Quincy QPNC354 Instructions for use

ENGLISH
Cod. 2200780118 04 - Edition 08/2020 - 1
INSTRUCTION AND MAINTENANCE MANUAL
DRYERS
QPNC354 (E11)- QPNC424 (E12)-
QPNC530 (E13)- QPNC636 (E14)
(R410A)
Code
2200780118
04
Edit. 08/2020
READ THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE
DRYER.

ENGLISH
2 - Edition 08/2020 Cod. 2200780118 04 -
CONTENTS
PART A: INFORMATION FOR THE USER
1.0 GENERAL CHARACTERISTICS
2.0 INTENDED USE
3.0 OPERATION
4.0 GENERAL SAFETY STANDARDS
5.0 DESCRIPTION OF DANGER SIGNALS
6.0 DANGER ZONES
7.0 SAFETY DEVICES
8.0 POSITION OF PLATES
9.0 DRYERS ROOM
10.0 TRANSPORT AND HANDLING
11.0 UNPACKING
12.0 INSTALLATION
13.0 DIMENSIONS AND TECHNICAL DATA
14.0 MACHINE ILLUSTRATION
15.0 SCRAPPING THE DRYERS
PART B: INFORMATION RESERVED FOR TECHNICALLY SKILLED PERSONNEL
16.0 PARTIAL ROUTINE MAINTENANCE
17.0 TROUBLE-SHOOTING AND EMERGENCY REMEDIES
18.0 STARTING UP, FREE CONTACT FEATURES
ATTENTION: THERE IS A COPY OF THE WIRING DIAGRAM INSIDE THE ELECTRIC PANEL
ADDRESSES OF ASSISTANCE CENTRES
In the event of breakdown or malfunction of the dryer, switch it off and do not tamper with it. If repairs are needed, apply
only to a technical assistance centre approved by the manufacturer and insist on the use of original spare parts. Failure
to comply with the above may endanger the safety of the machine.
INTRODUCTION
Keep this manual with care for future consultation; the use and maintenance manual is an integral part on the
dryer. Read this manual carefully before carrying out any operations on the dryer.
The installation of the dryer and all operations involving it must be performed in conformity with the regulations
in force concerning electric plants and personal safety.
CHARACTERISTICS AND SAFETY PRECAUTIONS
BEFORE REMOVING THE PROTECTIVE GUARDS TO CARRY OUT ANY MAINTENANCE ON THE MACHINE, SWITCH OFF THE ELECTRIC
POWER SUPPLY AND DISCHARGE THE RESIDUAL PRESSURE INSIDE THE UNIT.
ALL WORK ON THE ELECTRIC PLANT, HOWEVER SLIGHT, MUST BE CARRIED OUT BY PROFESSIONALLY SKILLED PERSONNEL.
The manufacturer does not accept responsibility for damage caused as a result of negligence of failure to abide by the
instructions given above.
THIS MACHINE IS NOT SUITABLE FOR EXTERNAL INSTALLATION
THIS MACHINE CORRESPOND TO THE ESSENTIAL SAFETY REQUIREMENTS FORESEEN FROM THE
EUROPEAN STANDARD (2006/42 CE).
THE LUBRICATING LIQUIDS AND OTHER EVENTUAL FLUIDS MUST NOT BE DISCHARGED IN THE
ENVIRONMENT. THESE POLLUTING AND HAZARDOUS PRODUCTS MUST COMPULSORY BE DISPOSED BY
CHARGING AUTHORISED AND SPECIALISED FIRMS ACCORDING TO THE DIFFERENT TYPOLOGY OF
PRODUCT.
DIFFERENTIATE THE COMPRESSOR COMPONENTS ACCORDING TO THE DIFFERENT CONSTRUCTION
MATERIALS (PLASTIC, COPPER, IRON, OIL FILTER, AIR FILTER ECC…)

ENGLISH
Cod. 2200780118 04 - Edition 08/2020 - 3
1.0 GENERAL CHARACTERISTICS
The dryer is a chilling machine with direct expansion and dry evaporator.
The air to be dried is sent to the heat exchanger in which the water vapour present is condensed: the condensate
gathers in the separator and is discharged outside through a steam trap.
2.0 INTENDED USE
The dryer has been built to dry the compressed air for industrial use. The dryer cannot be used in premises where there
is a risk of fire or explosion or where work is carried out which releases substances into the environment which are
dangerous with regard to safety (for example: solvents, inflammable vapours, alcohol, etc.).
In particular the appliance cannot be used to produce air to be breathed by humans or used on direct contact with
foodstuffs. These uses are allowed if the compressed air produced is filtered by means of a suitable filtering system
(Consult the manufacturer for these special uses.)
This appliance must be used only for the purpose for which it was specifically designed. All other uses are to be
considered incorrect and therefore unreasonable. The Manufacturer cannot be held responsible for any damage resulting
from improper, incorrect or unreasonable use.
3.0 OPERATION
The gaseous refrigerant coming from the evaporator (4) is sucked by the refrigeration compressor (1) and it is pumped
into the condenser (2). This one allows its condensation, eventually with the help of the fan (3); the condensed refrigerant
passes through the dewatering filter (8) and it expands through the capillary tube (7) and goes back to the evaporator
where it produces the refrigerating effect.Due to the heat exchange with the compressed air which passes through the
evaporator against the stream, the refrigerant evaporates and goes back to the compressor for a new cycle.
The circuit is equipped with a bypass system for the refrigerant; this intervenes to adjust the available refrigerating
capacity to the actual cooling load. This is achieved by injecting hot gas under the control of the valve (9): this valve
keeps constant the pressure of the refrigerant in the evaporator and therefore also the dew point never decreases below
0 °C in order to prevent the condensate from freezing inside the evaporator. The dryer runs completely automatically.
DRYER FLOW DIAGRAM
1) REFRIGERANT COMPRESSOR
9) HOT GAS BYPASS VALVE
2) CONDENSER
10) AIR-TO-AIR EXCANGER
3) MOTOR FAN
11) DIGITAL CONTROLLER
4) EVAPORATOR
12) MAX PRESSURE SWITCH
5) DEMISTER CONDENSATE SEPARATOR
13) FAN CONTROL PRESSURE SWITCH
6) IMPURITY TRAP
14) LIQUID SEPARATOR
7) EXPANSION CAPILLARY TUBE
15) CONDENSATE DRAIN
8) REFRIGERANT FILTER
4.0 GENERAL SAFETY STANDARD
The appliance may be used only by specially trained and authorized personnel.
Any tampering with the machine or alterations not approved beforehand by the Manufacturer relieve the latter of
responsibility for any damage resulting from the above actions.
The removal of or tampering with the safety devices constitutes a violation of the European Standards on safety.
ALL WORK ON THE ELECTRIC PLANT, HOWEVER SLIGHT, MUST BE CARRIED OUT BY PROFESSIONALLY SKILLED PERSONNEL.
5
15 6
14 1
3
7
8
2
4
10
11
9
12 13
AIR OUTLET
AIR INLET
CONDENSATE DRAIN

ENGLISH
4 - Edition 08/2020 Cod. 2200780118 04 -
5.0 DESCRIPTION OF DANGER SIGNALS
1) Dangerous
electricvoltage
2) Air not fit for
breathing
3) High pressure
4) Fan rotating
5) Hot parts
6.0 DANGER ZONES
6.1 DANGER ZONES
(1)
(2)
(3)
(4)
Risks present on the whole machine
7.0 SAFETY DEVICES
7.1 SAFETY DEVICES
1) Cooling fan shield
3) Earth
2) high pressure side switch
FIG. 3
1
3
2
FIG. 2
3
1
1
1
2
4
3
1
1
5

ENGLISH
Cod. 2200780118 04 - Edition 08/2020 - 5
8.0 POSITION OF PLATES
8.1 POSITION OF THE DANGER PLATES (Fig. 4)
The plates fitted on the compressor unit are part of the machine; they have been applied for safety purposes and must
not be removed or spoiled for any reason.
Ref.1 - Spare plate Code 1079 9903 48
8.2 POSITION OF THE DATA PLATES (Fig. 4)
Ref. 2) “IN”
Ref. 4) Identification plate
Ref. 3) “OUT”
9.0 DRYERS ROOM
9.1 FLOOR
The floor must be even and of industrial type; the total weight of the machine is shown in Fig. 5
Remember the total weight of the machine when positioning it.
9.2 VENTILATION
The choice of an appropriate room will prolong the life of your dryer; the room must be spacious, dry, well ventilated and
free from dust.
The operating conditions to be complied with are the following:
Min. room temperature: + 3 °C (+37,4 °F) (compulsory)
Min. inlet allowed temperature: 3°C (+37,4 °F)
Max. room temperature: + 45 °C (+113 °F) (compulsory)
Max. working pressure: 14 bar (203 psi)
Max. temperature of incoming air: 55 °C (+131 °F)
⚫Please keep environmental conditions stable (temperature and humidity) in order to avoid refrigerant compressor/fan
overload and/or reduction of dryer performance. Similar failures shall affect warranty reimbursements.
⚫Please ensure the appropriate composition of the air within the machine room: - clean with no damaging contaminants
(e.g., dust, fibers, fine sand) - free of explosive or chemically unstable gases or vapors - free of acid/alkaline forming
substances, particularly ammonia, chlorine or hydrogen sulfide. Similar failures shall affect warranty reimbursements.
⚫Please remember that we do not recommend the application of duct to extract air in presence of axial fans.
FIG. 4
1
2
3
4
1
1079 9903 48

ENGLISH
6 - Edition 08/2020 Cod. 2200780118 04 -
10.0 TRANSPORT AND HANDLING
The machine must be transported as shown in the following figures.
11.0 UNPACKING
CUTTING THE METAL STRAPPING IS A DANGEROUS OPERATION, DO NOT ABANDON THE CUT PIECES IN THE ENVIRONMENT.
After removing the packing, ensure that the machine is unbroken and that there are no visibly damaged parts.
If you are in doubt, do not use the machine but apply to the manufacturer technical assistance service or to your dealer.
The packing material (plastic bags, polystyrene foam, nails, screws, wood, metal strapping, etc.) must not be left within
the reach of children or abandoned in the environment, as they are a potential source of danger and pollution.Dispose of
these materials in the approved collection centres.
FIG. 5
MODD.
NET
WEIGHT
Kg. (lb)
354
145 (320)
424
158 (348)
530
165 (368)
636
164 (362)

ENGLISH
Cod. 2200780118 04 - Edition 08/2020 - 7
12.0 INSTALLATION
12.1 POSITIONING
After unpacking the equipment and preparing the dryers room, put the machine into position, checking the following
items:
⚫ensure that there is sufficient space around the machine to allow maintenance (see Fig. 6).
ENSURE THAT THE OPERATOR CAN SEE THE WHOLE MACHINE FROM THE CONTROL PANEL AND CHECK THE PRESENCE OF ANY
UNAUTHORIZED PERSONS IN THE VICINITY OF THE MACHINE.
12.2 ELECTRICAL CONNECTION
⚫Check that the supply voltage is the same as the value indicated on the machine data plate.
⚫Check the condition of the line leads and ensure that there is an efficient earth lead.
⚫Ensure that there is an automatic cut-out device upstream for the machine against overcurrents, with a
differential device ( Ref. 1 Fig. 6 ), wiring diagram.
ONLY PROFESSIONALLY SKILLED PERSONNEL MAY HAVE ACCESS TO THE ELECTRIC PANEL. SWITCH OFF THE POWER BEFORE
OPENING THE DOOR OF THE ELECTRIC PANEL. COMPLIANCE WITH THE REGULATIONS IN FORCE CONCERNING ELECTRIC PLANTS
IS FUNDAMENTAL FOR OPERATOR SAFETY AND FOR THE PROTECTION OF THE MACHINE.
12.3 CONNECTION TO THE COMPRESSED AIR NETWORK
Fit a manual interception valve Ref. 1 between the machine and the compressed air network so that the dryer may be
isolated during maintenance operations (see figure 7 ).
Drainage of condensate Rif. 2 Fig. 7 (automatic) are led outside the machine with a flexible pipe that may be inspected.
Drainage must comply with the local regulations in force.
⚫All refrigerant dryers shall be equipped with proper pre-filter at closest position to dryer air inlet (to be replaced
according to service plan: once per year or even before in case of particular high humidity ambient conditions).
ALL DAMAGE DUE TO THE FAILURE TO COMPLY WITH THESE NDICATIONS CANNOT BE ATTRIBUTED TO THE MANUFACTURER AND
MAY CAUSE INVALIDITY OF THE GUARANTEE CONDITIONS.
12.4 STARTING UP
See part B of this manual, Chapter 16.0
FIG. 6
ATTENTION:
THE DIFFERENTIAL AUTOMATIC SWITCH AGAINST
CURRENT OVERLOAD REF. 1 IS NOT CURRENT
SUPPLIED WITH THE MACHINE.
1
Minimum mt. 1,5 (59 in)
PROTECT THE POWER CABLE WITH A SUITABLE
CHANNEL.
FIG. 7
1
2

ENGLISH
8 - Edition 08/2020 Cod. 2200780118 04 -
13.0 DIMENSIONS AND TECHNICAL DATA
MODD.
WEIGHT
Kg. (lb.)
Freon
R410A Kg.
Kg. (lb.)
Bar (psi)
MAX.
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
354
145 (320)
1,5
1,5 (3,31)
1389
2090 (2,8)
151
210 (0,281)
14 (203)
424
158 (348)
1,5
1,5 (3,31)
1429
2440 (3,27)
551
780 (1,045)
14 (203)
530
165 (368)
1,85
1,85 (4,08)
1459
2440 (3,27)
551
780 (1,045)
14 (203)
636
164 (362)
1,95
1,95 (4,3)
1870
3100 (4,16)
900
1100 (1,48)
14 (203)
Reference conditions:
Limit conditions:
50 Hz
60 Hz
50 Hz
60 Hz
Ambient temperature
25 °C
38 °C (+100°F)
Max. ambient temperature
45 °C
45 °C (113°F)
Inlet air temperature
35 °C
38 °C (+100°F)
Min. ambient temperature
3 °C
3 °C (37,4°F)
Working pressure
7 bar
7 bar (101,5 psi)
Max. inlet air temperature
55 °C
55 °C (131°F)
Max. working pressure
14 bar
14 bar (203 psi)
14.0 MACHINE ILLUSTRATION
14.1 GENERAL LAY-OUT
1
Refrigerant compressor
7
Freon filter
2
Condenser
8
Capillary
3
Motor fan
9
Pressure switch of motor fan
4
Evaporator
10
Pressure switch of the high pressure
5
Condensate drain
11
Liquid separator
6
Hot gas by pass valve
TYPE
A
B
354
2 ”F.
2” F.
424
2”1/2 F.
2”1/2 F.
530
2”1/2 F.
2”1/2 F.
636
2”1/2 F.
2”1/2 F.
(A) AIR INLET
(B) AIR OUTLET
ELECTRICAL CABLE
CONDENSATE
DRAINING
TYPE
L
(mm / in)
W
(mm / in)
H
(mm / in)
354
805 (31.7)
1040 (41)
962 (37,87)
424
805 (31.7)
1040 (41)
962 (37,87)
530
805 (31.7)
1040 (41)
962 (37,87)
636
805 (31.7)
1040 (41)
962 (37,87)
L
W
H
Nominal
Power
W (HP)
Nominal
Power
W (HP)
)
Refrigerant gas (1)
GWP 100 (2)
R-410A
2088
(1) According to ISO 817
(2) According to EN-378-1
3
FIG. 8
2
9
4
7
10
1
5
8
6
11

ENGLISH
Cod. 2200780118 04 - Edition 08/2020 - 9
14.2 DIGITAL CONTROLLER
Identification
Front panel of the controller
Reference
Name
1
Alarm icon
2
Refrigerant compressor icon
3
Fan icon
4
Alarm LED
5
Button to snooze or to reset the alarm
6
SET button
7
UP button
8
DOWN buttom
6+7
Back to previous screen
6+8
Menu
Icons
Icon
Name
Mode
Function
Alarm
Off
No active alarms
On
Probe failure alarm
High temperature or low
temperature alarm
Service alarm
Refrigerant
compressor
On
Dryer on
Flashing + SE
Maintenance warning
Flashing + L2
Dewpoint too low
Dryer is stopped
Flashing + H3
Too high discharge
temperature of the
refrigerant compressor
(see further)
Dryer is stopped
jhjdd
Fan
Off
Fan off
Flashing
Not applicable
On
Fan on
15.0 SCRAPPING THE UNIT
If the machine is to be scrapped, it must be dismantled into parts of the same material, to be disposed of according to the
local regulations in force.
ALWAYS RESPECT THE REGULATIONS IN FORCE FOR DISPOSING OF OLD OIL AND OTHER POLLUTING MATERIALS SUCH AS
INSULATING FOAM, ETC.
1
2
1
3
5
4
6
7
8

ENGLISH
10 - Edition 08/2020 Cod. 2200780118 04 -
PART “B”
THIS PART “B” OF THE INSTRUCTIONS MANUAL IS RESERVED FOR
PROFESSIONALLY SKILLED PERSONNEL APPROVED THE MANUFACTURER.
16.0 PARTIAL ROUTINE MAINTENANCE
BEFORE CARRYING OUT ANY MAINTENANCE JOBS IT IS OBLIGATORY TO STOP THE MACHINE AND DISCONNECT IT FROM THE
POWER MAINS AND FROM THE COMPRESSED AIR DISTRIBUTION NETWORK.
16.1 MAINTENANCE SCHEDULE
These maintenance intervals are recommended for work environments that are not dusty and are will ventilated. For
particularly dusty environments, double the frequency of controls.
Every week
◼◼
Brush/blow off the finned surface of the condenser
◼◼
Clean the filter of the automatic condensate drain
Every 2000 hours / 1 year
◼◼
Replace the filter of automatic condensate drain (2902016102)
Every 4000 hours / 2 year
◼◼
Replace drain kit (2200902017)
16.2 CLEANING OF THE AUTOMATIC CONDENSWATER DISCARGER FILTER (Fig. 10)
Clean the filter of the steam trap.
Proceed as follows:
- Close the cock Ref. 1 Fig. 10
- Release the pressure in the dryer by pressing the condensate drain “TEST” pushbutton locate on the steam trap
Ref. 2 Fig. 10.
- Switch off the machine. Turn the switch in position STOP Ref. 3 Fig. 10
- Turn on the supply automatic differential switch Ref. 4 Fig. 10
HOT PARTS INSIDE
- To use the hole Ref. 5
- Remove the stopper Ref. 6
- Remove the filter Ref. 7
- Clean the filter Ref. 5 with a jet of air, working from inside to outside
- Install the filter, fix the plug Ref. 7 - 6
- Close the panels Ref. 5
1
5
FIG. 10
2
3
4
6
7

ENGLISH
Cod. 2200780118 04 - Edition 08/2020 - 11
16.3 CLEANING THE CONDENSER (Fig. 10)
The condenser must be cleaned every month.
Proceed as follows:
- Switch off the machine. Turn the switch in position STOP Ref. 3 Fig. 10
- Turn on the supply automatic differential switch Ref. 4 Fig. 10
- To use the hole Ref. 5 Fig. 10
- Clean the condenser fins Ref. 1 with compressed air (Fig. 10) DO NOT USE WATER OR SOLVENTS
- Close the panels Ref. 5 Fig. 10
17.0 TROUBLE-SHOOTING AND EMERGENCY REMEDIES
ALL WORK MUST BE CARRIED OUT BY PROFESSIONALLY SKILLED PERSONNEL. BEFORE CARRYING OUT ANY MAINTENANCE
JOBS IT IS OBLIGATORY TO STOP THE MACHINE AND DISCONNECT IT FROM THE POWER MAINS.
N.B. OPERATIONS MARKED ◼◼MUST BE CARRIED OUT BY PROFESSIONALLY SKILLED PERSONNEL APPROVED THE
MANUFACTURER
FAULT FOUND
POSSIBLE CAUSES
OBSERVATIONS
1) No compressed air passes through the dryer
outlet
1A) The pipes are frozen inside
◼◼ -The bypass valve of the hot gas is broken or
out-of-calibration
-The room temperature is too low and the
evaporators piping are obstructed with ice
2) Presence of condensate in the pipings.
2A) The condensate separator does not work
correctly
2B) The dryer is working outside its rating
2C) The dryer is working under bad conditions of
condensation
-Clean the filter from the condensate drain
◼◼-Check the condensate drain
-Check the flow rate of treated air
-Check the room temperature
-Check the air temperature at the drier inlet.
-Clean the condenser.
◼◼-Check the operation and the calibration of the
press. switch
◼◼-Check the good operation of the fan.
3) The compressor head is very hot
(> 55 °C)
Make reference to 2B
Make reference to 2C
3A) The cooling circuit is not working with the right
gas charge
◼◼ -Check if there are leaks of refrigerating gas.
◼◼ - Charge it again.
4) Motor cuts out on overload
Make reference to 2B
Make reference to 2C
Make reference to 3A
5) The motor hums and does not start.
Sequency relays switched on
The line voltage is too low.
You switched the machine off and on again
without leaving enough time for the pressure
balancing.
The starting system of the motor is defective.
- Exchange two phases of main supply
-Contact the electric power company
-Wait a few minutes before starting the machine
again.
◼◼ -Check the running and starting relays and
condensers (if any)
6) The machine has stopped and does not restart
even after a few minutes.
The termostatic protection with manual reset
has intervened: make reference to 2B-2C-3A.
The motor has burnt out.
7) The compressor is very noisy.
Troubles with the internal mechanical parts or
with the valves

ENGLISH
12 - Edition 08/2020 Cod. 2200780118 04 -
17.1 REMOTE ALARM FUNCTION
The controller allows to remotely visualize a number of alarms. This is managed by two potential free contact NC
(Normally Closed).The contacts opens in case of an alarm.
- CD contact : it’s in series to all the alarms from the controller ( see the section “fault messages”), to the fan motor
breaker Q2, to the phase sequency relay KPH and to the safety pressure switch AP. The contact opens when one of the
fault happens.
-EF contact : it’s in series to the alarms coming from the drain. The contact opens when one of the fault happens.
Free contact location
FAULT MESSAGES
Flashing fault message
Description
Remedy
Dewpoint temperature probe
failure
Replace the probe
Refrigerant compressor
discharge temperature probe
failure
Replace the probe
Pressure dewpoint too high
Refer to the fault and remedies
section
DRAIN
DIXELL+
KPH+
Q2+
AP

ENGLISH
Cod. 2200780118 04 - Edition 08/2020 - 13
Flashing fault message
Description
Remedy
Pressure dewpoint too low.
Refrigerant compressor shut
down
Refer to the fault and remedies
section
Refrigerant compressor
discharge temperature too high;
refrigerant compressor stopped.
Refer to the fault and remedies
section
Internal EPROM error
(not remotable)
Reset by pressing one of the four
buttons.
If the problem persists, replace
the controller
Maintenance required
(not remotable)
Perform the maintenance and
reset the alarm
RESETTING THE MAINTENANCE WARNING
Front panel of the controller
To reset the maintenance warning, follow steps 1 to 12:
1. The display is flashing between standard view (dewpoint) and maintenance required (SE) alarm.
2. Push and hold buttons SET (6) and DOWN (8) to enter the menu.
3. Message “SE” appears on display.
4. Push and release the UP button (7).
5. Message “rS” appears on display.
6. Push and release the SET button (6).
7. Message “n” appears on display.
7
8
5
6

ENGLISH
14 - Edition 08/2020 Cod. 2200780118 04 -
8. Push and release the UP button (7).
9. Message “y” appears on display.
10. Push and release SET (6) to reset service alarm.
11. Message “y” blinks for 3 seconds.
12. Then “rL” is fixed and “°C” blinks on display for about 10 seconds.
The service alarm is now reset.
SETTING THE SERVICE INTERVAL
To set the service interval, follow steps 1 to 9:
1. PDP is showing standard view.
2. Push and hold buttons SET (6) and DOWN (8) to enter the menu.
3. Message “SE” appears on display.
4. Push and release SET (6) to enter the “SE” menu.
5. Current service interval is displayed.
(“60” or any other value between “0” and “99”)
6. Select desired service interval using the UP and DOWN button.
(40=4000h, 55=5500h, 80=8000h,…)
7. Push and release SET to confirm the new service interval.
8. The selected value blinks during 3 seconds.

ENGLISH
Cod. 2200780118 04 - Edition 08/2020 - 15
9. Then “rS” is fixed and “°C” blinks on display for about 10 seconds.
The new service interval is now set.
FREEZE PROTECTION FUNCTION
Once the digital controller detects a dewpoint temperature below -2°C / 28,4°F during more than 2
minutes, (L2 Alarms), it switches off the refrigerant compressor.
AUTOMATIC CUT OUT OF REFRIGERANT COMPRESSOR
If the refrigerant temperature detected at the delivery pipe of refrigerant compressor overcome the
limit setted by manufacturer, the controller stops the refrigerant compressor in order to avoid further
possible failure.
RESETTING THE DRYER AFTER A REFRIGERANT COMPRESSOR STOP
Press button 7 to reset the alarm.
The dryer restarts when both the following conditions are true.
•The dewpoint temperature is higher than -2°C / 28,4°F
•30 second are passed from the refrigerant compressor stop (minimum balancing pressure
stop time).
A countdown is available if the reset is made before the minimum stop time.
SILENT ALARM FUNCTION
To snooze the alarm, press button 5.
REFRIGERANT COMPRESSOR DISCHARGE TEMPERATURE VISUALIZATION FUNCTION
To see the discharge refrigerant compressor temperature, follow steps 1 to 5:
1. PDP is showing standard view.
2. Push and hold buttons SET (6) and DOWN (8) to enter the menu.
3. Push and release the UP button (7) until message “S3” appears on display.
4. Push and release the SET button (7) to enter the “S3” parameter.
5. Current temperature of discharge refrigerant compressor is displayed.

ENGLISH
16 - Edition 08/2020 Cod. 2200780118 04 -
17.2 REMOTE START/STOP FUNCTION
Remove the bridge between A and B and wire a potential free contact in between.
The machine will be remotely controlled by the potential free contact, when the main switch is ON.
Tag clearly that the machine is remotely controlled !
1. check carefully the electrical diagram before to proceed with any electrical action
2. The potential free contact MUST be tight. A false contact can damage the electrical
components
3. Switch off the machine (main switch OFF ) before opening the cubicle door
4. Every damage coming from an incorrect or missing application of the following prescriptions,
cannot be addressed to the manufacturer and can affect the warranty of the products
18.0 STARTING UP
BEFORE CARRYING OUT ANYOPERATION ON THE MACHINE, ENSURE THAT THE ELECTRIC POWER SUPPLY HAS
BEEN DISCONNECTED
WAIT AT LEAST TWO HOURS BEFORE STARTING UP, AFTER ANY MACHINE MOVEMENT (TRANSPORT OR
HANDLING).
18.1 PRELIMINARY CONTROLS
Before starting the dryer, check:
- The correct connection to the compressed air piping: remember to remove eventual caps on the drier inlet and outlet.
- The correct connection to the condensate drainage system.
- That the power supply is right.
18.2 STARTING AND STOP
Start the system before the air compressor starts running and stop it after the air compressor has been stopped. The
compressed air piping will be free of condensate only by doing so. The drier must be kept running during all the time the
air compressor is running.
WARNING: if the drier is switched off, before starting it again, wait at least 5 minutes in order to allow the pressure
balancing.
BEFORE CARRYING OUT ANY MAINTENANCE JOBS IT IS OBLIGATORY TO STOP THE MACHINE AND DISCONNECT IT FROM THE
POWER MAINS AND FROM THE COMPRESSED AIR DISTRIBUTION NETWORK.
1

ENGLISH
Cod. 2200780118 04 - Edition 08/2020 - 17
PRESSURE DISCHARGE PROCEDURE
Proceed as follows:
- Close the taps Ref. 1 Fig. 11
-Release the pressure in the dryer by pressing the condensate drain “TEST” pushbutton locate on the steam trap
Ref. 1 Fig. 11
- Switch off the machine. Turn the switch in position STOP Ref. 3 Fig. 11
- Turn on the supply automatic differential switch Ref. 4 Fig. 11
CALIBRATIONS
BYPASS VALVE FOR HOT GAS
N.B.These valves have already been calibrated and they do not require any adjistment. A dew point different from the
rated one generally depends on causes which are not attributable to their operation.
Ref. 1) Closing cap
Ref. 2) Adjusting screw
WORKING PRESSURES AND TEMPERATURES OF R410A
SUCTION SIDE OF
REFRIGERATION COMPRESSOR
Evaporat.
Temperat.
°C (°F)
Evaporating
Pressure bar (psi)
RATED VALUES
AT AMBIENT
(Temperat.
20°C –68°F)
0 ÷ 1
32 ÷ 33,8
R410A
7,0 ÷ 7,2
101,5 ÷ 104,4
2
1
FIG. 11
3
4
1
2
This manual suits for next models
3
Table of contents
Popular Dryer manuals by other brands

Louis
Louis 10028729 Instructions for installation and use

Maytag
Maytag MLE24PRAZW0 installation instructions

Kenmore
Kenmore 110C79592800 User instructions

Siemens
Siemens WT34A090GB Installation and operating instructions

Ariston
Ariston ASL 65 VXS NA Use and installation manual

Maytag
Maytag MDG17CSAWW - 7.4 cu. Ft. Commercial Gas... installation instructions