4...20 mA from safe and zone 2 No
5531B1 4...20 mA from safe, zone 2 and 22 Yes
5531B 4...20 mA from zone 0 No
5531B2 4...20 mA from zone 0 and 20 Yes
Accessories
Type Specification
8335 Splash proof cover
8501 Field enclosure for 5531A

12 5531V105-UK
Programming
0.0
1.0 1.1 1.2 1.3
Display type no. is shown
To store changes press simultaneously.
DP SW 1 must be ON to enable front buttons.
If no buttons are pressed for a period of 2 minutes,
display returns to stage 0.0
Power on
Routing diagram
DP 1 Front keyboard SW ON SW OFF
Keys locked
Keys NOT locked
-
1
1
-
DP 1 Backlight SW ON SW OFF
Off
Halfintensity
Full intensity
2
3
-
-
2
2, 3

Programmable displays with a wide
selection of inputs and outputs for display of temperature,
volume and weight, etc. Feature linearisation, scaling,
and difference measurement functions for programming
via PReset software.
Displays
A wide selection of transmitters for DIN
form B mounting and DIN rail devices with analogue
and digital bus communication ranging from application-
specic to universal transmitters.
Temperature
Galvanic isolators for analogue and digital
signalsaswellasHART®signals. A wide product range
with both loop-powered and universal isolators featuring
linearisation, inversion, and scaling of output signals.
Isolation
Interfaces for analogue and digital signals
aswellasHART®signals between sensors / I/P converters /
frequency signals and control systems in Ex zone 0, 1 & 2
and for some devices in zone 20, 21 & 22.
Ex interfaces
PC or front programmable devices with
universal options for input, output and supply. This range
offers a number of advanced features such as process
calibration, linearisation and auto-diagnosis.
Universal

Head ofce
Denmark www.prelectronics.com
PR electronics A/S sales@prelectronics.dk
Lerbakken 10 tel. +45 86 37 26 77
DK-8410 Rønde fax +45 86 37 30 85
www.prelectronics.fr
sales@prelectronics.fr
www.prelectronics.de
sales@prelectronics.de
www.prelectronics.es
sales@prelectronics.es
www.prelectronics.it
sales@prelectronics.it
www.prelectronics.se
sales@prelectronics.se
www.prelectronics.co.uk
sales@prelectronics.co.uk
www.prelectronics.com
sales@prelectronics.com
www.prelectronics.cn
sales@prelectronics.cn
Table of contents
Popular Touch Panel manuals by other brands

Zennio
Zennio Z70 v2 user manual

elsner elektronik
elsner elektronik Corlo Touch KNX 5in Technical specifications and installation instructions

AXIOMTEK
AXIOMTEK GOT321A-ELK-WCD user manual

Unipulse
Unipulse DeviceNet F381A Operation manual

Avalue Technology
Avalue Technology Medi-View AID-156 Quick reference guide

ICOP Technology
ICOP Technology PPC-150T-APL Series user manual