RAMVAC Badger LF User manual

Badger LF
User Manual
LF

1
www.DentalEZ.com 866-DTE-INFO (opt 4)
1
www.DentalEZ.com
Table of Contents
Section I Introduction
Classications .............................................................................................................. 2
Safety Information........................................................................................................2
Explanation of Signs and Symbols.......................................................................... ... 3
Specications............................................................................................................... 3
Packaging............................................................................................................. ........ 4
Section II Installation
Product Features.......................................................................................................... 5
Vacuum and Drain Plumbing....................................................................................... 6
Drain Valve Plumbing Options..................................................................................7-9
Electrical ......................................................................................................................10
Muler Installation.................................................................................................. .....11
Exhaust Plumbing .......................................................................................................12
Section III Operation
E2 Control Features ....................................................................................................13
E2 Faults ......................................................................................................................13
Turning the System On/O.........................................................................................14
Shutdown Cycle...........................................................................................................14
Vacuum Level ..............................................................................................................14
Separation Tank ..........................................................................................................14
Section IV Care
Maintenance Overview ...............................................................................................15
Preventative Maintenance Schedule.........................................................................15
Cleaning the Vacuum System....................................................................................15
Cleaning the Vacuum Unit..........................................................................................16
Changing the Air Filter................................................................................................16
Pump Head Exchange ................................................................................................16
Check Poly V-Belt........................................................................................................16
Section V User Service Information
Troubleshooting ..........................................................................................................17
Section VI Electrical Connections.......................................................................18
Section VII System Schematics...........................................................................19
Section VIII Parts List/Diagrams
Regular Maintenance Kit ...........................................................................................20
Mechanical Replacement Parts Kits..........................................................................21
Electrical Replacement Parts Kits............................................................................ 22
Limited Warranty........................................................................................................23
EMC Information....................................................................................................24-25

2
www.DentalEZ.com 866-DTE-INFO (opt 4)
2
www.DentalEZ.com
Badger LF User Manual
This manual contains installation, operation,
care, and repair instructions and user service
information for the RAMVAC® Utility Badger LF
dental vacuum system.
The main purpose of the Badger LF is to provide
a positive displacement, oil-less dry vacuum
system intended for use in a dental facility and
to be used by trained professional dental care
personnel only.
Badger LF is designed to provide trouble-free service
when installed, operated and cared for according to
the procedures set forth in this User Manual.
Vacuum is supplied to the system by a durable oil-
less rotary vane pump. A space-saving integrated
separation tank keeps liquid and foam out of the
pump. The E2 control provides precise electrical
control over run-time and shutdown operations
while vacuum is maintained at a uniform level by
the RAMVAC vacuum level control valve.
To ensure proper installation of the Badger
LF, carefully read all instructions contained
in this manual prior to installing, operating,
and servicing. For safety, pay close attention
to all notices, warnings, cautions and notes.
Section I Introduction
Safety Information
Classications
After the Badger LF is installed, please review the
features, operation procedures and care guide-
lines with the doctor's sta. Leave this manual in
the doctor's oice for future reference.
RAMVAC vacuum units are certied to ANSI/AAMI,
EX606-0-1:2005(R2012) and certied to CAN/CSA
Standard C22.2 No. 60601-11:08, and comply with
NFPA 99c Level 3 vacuum requirements, and are
manufactured in a FDA Registered ISO 13485:2003
certied facility.
– Type of protection against electric shock:
Class 1 Equipment
– Degree of protection against the ingress of
water: Ordinary
Here’s what you need to do to insure the safety
potential of this equipment is achieved:
• Make sure your equipment is installed ac-
cording to our written instructions and the
Installation Checklist is completed. If you have
purchased your RAMVAC from an authorized
dealer, the dealer is responsible for presenting
you with the completed checklist.
• Exhaust from dental vacuum systems can be
hazardous. Make sure the exhaust pipe is ter-
minated outside your building according to our
written instructions.
• Nitrous oxide and oxygen can be safely scav-
enged in the small concentrations typically
encountered in dental analgesia. The additional
air drawn into a properly installed and operated
Vacuum Unit will dilute these agents.
• Never use your RAMVAC to remove pure nitrous
oxide, oxygen or other oxidizing agents directly
from storage vessels or supply hoses. Large
concentrations may cause a re in the Vacuum
Unit and may cause an exhaust hazard.
• Never use this equipment in an OXYGEN RICH
ENVIRONMENT. Large concentrations may
cause a re in the Vacuum Unit and may cause
an exhaust hazard.
• Never use your RAMVAC for housekeeping
functions.
• Never use your RAMVAC to collect lab dust.

3
www.DentalEZ.com 866-DTE-INFO (opt 4)
3
www.DentalEZ.com
Installation by an authorized RAMVAC dealer
service technician is recommended.
NOTICE
Do not modify the Badger LF without
permission from RAMVAC. Modication will void
the warranty and could result in serious injury.
WARNING
For any questions about an order, please
contact a RAMVAC customer service
representative at 866-DTE-INFO.
NOTICE
Section I Introduction
= Caution
= Warning
= Biohazard
= Hot Surfaces
= General Mandatory Action
= Refer to Manual (follow instructions)
= Box Must Remain Upright
=
Do Not Place Box On Unlevel Surface
= Do Not Stack Box
=
Box Contents Safe Temperature Range
= Box Contents Safe Humidity Range
= Protective Earth
= Hazardous Moving Parts
Explanation of Signs & Symbols
-29ºC
(-20ºF)
74ºC
(165ºF)
0%
95%
-29ºC
(-20ºF)
74ºC
(165ºF)
0%
95%
-29ºC
(-20ºF)
74ºC
(165ºF)
0%
95%
-29ºC
(-20ºF)
74ºC
(165ºF)
0%
95%
-29ºC
(-20ºF)
74ºC
(165ºF)
0%
95%
Specications
The Badger LF Vacuum System must be
switched by a low voltage switch. It cannot be
switched with High Voltage.
NOTICE
Voltage 208-230 VAC, Single Phase
Frequency 60Hz only
Horsepower 1.5 HP
Full Load Amperes 6.2 Amps (Hi EFF motor)
Switching (low voltage) 24 VDC
Preset Vacuum Level 23.7 kPa (7" Hg)
Maximum Vacuum Level 50.8 kPa
Gauge Accuracy ASME/ANSI B40.1 Grade B (+/-3/2/3%)
Dimensions (WxDxH) 62.74 cm x 45.72 cm x 59.06 cm (24.7" x 18" x 23.25")
Floor to Drain Center Line 19.7 cm (7.75")
Weight 79.4 kg (175 lbs)
Tank Capacity 18.9 Liters (5 gallons)
Operating Temperature 4.4°C to 40°C (40°F to 104°F)
Storage Temperature -17.8°C to 65.6°C (0°F to 150°F)
Db Level 72db LF1 / 74db LF2
BTU Rating 900 btu/hr
Humidity in Transport/Storage/Operation 0% to 95% RH, no condensing moisture
Altitude in Operation 70-105 kPa (Sea level to 2,743m(9,000ft))
Altitude in Transport/Storage 50-105 kPa (Equates to 18,000 to - 1,000ft. elevation range

4
www.DentalEZ.com 866-DTE-INFO (opt 4)
4
www.DentalEZ.com
Badger LF User Manual
Packaging
It is recommended to leave the unit attached
to the shipping pallet during transport until
nal destination.
NOTICE
1. Carefully remove the shipping carton from the pallet containing the Badger LF.
2. Visually inspect the entire unit for damage. If shipping damage is found, immediately contact the
freight carrier and supplier.
3. Using a 7/16" wrench, unbolt both sides of Badger LF from the pallet.
4. To lift and handle the unit, grasp the frame rails shown in the gure below.
Lifting point Lifting points
5. Verify additional parts shipped with the Badger LF Vacuum Unit for use at installation:
This unit is heavy. Never attempt to lift or
handle without assistance.
CAUTION
Section I Introduction
Use 7/16" wrench to
remove nut and washer
from both sides of pallet
• Installation Kit
• Facility Plumbing Adapter Kit
• Drain Plumbing Adapter Kit
• Badger LF Installation Packet
• Badger LF Doctor's Packet
• SlugBuster Starter Pack
• 2 cans SlugBuster Powder
• 2 Gallon SlugBuster Mixing Jug
• Badger LF Muler Kit

5
www.DentalEZ.com 866-DTE-INFO (opt 4)
5
www.DentalEZ.com
Section II Installation
Product Features
Drain Check
Valve
Motor
Drain
Slide Valve
Pump
Exhaust
Drain Solenoid Valve
Power Conduit Whip
Exhaust
Vacuum Gauge
Belt Guard
E2 Control
Separation Tank
Tank Inlet
Tank Outlet

6
www.DentalEZ.com 866-DTE-INFO (opt 4)
6
www.DentalEZ.com
Badger LF User Manual
Vacuum and Drain Plumbing
Drain Line Options
NFPA 99c Edition
Tank Drain Line
• Waste Pipe, Slide Valve, and Drain Check Valve
- 1-1/2” PVC Schedule 40 with DWV ttings.
- Min. slope ¼” per 10 ft (2 mm per 1m).
- Use only RAMVAC supplied 1 -1/2” drain check valve.
• Trap and Drain Branch
-Trap and drain branch line 2 sizes larger than waste pipe.
-Trap seal minimum 4” deep.
• Vents
-Trap vent size no less than half the trap and drain branch size.
-Vents no smaller than drain check valve.
-Vents must extend minimum of 6” above tank top before
turning horizontal.
• Follow NFPA 99c Edition, RAMVAC Instructions,
and local codes.
To
Sewer
Vent Trap Vent
Waste Pipe
Drain Branch
Trap
To
Sewer
Drain Branch
Trap
Vent Trap Vent
Slide Valve
(must be open)
Facility Vacuum Lines
• Build Like a Drain Line:
- Use DWV Fittings
- Minimum slope ¼” per 10 ft (2 mm per 1m)
• Can be adapted to t facility plumbing from 3/4” to 2”
• If an in-line low spot is unavoidable, place it in a
known location and incorporate a clean-out.
• For overhead piping, contact RAMVAC.
• For nitrous oxide scavenging, contact RAMVAC.
• Follow NFPA 99c Edition, RAMVAC Instructions, an
local codes.
Section II Installation
Drain
Check
Valve

7
www.DentalEZ.com 866-DTE-INFO (opt 4)
7
www.DentalEZ.com
Drain Valve Plumbing Options
Section II Installation
27.25"
10"
80˚

8
www.DentalEZ.com 866-DTE-INFO (opt 4)
8
www.DentalEZ.com
Badger LF User Manual
Section II Installation
20.5"
3.25"

9
www.DentalEZ.com 866-DTE-INFO (opt 4)
9
www.DentalEZ.com
Section II Installation
3.25"
20.5"

10
www.DentalEZ.com 866-DTE-INFO (opt 4)
10
www.DentalEZ.com
Badger LF User Manual
Section II Installation
Electrical
• Follow NEC, NFPA 99C, and all local codes.
• Vacuum pump is shipped with the appropriate
6' electrical power conduit whip.
• Qualied personnel must install a dedicated
electrical circuit.
• See “Specications” for more electrical
information.
Electrical shock could occur as a result of
improper grounding. This product must be
grounded according to NEC regulations and
local codes.
WARNING
Always turn o Vacuum pump and remove
power when servicing.
WARNING
Use of an extension cord is not advisable. An
undersized extension cord will cause a drop in line
voltage and loss of power. Overheating will result.
CAUTION
1.
2.
3.
F
G
H
E2 Control
Terminals
RAMVAC
Remote Control
Panel or
equivalent with
illuminated
24v Switch
F. G. H.
Switch
Light
Common
F. G. H.
Electrician must provide a means to isolate the
circuit electrically from the supply mains on
all poles simultaneously. It shall be capable of
being locked in the OFF position.
WARNING
Vac Switch
Vac Light
Common
F - +24v DC
G - +24v DC
H - 24v DC Control
Illuminated Remote Switch
E2 Control
Electrols
Terminals
Toggle Switch
or other
non-illuminated
switch
(option)
F
H
E2 Control
Terminals
WARNING
This device should only be installed by licensed
electrical and plumbing contractors to all appli-
cable federal, state or local building codes.
To avoid the risk of electrical shock, this
equipment must only be connected to a
supply mains with protective earth.
WARNING

11
www.DentalEZ.com 866-DTE-INFO (opt 4)
11
www.DentalEZ.com
Muler Installation
Tools needed:
• 5/16” nut driver or athead screwdriver
Section II Installation
To prevent any chance of electrical shock,
always disconnect power when indicated.
WARNING
1. To install the muler assembly, slide the assembly all the way down onto the pre-installed
silencer.
NOTE: Following the directional arrows making sure that the ow arrow is pointed upwards.
2. Use a 5/16” nut driver or athead screwdriver to tighten the bottom hose clamp so that the muf-
er is tightly seated onto the silencer.
Hose Clamp
Muler
Assembly
Silencer
Muler Assembly
Installed Muler

12
www.DentalEZ.com 866-DTE-INFO (opt 4)
12
www.DentalEZ.com
Badger LF User Manual
Exhaust Plumbing
Outside End
(Installer supplied)
1. Turn outside end down toward ground and
screen to prevent entry of water, debris, and
creatures.
2. Locate inconspicuously for sight and sound.
3. Locate to prevent exhaust from entering
building.
Pipe needed:
2” Sch 80 CPVC, or metal (NOT tar coated).
Outside Wall
Breathing Dental Vacuum System Exhaust May
Be Harmful. Exhaust to Outside of Building.
Follow NFPA 99c, RAMVAC Instructions, and
local requirements.
BIOHAZARD
Roof Line
Run Dedicated Exhaust Lines for each RAMVAC
unit installed. DO NOT connect to plumbing vents.
NOTICE
Support loosely. DO NOT allowing piping to
touch ductwork. DO NOT make solid attach-
ments to building structure.
NOTICE
All joints MUST be glued with approved adhesive.
NOTICE
Section II Installation
If exhaust noise is excessive, please contact
your authorized dealer or RAMVAC for
additional muler options.
NOTICE

13
www.DentalEZ.com 866-DTE-INFO (opt 4)
13
www.DentalEZ.com
Hour Meter
START/RUN
Button
Shutdown Button
Power Status
Maintenance Light Reset Button
Vacuum
Pump Status Vacuum
Pump
Error
Tank
Float
Error
E2 Control Features
• Status Lights
• Power Status – Green light is on when line
voltage is present. Power Status light ashes
while unit is performing a shutdown cycle.
(See Shutdown Cycle Section)
• Vacuum Pump Status – Green light is on when
vacuum pump is running.
• Accepts the remote switch input.
• Maintenance Light – Yellow light is on when
preventive maintenance is due.
• Provides 24v DC low voltage signal to the re-
mote switch panel
• Controls the tank draining sequence.
• Keeps track of run time hours.
• Error Lights display fault information.
Section III Operation
E2 Faults
Faults: System Status: Corrective Action:
Maintenance System runs normally. “Maintenance” LED is illuminated. Perform “Preventive Maintenance”
Vacuum Pump Error System will not run. Remote switch indicator ashes.
“Vacuum Pump Error” LED is illuminated on E2. See Troubleshooting Section
Tank Float Error System will not run. Remote switch indicator ashes.
“Tank Float Error” LED is illuminated on E2. See Troubleshooting Section
NOTE: An Error will cause the unit to shut down. This is to protect the system from damage. An Error Fault should only be
cleared after the cause of the fault has been identied and corrected. To clear an Error Fault, press and release the Reset
Button. The unit should automatically restart.
F. G. H.

14
www.DentalEZ.com 866-DTE-INFO (opt 4)
14
www.DentalEZ.com
Badger LF User Manual
Section III Operation
Illuminated Remote Control Panel
Non-Illuminated Remote Panel
E2 Start/Run & Shutdown
Pushbuttons
Use this switch to turn system on
and o.
• If you have no remote switch.
• If you want to turn the system on
or o from the equipment’s location.
Use this switch to turn system on
and o from a remote location.
• Non-illuminated switches provide
no indication for system status.
Use this switch to turn system on and o
from a remote location.
• Switch light is steady-on when system is
running without “Fault”.·
• Switch light ashes if a “Fault” has occurred.
Turning the System On/O
Make sure all HVEs and saliva ejectors are
closed before turning the system o.
NOTICE
The RAMVAC can be run continuously throughout
the workday. Avoid wasting electricity by turning
o the RAMVAC if vacuum will not be needed for
an hour or more.
NOTE:No high voltage switching with the Badger LF.
NOTE:No special skills are required by the operator
to safely utilize this equipment. Contact the installing
dealer or RAMVAC if the following pages do not ade-
quately answer all questions.
IMPORTANT: Fluids in the separation tank are
hazardous. The Badger’s drain must be properly
connected to the facility’s sewer plumbing.
NOTICE
Shutdown Cycle
Turn the unit OFF at the end of each day. When
the unit is turned o, the power status light will
blink for 90 seconds, the tank will drain and the
Vacuum Pump will RESTART and run for a period
of 10 minutes. After this time has elapsed, the unit
will automatically turn o. This cycle is utilized to
prevent corrosion in the pump.
The vacuum level of the Badger LF is factory set
at 7 inch Hg (when all HVEs and SEs are closed).
Do not increase vacuum level above 12 inch Hg.
Vacuum Level
Separation Tank
The Badger LF contains an integrated separation
tank that will collect uids that are evacuated from
the operatory room. If the uid rises to an excessive
level within the tank, the Badger LF will disrupt vac-
uum for approximately 60 seconds in order for the
tank to drain. After this drain time has elapsed, the
unit will automatically restart and restore vacuum.

15
www.DentalEZ.com 866-DTE-INFO (opt 4)
15
www.DentalEZ.com
Section IV Care
Key points for trouble-free operation:
• Rinse vacuum lines daily with the recommend-
ed quantity of liquid and line cleaner.
• Check air lter on schedule.
• Exchange the pump head on schedule.
Foam may cause damage to the pump. Avoid
interruptions by insuring your cleaner is truly
“non-foaming”. Test by shaking the mixed
solution. True “non-foamers” will be bubble free.
CAUTION
Prior to performing any maintenance, proper
precautions should be taken to reduce the pos-
sibility of contact with infectious substances.
WARNING
Maintenance Overview
Preventative Maintenance Schedule IMPORTANT: Use of line cleaners outside of
this pH range will void the warranty.
CAUTION
Use of SlugBusterTM vacuum line cleaner is
highly recommended. SlugBuster is available
in powder and liquid forms, which can be or-
dered through any authorized RAMVAC dealer.
NOTICE
SlugBuster Ordering Information
RAMVAC
Part No.
Contents
900143 Powder Starter Pack: Mixing jug, two 40 oz.
containers of SlugBuster.
900146 Powder 6 Pack: six 40 oz. containers of
SlugBuster (makes 480 gallons of solution)
900241 Liquid Single Gallon: 1 gallon of SlugBuster
concentrate and hand pump dispenser
900243 Liquid Starter Pack: Mixing jug, 1 gallon of Slug-
Buster concentrate and hand pump dispenser
900246 Liquid 4 Pack Case: 4 single gallons of SlugBuster
concentrate and 4 hand pump dispensers
Cleaning the Vacuum System
NOTE:The Vacuum System should be cleaned daily.
NOTE:Check the treatment room solids separator
routinely and clean when dirty.
1. Just before turning o the RAMVAC, rinse vac-
uum lines rst with hot water - approximately
one quart through each high volume line and a
few ounces through each saliva ejector line.
2. Aspirate a few ounces of a dental vacuum line
cleaner through each vacuum line.
SlugBusterTM is highly recommended.
After Surgical Procedures
1. Aspirate a few ounces of an appropriate vacu-
um line cleaner, such as SlugBusterTM, through
the lines.
For Overhead Plumbing
1. Be sure to allow air to follow liquids before
closing vacuum valves.
Cleaners
Cleaners should have these qualities:
• Non-foaming
• Deodorizing
• Sanitizing
• pH between 6 and 10
Daily - Rinse vacuum lines
See "Cleaning the Vacuum System"
Every 1,000 hours* - Inspect air lters
See "Changing the Air Filters"
Every 12,000 Hours* - Exchange pump head
See "Pump Head Exchange"
* The "Maintenance" LED on the E2 Control will
illuminate every 1,000 hours.
* To reset the "Maintenance" LED after
maintenance has been performed, press and
hold the "Reset" button for 10 seconds until the
"Maintenance" LED begins blinking.

16
www.DentalEZ.com 866-DTE-INFO (opt 4)
16
www.DentalEZ.com
Badger LF User Manual
NOTE:The Vacuum Unit should be cleaned every
1,000 hours.
1. Always disconnect the power from the
equipment prior to cleaning.
2. All components can be safely wiped down
with a damp cloth, wet with water. We do
not recommend using any cleaners or harsh
chemicals to clean this equipment since their
potentially harmful eects have not been
evaluated.
3. Do not heavily wet electrical components
4. Allow equipment to air dry or dry with a clean,
soft cloth.
Cleaning the Vacuum Unit
Changing Air Filters
NOTE:Inspect air lters every 1000 hours.
1. The Air Filter is accessed by twisting the
end cap on the Air Filter Housing in a count-
er-clockwise motion.
2. Replace lters every 2,000 hours or when
visibly dirty.
Section IV Care
Some parts/components on the
vacuum unit get hot during operation.
Provide the equipment ample time to
cool prior to cleaning.
CAUTION
A detailed instruction sheet will be sent with
the replacement pump.
NOTICE
Pump Head Exchange
NOTE:Inspect pump head every 1,000 hours.
Check Poly V-Belt
Disconnect power before any service to avoid
injury during dry down cycle. E2 can start
machine if still powered. Keep hands away
from moving parts.
CAUTION
NOTE:Inspect belt every 2,000 hours. Replace if
cracked or frayed.

17
www.DentalEZ.com 866-DTE-INFO (opt 4)
17
www.DentalEZ.com
Section V User Service Information
TROUBLESHOOTING
Symptom Possible Cause(s) Corrective Action
Low or No Vacuum
(motor running okay)
Tank drain check valve blocked open Clean tank drain check valve
Clogged vacuum line Locate and remove clog
Vacuum controller stuck open Repair and replace vacuum controller
Vacuum leaks Locate and x leak
Worn or broken vanes Exchange pump head
Motor Does Not Run
"Tripped" breaker Reset breaker
"Tripped" motor overload Reset motor overload
Motor failure Replace Motor
Failed control component Replace failed component
"Vacuum Pump Error" fault See "Vacuum Pump Error" fault below
"Tank Float Error" fault See "Tank Float Error" fault below
Liquid Comes
Out Exhaust
Unit unleveled Level unit
Foam in tank Use non-foaming line cleaner
"Vacuum Pump Error"
Fault
Incorrect electrical installation Correct installation
Motor failure Replace motor
"Tripped" motor overload Reset motor overload
"Tank Float Error"
Fault
Separating tank overlled Drain separation tank
Separation tank drain check valve stuck Clean separation tank drain check valve
Clogged drain line Locate and remove clog
Drain shut-o valve closed Open drain shut-o valve
Tank oat switch stuck Replace tank oat switch
Facility drain elevated above tank drain Raise unit
Maintenance Required Preventative maintenance due Perform preventative maintenance

18
www.DentalEZ.com 866-DTE-INFO (opt 4)
18
www.DentalEZ.com
Badger LF User Manual
Section VI Electrical Connections
L1 - BLACK
L2 - RED
GROUND - GREEN/YELLOW
L2 L1 L2 L1
Vacuum
Motor
Power
(230v 1 phase)
Ground

19
www.DentalEZ.com 866-DTE-INFO (opt 4)
19
www.DentalEZ.com
Section VII System Schematics
Facility
Plumbing
Remote
Switch
Breaker
Box Disconnect
Tank
Drain
Vacuum
devices
2” Dedicated
Exhaust
to outside
Low Voltage Wires
3 conductors
Table of contents
Popular Vacuum Cleaner manuals by other brands

iRobot
iRobot Roomba Combo j5 user manual

Nilfisk-Advance
Nilfisk-Advance Multi 20 user manual

Hoover
Hoover Stick Cleaner S2535 owner's manual

EIBENSTOCK
EIBENSTOCK SS 1400 Original operating instructions

Bissell
Bissell POWERFORCE HELIX TURBO REWIND PET 2692... user guide

Makita
Makita CL106FD instruction manual