RAB Lightcloud LCGATEWAY User manual

EZPAN EDGELIT PANEL 2X2
INSTALLATION INSTRUCTIONS
Thank you for buying RAB lighting xtures. Our goal is to design the best quality products to get the job done right. We’d like to hear your comments.
Call the Marketing Department at 888-RAB-1000 or email: marketing@rabweb.com
TM
Access Plate
Conduit Knockouts
SAFETY INSTRUCTIONS
WARNING: Risk of re or electric shock. Suitable for Damp locations.
WARNING: Suitable for 9/16” or 15/16” Flat Tee Grid in both Insulated Ceilings and Non-Insulated Ceilings. Access above
ceiling required.
WARNING: Do not handle energized xture when hands are wet, when standing on wet or damp surfaces, or in water.
WARNING: Vapor barrier must be suitable for 90° C.
WARNING: Fixture to be independently supported to building structure.
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB xtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding
is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A
PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
Make certain power is OFF before installing or maintaining xture.
Fixture
Grid Clip (4)
Tee-Grid
Bar
Access Plate Screw
Splice Box
2
Grid Clip
Hole
Grid
Clip
Power
Feed
Fixture Firmly bend Grid
Clips up and out
RECESSED CEILING MOUNTING
The xture is suitable only for INDOOR RECESSED CEILING
application. Above ceiling access required.
To mount in an insulated or non-insulated ceiling - 9/16”or
15/16” exposed Flat Tee Grid Ceiling follow the steps below.
1. Firmly bend the pre-installed Grid Clips (4) up and out
as shown in Fig. 1.
2. Rotate and slide the Fixture as required to t through
the Tee-Grid Bar and place it as indicated by the
directional arrow as shown in Fig. 2. Secure the Fixture
to the Tee-Grid Bar.
3. Support wires are required by Installation Codes.
Support the Fixture to the building structure by
Support Wires (supplied by others) through the Grid
Clip Hole as shown in Fig. 3.
4. Make sure that the orientation of the Splice Box and
Access Plate faces an accessible tile to make electrical
splices.
5. Loosen Access Plate Screw and remove the Access
Plate. Knock out appropriate Conduit Knockouts
on the Access Plate to route input conduit. Use
appropriate conduit connectors as required by code
(Fig. 4.).
6. Connect wires as shown in wiring diagram. Push all
wires back into the Splice Box. Use appropriate UL
approved wire connectors as required by code to
complete wiring. Terminal Block accepts input power
wires of 16-18 AWG. If electrical supply wire is greater
than 16 AWG the installer must connect using a
16 AWG Pigtail (supplied). Be careful not to pinch wires.
WARNING: To prevent wiring damage or abrasion, do
not expose wiring to edges of sheet metal or other
sharp objects.
7. Replace Access Plate and tighten Access Plate Screw.
Support Wire
(supplied by
others)
Fig. 2
Fig. 1
Fig. 3
Fig. 4

EZPAN EDGELIT PANEL 2X2
INSTALLATION INSTRUCTIONS
Thank you for buying RAB lighting xtures. Our goal is to design the best quality products to get the job done right. We’d like to hear your comments.
Call the Marketing Department at 888-RAB-1000 or email: marketing@rabweb.com
TM
CLEANING & MAINTENANCE
CAUTION: Be sure xture temperature is cool enough to
touch. Do not clean or maintain while xture is energized.
1. Clean acrylic lens & xture with non-abrasive cleaning
solution.
2. Do not open xture to clean the LEDs. Do not touch the
LEDs.
TROUBLESHOOTING
1. Check that the line voltage at xture is correct. Refer to
wiring directions.
2. Is the xture grounded properly?
010V DIMMABLE WIRING
Universal voltage driver permits operation at 100V thru
277V, 50 or 60 Hz. 0-10V control wires must be rated for
300V minimum. Terminal block accepts input power wires
of 16-18 AWG.
1. Connect LINE supply lead to (L) marked on Terminal Block.
2. Connect COMMON supply lead to (N) marked on Terminal
Block.
3. Connect the GROUND wire to pre-installed Push-in
Connector.
4. Connect DIM+ lead to (DIM+) marked on Terminal Block.
5. Connect DIM- lead to (DIM-) marked on Terminal Block.
Easy Installation & Product Help
Tech Help Line
Call our experts 888 RAB-1000
©2016 RAB LIGHTING Inc.
No
rthvale, New Jersey 07647 USA
rabweb.com
Visit our website for product info
email
Answered promptly sales@rabweb.com
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation
or maintenance.
EZPAN EDGELIT PANEL 2X2 0616
For 12-14 AWG wire, insert supplied 16 AWG Pigtail wires into
Terminal Block.
1. Connect LINE supply lead to Black Pigtail with wire nut
supplied.
2. Connect COMMON supply lead to white Pigtail with wire
nut supplied.
3. Connect the GROUND wire to Green Pigtail with wire nut
supplied.
4. Connect DIM+ lead to (DIM+) marked on Terminal Block.
5. Connect DIM- lead to (DIM-) marked on Terminal Block.

Welcome
LCSENSE15/D10
Ceiling Sensor
© RAB Lighting, Inc
170 Ludlow Avenue Northvale, NJ 07647
Custom manufactured in China
1 (844) LIGHTCLOUD
1 (844) 544-4825
Lightcloud is a commercial
wireless lighting control system
& service. It’s powerful and
flexible, yet easy to use
and install. Learn more at
lightcloud.com
1 (844) LIGHTCLOUD
1 (844) 544-4825
WE ’RE HERE TO HELP:

Lightcloud is a wireless
lighting control service.
The Lightcloud Ceiling
Sensor is a remotely
configurable passive infrared
motion sensor that can
switch and dim both hard-
wired circuits and remote
circuits using Lightcloud
Controllers.
Hello
Product Features
Advanced PIR Sensing
Secure Cloud Control & Configuration
Retrofit-Friendly Local Control
Scheduling & Astronomical Clock
Power Monitoring
0-10V Dimming
Patent Pending

Contents
PART NUMBER
LCSENSE15/D10
INPUT
120-277VAC, 50/60Hz,
<1W (Standby) - 2W (Active)
MAXIMUM SWITCHED LOAD RATINGS
Electronic Ballast: 277VAC, 3300W
Magnetic Ballast: 277VAC, 1200W / 120VAC, 800W
Tungsten: 220VAC, 3000W
Dimming: 0-10V (Class2)
OPERATING TEMPERATURE
-20ºC to 40ºC
Specifications
OPERATING HUMIDITY
10% RH to 95% RH
Non-Condensing
OVERALL DIMENSIONS
4.91” Diameter, 1.61” Height
WIRELESS RANGE
Line-of-Sight: 1000 feet
Obstructions: 100 feet
Warranty is active as long as service plan is active.
Indoor Damp Location
Lightcloud Ceiling Sensor Instruction Manual
Wire Nuts
x 4
x 2
What You Need
Lightcloud Gateway
A Lightcloud installation requires
at least one Lightcloud Gateway to
manage your devices.
1 (844) LIGHTCLOUD
or 1 (844) 544-4825
WE’RE HERE TO HELP:

Wiring SWITCHED NEUTRAL
The “Switched Neutral” white with red stripe wire is the
neutral line for the load being switched. This enables power
measurement. See the Power Measurement section under
“Functionality” for more information.
BLACK
WHITE/RED
0-10V
DIMMING
Panel
Load
BLACK / HOT
WHITE / NEUTRAL
WHITE
BLACK
RED
WHITE
PURPLE
GRAY
PURPLE
GRAY
Setup & Installation
1Find a suitable location
Use these guidelines when installing devices:
• If there is a clear line of sight between two Lightcloud devices,
they can be placed up to 1000 feet apart.
• If the two devices are separated by ordinary drywall construction,
try to keep them within 100 feet of each other.
• Brick, concrete and steel construction may require additional
Lightcloud devices to go around the obstruction.
!This product should only be installed by a qualified electrician
and in compliance with local and national electrical codes.
Lightcloud Gateway
<= 100 ft.
Add an additional Lightcloud
Device to extend network range
around corners B R IC K ,
CONC R E TE O R
M E TA L W AL L
D RY W AL L
OR SI MIL AR

Setup & Installation(cont’d)
DE VIC E ID s
3Labeling your device
For setup and maintenance, we provide two Lightcloud Device Tables with
the Gateway: one that you can attach to your panel and one to hand o to
a building manager. Attach the Device Identification stickers included with
each device to a row, then write in additional information, such as Zone
name, Panel/Circuit Number, and whether or not a zone uses dimming.
ZO NE NAM E PAN EL /
CI RCUIT #
INSTALL AT A JUNCTION BOX INDOOR/OUTDOOR
The Ceiling Sensor can control other Lightcloud devices, wirelessly.
If you don’t need to hard-wire a switched circuit to the Sensor,
no problem—just tie the white/red wire to neutral and cap o any
unused wires.
2Install your Lightcloud Ceiling Sensor
Sensor attached
attached to wired
junction box

Setup & Installation(cont’d)
4
5
Power up
Confirm device connectivity
Confirm Status Indicator is solid green. If it is not, make sure your
device is within range of another Lightcloud AC-powered device.
To add new devices to your Lightcloud network, call RAB at
STATUS
INDICATOR

Setup & Installation(cont’d)
6Place cover
Secure cover onto sensor by pushing up and twisting to the right (clockwise).
7Commission & Configure Your Devices
All Lightcloud products can be commissioned and configured by:
• Logging on to lightcloud.com
• Calling RAB at 1 (844) LIGHTCLOUD

Functionality
Overview
STATUS INDICATOR
POWER
INDICATOR
DEVICE
BUTTON
MOTION
INDICATOR
LIGHT
SENSOR
SENSOR
SIGNAL
INDICATOR
STATUS INDICATOR:
• Solid GREEN when connected to your Lightcloud network
• Blinking RED when not connected to a Lightcloud network. The device will
automatically continue trying to connect to a network that is in Setup Mode.
POWER INDICATOR:
Illuminated when powered. Blinking when indicated from the Lightcloud application.
SIGNAL INDICATOR:
After the Device Button has been pressed, this indicator illuminates when the
device receives a message and indicates the strength of the signal.
3 - Best Signal
2 - Acceptable Signal
1 - Unacceptable Signal
Consult the “Finding a Location” section for more information.
DEVICE BUTTON:
• Press once to highlight this device in the Lightcloud Application
(pressing once also enables display of the Signal Indicators)
• Press twice to toggle circuit on and o
• Press twice and hold to set dim level
• Press and hold for 10 seconds to remove this device from a Lightcloud network
MOTION INDICATOR:
Illuminates when motion is detected
SENSOR:
Passive-infrared motion sensor

OCCUPANCY & VACANCY SENSING:
The Lightcloud Ceiling Sensor can operate in either Occupancy or Vacancy Sensor
modes, selectable via the Lightcloud application. In Occupancy mode, the attached
circuit will be switched on when motion is detected, and o (or dimmed) when the
timeout expires. In Vacancy mode, the attached circuit will be turned o when the
motion timeout expires, but will only be turned on via the Lightcloud application,
Lightcloud Wall Switch, or similar. Motion detection and timeout can still be used
via Lightcloud Automations to control other devices.
CONTROLLER MODE:
In Controller Mode, the attached circuit is controllable as an independent zone
in the Lightcloud application. Motion detection and timeout can still be used via
Lightcloud Automations to control other devices.
RANGE TEST MODE:
When Range Test Mode is activated via the Lightcloud application, the timeout
period is shortened so that you can test dierent sensitivities quickly. All indicators
will go o except for the Motion Indicator. When satisfied, turn o Range Test
Mode to continue normal operation.
Functionality(cont’d)
Features
SIDE
VIEW
TOP
VIEW
15’ 7.5’ 7.5’ 15’
30’
9’
0’
0’
7.5’
7.5’
15’
15’
PASSIVE INFRARED MOTION DETECTION

POWER LOSS DETECTION:
If power to the Ceiling Sensor is lost, the device will detect this and alert the
Lightcloud application.
EMERGENCY DEFAULT:
If communication is lost, the Ceiling Sensor may optionally fall back to a specific
state, such as turning the attached circuit on. This may be configured via the
Lightcloud application or by calling RAB.
Functionality(cont’d)
Features
010V DIMMING:
0-10V is a common method of low-voltage control of dimmable drivers and ballasts.
Purple: 0-10V positive | Gray: 0-10V common
Note: The National Electrical Code requires that low-voltage wiring used in the same
enclosure as high voltage wiring have an equal or better insulation rating. You may need
to complete your low-voltage wiring in another enclosure or use a partition.
DEVICE IDENTIFICATION:
For help with installation, there are two ways to identify this device:
• Pressing the Device Button on the actual product will produce a message in
the Lightcloud application indicating which device you are working with.
• Pressing the “Indicate” button in the Lightcloud application will cause the
device’s Status Indicator to blink green. This will also switch the device’s relay
on and o repeatedly, allowing you to quickly identify which circuit it is.
POWER MEASUREMENT:
The Lightcloud Ceiling Sensor is capable of measuring the power usage of the
attached circuit. In order to utilize this function, the neutral wire of the load
must be connected to the white-red switched neutral wire. If this wire is not
used, it should be tied to the regular neutral wire (i.e. all neutral wires joined).
FCC Information:
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
Note: This device has been tested and found to comply with the limits for Class B digital devices pursuant to Part 15 Subpart B, of
the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential environment.
This equipment generates, uses, and can radiate radio frequency energy, and if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in
a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by
turning the equipment o and on, the user is encouraged to try and correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit dierent from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
To comply with the FCC's RF exposure limits for general population / uncontrolled exposure, this transmitter must be installed to
provide a separation distance of at least 20 cm from all persons and must not be co-located or operating in conjunction with any other
antenna or transmitter.
CAUTION: Changes or modifications to this equipment not expressly approved by RAB Lighting may void the user’s authority to
operate this equipment.

© RAB Lighting, Inc
170 Ludlow Avenue Northvale, NJ 07647
Custom manufactured in China
1 (844) LIGHTCLOUD
1 (844) 544-4825
Lightcloud is a commercial
wireless lighting control system
& service. It’s powerful and
flexible, yet easy to use
and install. Learn more at
lightcloud.com

Welcome
LCCONTROL20/D10
Controller
1 (844) LIGHTCLOUD
1 (844) 544-4825
WE’RE HERE TO HELP:



Contents
Specifications
PART NUMBER
LCCONTROL20/D10
INPUT
120-277VAC, 50/60Hz
<2W (Standby - 4W (Active)
MAXIMUM SWITCHED LOAD RATINGS
For Control of Magnetic, Electronic Ballast or LED
277VAC: 20A Magnetic/Resistive
240VAC: 5A Tungsten/Electronic, 20A FLA/
60 LRA, 2HP
120VAC: 15A Tungsten, 1HP
OPERATING TEMPERATURE
-40ºC to +40ºC
OVERALL DIMENSIONS
1.55" diameter, 5.75" length
1/2" NPT Mount, Male
16AWG pigtails
WIRELESS RANGE
Warranty is active as long as service plan is active
Class 2
IP66 Rated
Indoor and Outdoor Rated
Wet and Damp Location
Plenum Rated
Lightcloud Controller
Instruction Manual
Wire Nuts
NPT Nut O-ring
x 4 x 2
Line-of-Sight: 1000 feet
Obstructions: 100 feet

What You Need
Lightcloud Gateway
A Lightcloud installation requires
at least one Lightcloud Gateway
to manage your devices.
1 (844) LIGHTCLOUD
or 1 (844) 544-4825
WE’RE HERE TO HELP:

Wiring
SWITCHED NEUTRAL
The “Switched Neutral” white with
red stripe wire is the neutral line
for the load being switched.
This enables power measurement.
See the Power Measurement
section under “Functionality” for
more information.
BLACK
WHITE/RED
0-10V DIMMING
Panel
Controller
Lightcloud
™
Load
BLACK / HOT
WHITE / NEUTRAL
WHITE
BLACK
RED
WHITE
PURPLE
GRAY
PURPLE
GRAY

Setup & Installation
1
OFF
WARNING
OFF
Turn o power
Find a Suitable Location
1a
Use these guidelines when installing devices:
• If there is a clear line of sight between two Lightcloud
devices, they can be placed up to 1000 feet apart.
• If the two devices are separated by ordinary drywall
construction, try to keep them within 100 ft. of each other.
• Brick, concrete and steel construction may require
additional Lightcloud devices to go around the obstruction.
Lightcloud Gateway
<= 100 ft.
Add an additional Lightcloud
Device to extend network range
around corners B RI CK ,
CONC RE T E O R
M E TA L WA LL
DRY WA LL
OR SIMIL AR
Table of contents
Other RAB Gateway manuals
Popular Gateway manuals by other brands

Milesight
Milesight UG65 user guide

CyberData
CyberData VoIP Multicast Gateway Specification sheet

Panduit
Panduit Synapsense WSN installation manual

Planet Networking & Communication
Planet Networking & Communication LCG-300 Series user manual

SkyLink
SkyLink HU-318 user guide

HUBBELL LIGHTING
HUBBELL LIGHTING wiSCAPE GATEWAY installation instructions