RCS Technology TBZ500 User manual

DCN: 140-02338-01 DRAFT 20619
Page 1
Installation Guide
Model TBZ500
Battery Powered Z-Wave Thermostat
This thermostat is compatible with most HVAC systems, including the following:
24VAC systems Note: requires both the R and C wires unless battery powered.
Standard gas/oil/electric heating systems
o1 stage heating and cooling
o2 stage heating and cooling
Heat Pump systems:
o1 stage heating and cooling
o2 stage heating and cooling
o2nd or 3rd stage Auxiliary heating (heat strips)
Do NOT use for line voltage controls (120/240VAC)
The thermostat can be powered by batteries or 24VAC.
Battery Power
The thermostat can be powered by four AA Alkaline batteries. The thermostat will operate
for approximately two years on four AA Alkaline batteries depending on the frequency of
user operations and backlight operation. Always use Alkaline batteries and replace in
complete all four at a time with new batteries.
Z-Wave Operation when Battery Powered
Important Note: If the thermostat is installed on a Z-Wave network, while it is battery
powered,it will not work as a Z-Wave repeater.
24VAC Power
Powering the thermostat with 24VAC power requires both the C wire (24VAC common
wire - typically blue) and the R wire (24VAC hot wire - typically red). If the C wire is not
available, then batteries are required.
Note! If the thermostat is powered from 24VAC, batteries are not required.
Z-Wave Operation when 24VAC powered
If the thermostat is installed on a Z-Wave network while it is 24VAC powered, it operates
as an always-on Z-Wave repeater.
Installation Steps
Remove old thermostat.
Install TBZ500
Set up the thermostat for the HVAC system
Enroll on Z-Wave network
Remove old thermostat
Turn off power. Usually at the heating/cooling system or circuit- breaker panel.
Remove cover of old thermostat to expose the wiring terminals
Take a picture of the wiring terminals! Note: This will help with
troubleshooting later if needed.
Mark the wires attached to the terminals with the wiring labels included

DCN: 140-02338-01 DRAFT 20619
Page 2
Use the terminal labels and not the wiring color to mark the wires
Remove the old thermostat base
Caution. Don’t let the wires slip into the wall.
Wiring colors. While the wiring terminals markings are intended to match the wire color
(R=red, G=green, W=white, Y=yellow), not all installations were correctly installed this way.
Be sure to follow the terminal marking when marking the wires, even if the wire color
doesn’t match.
The C wire. If the 24VAC Common wire (usually Blue) is present and is connect to 24VAC
common at the HVAC system end, the thermostat can be powered from the HVAC system
and batteries are not required. If there is no Common wire, batteries are required.
Mount the thermostat base
Mount the thermostat base to the wall using the wall anchors and screws provided.
Level as needed.
Connect the wires –most common connections
Single Stage Gas Heating/Cooling HVAC System Wiring to the Thermostat
R vs RC and RH Connections:
Typical HVAC installations will have a common heating and cooling system 24VAC
transformer. For these systems, there is only one 24VAC “R” wire and it can connect to
either the RC or RH terminal on the thermostat. The thermostat is supplied with an RC-RH
jumper installed. Do not remove the jumper for common transformer HVAC systems.
Some installations may have separate heating and cooling systems/transformers. For
those systems there will be a separate “R” wire for the heating (RH) and cooling
transformers (RC).
Y
C
R
W
G
Y
W
G
R
C*
Take a
Picture!
*Note: the C wire (24V common) may
not be present.
If there is no C wire, the TBZ500
must be powered by batteries.
If the C wire is present, you can
power the thermostat without
batteries
Mark the wires according to the terminal markings.
There may be additional wires. Mark these according to the
terminals. Y1, Y2, W1, W2, O, B.
W
Y
G
C*
R
Connect the wires as marked from the HVAC
system to the corresponding terminals on the
thermostat back.
*C wire (24VAC common) may not be present.
If not, batteries must be installed.
Factory installed RC and RH jumper
Thermostat
Terminal Block
W2/O W1 RH C RC G Y1 Y2

DCN: 140-02338-01 DRAFT 20619
Page 3
To connect dual transformer systems, FIRST REMOVE THE SUPPLIED RH-RC JUMPER.
Then connect the heating “R” wire to the RH terminal and the cooling “R” wire to the RC
terminal on the thermostat.
Single Stage Heat Pump HVAC System Wiring to the Thermostat
If you have additional wires, see the wiring diagrams on page 5 and 6.
Check that the wires are screwed into the terminal blocks firmly.
Gently pull on the wires to confirm the connection.
Push all the excess wiring back into the wall.
Mount the thermostat
If the thermostat is 24VAC powered (24VAC common “C” wire connected).
DO NOT INSTALL BATTERIES!
Install the thermostat on to the base.
Turn on power to the thermostat.
Connect the wires as marked from the HVAC system
to the corresponding terminals on the thermostat
back.
*C wire (24VAC common)
Heat Pump systems usually have the C wire
connected to the thermostat. If there isn’t a C wire,
batteries must be installed.
** O or B wires (changeover valve) connect to the
W2/O terminal on the thermostat. Set the correct
changeover operation (O = change over with cool, B
= changeover with cool) in the SETUP menu.
Connect the R wire to either RC or RH terminals.
Factory installed RC and RH jumper
Factory installed RC and RH jumper. Do not remove.
O**
W
Y
G
C*
R
Thermostat
Terminal Block
W2/O W1 RH C RC G Y1 Y2

DCN: 140-02338-01 DRAFT 20619
Page 4
If the thermostats is battery powered (NO 24VAC C wire connected),
install 4 AA batteries into the back of the thermostat.
Install the thermostat on to the base.
Turn on power to the thermostat.
Install batteries
Watch polarity!
+
+
+
+

DCN: 140-02338-01 DRAFT 20619
Page 5
Standard HVAC System
G Fan
W1 Heat Stage 1
Y1 Compressor Stage 1
R 24VAC Return
C 24VAC Common
Thermostat Connection
Y2 Compressor Stage 2
W2 Heat Stage 2
For single transformer systems,
connect R wire to either RC or RH
terminal. They are jumpered
together by the factory installed
jumper.
For systems with separate heating
& cooling transformers, connect
Heating R to RH and Cooling R to
RC. NOTE! REMOVE THE
FACTORY INSTALLED RC/RH
JUMPER.
Standard Gas/Electric HVAC System Wiring
Thermostat Setup:
Standard Gas/Electric HVAC Systems
For Single Stage Heat/Cool Systems:
Go to the Menu screen by pressing and holding the FAN button for 5 seconds
Press the down arrow to select the SYSTEM menu and press Select.
Set the following:
SYSTEM TYPE: Set to STANDARD
FAN TYPE: Set to GAS for typical gas furnace (fan is controlled by the furnace)
Set to ELECTRIC for electric heat (fan on with heat call)
For Two Stage Heat/Cool Systems:
Go to ADVANCED SYSTEMS SETTINGS menu.
From the Setup menu screen, press and hold the Fan and Down arrow buttons
for 5 seconds. Use the Down arrow button to select the following:
2NDSTAGE HEAT ENABLE: Enable second stage heating output
If a single stage heating system, leave this set to N
If a 2 stage heating system, set to Yto enable.
2ND STAGE COOL ENABLE: Enable second stage cooling output
If a single stage cooling system, leave this set to N.
If a two stage cooling system, set to Yto enable.
Default Thermostat Setup:
Type: Standard HVAC
Fan Type: Gas Heat
1 Stage heating
1 Stage cooling
No Setup change required
for this configuration
Thermostat back
Typical thermostat wiring colors.
Caution: verify that original wiring
matches. Colors may be different.
Blue
Black/Brown
Red
White
Orange
Yellow
Green
C wire is not required for
battery operation.
C wire is required for 24VAC
operation.
W2/O
W1
24RH
24C
24RC
G
Y1
Y2
Factory Installed RC/RH jumper

DCN: 140-02338-01 DRAFT 20619
Page 6
G Fan
W1 Aux Heat
Y1 Compressor Stage 1
R 24VAC Return
C 24VAC Common
Y2 Compressor Stage 2
O Changeover Valve
Connect the R wire to either
the RC or RH terminal.
DO NOT REMOVE THE
RC/RH JUMPER
Heat Pump HVAC System
Thermostat Connection
Heat Pump HVAC System Wiring
Thermostat Setup:
Heat Pump HVAC Systems
For Single Stage Heat/Cool Systems:
Go to the Menu screen by pressing and holding the FAN button for 5 seconds
Press the down arrow to select the SYSTEM menu and press Select.
Set the following:
SYSTEM TYPE: Set to HEAT PUMP
CHANGE OVER: For changeover with cooling systems (Orange wire): set to WITH COOL (most common and default setting)
For changeover with heating systems (Brown wire): set to WITH HEAT
You must configure the thermostat’s changeover valve setting to work correctly with your HVAC system.
Check your system information to be sure and note the color of original thermostat wire and the terminal it was connected to.
No matter what the old stat connection was (O or B), connect the wire to the thermostats W2/O terminal.
For Two Stage Heat/Cool Systems:
Go to ADVANCED SYSTEMS SETTINGS menu. From the Setup menu screen, press and hold the Fan and Down arrow buttons
for 5 seconds. Use the Down arrow button to select the following:
AUXHEAT: If you have auxiliary heat strips, set this to Y to enable. (Default is Y)
2ND STAGE HEAT ENABLE: Enable second stage heating outputs
If a single stage heating system, leave this set to N
If a 2 stage heating system, set to Yto enable.
2ND STAGE COOL ENABLE: Enable second stage cooling outputs
If a single stage cooling system, leave this set to N.
If a two stage cooling system, set to Yto enable.
Note! If you get heating
when you expected cooling
or vice versa, change the
Change Over type to the
opposite setting.
Thermostat back
Black/Brown
Yellow
Green
Red
Blue
White
Orange
Typical thermostat wiring colors.
Caution: verify that original wiring
matches. Colors may be different.
C wire is not required for
battery operation.
NOTE! Most Heat Pump
systems do have the C wire
and the thermostat can be
power by the 24VAC from the
HVAC system.
Batteries are not required for
24VAC powered systems.
W2/O
W1
24RH
24C
24RC
G
Y1
Y2
Factory installed RC/RH jumper

DCN: 140-02338-01 DRAFT 20619
Page 7
Thermostat Setup
The thermostat must be setup for the correct system type and configuration of the HVAC
system for proper operation.
Preset HVAC System settings
The thermostat is preset for the following typical HVAC system configuration:
HVAC system type: Standard gas/electric
HVAC fan type: Gas heat
HVAC heating stages: one
HVAC cooling stages: one
If the thermostat is installed on this type HVAC system, the System
setup does not need to be changed.
If installed on a Heat Pump HVAC system or any HVAC configuration other than the preset
settings, change the System settings in the SYSTEM setup menu to match the HVAC
system.
Changing the HVAC system setup
The thermostat normally displays the Thermostat Main Control Screen. To change the
thermostats HVAC system settings, select the Menu Screen and then select the SYSTEM
menu. Follow instructions below to access the SYSTEM menu.
Note: To conserve battery life, the thermostat backlight turns off after a short time of no
activity. The first press of any button turns on the backlight (but does not initiate any
action). Press the button again to initiate the action desired. If the backlight is already on,
button presses work with the first press.
Thermostat Main Screen
The thermostat Main screen shows the basic thermostat settings and controls. It allows
you to set the temperature setpoints and the operating modes of the HVAC system. To
change the thermostat setup and other user options, first select the thermostat Menu
screen.
To select the Menu
screen, press and
hold the FAN button
until the Setup screen
is displayed

DCN: 140-02338-01 DRAFT 20619
Page 8
Thermostat Menu Screen
Selecting the Menu Options
When the Thermostat Menu Screen is displayed, use the Up or Down arrow buttons to
scroll through the following options:
SETUP (user preference settings)
SYSTEM (HVAC system setup)
ZWAVE (install/uninstall from Z-Wave network)
CLOCK (set the time and day)
INFO (firmware versions and Z-Wave network information)
SYSTEM SETUP
To change the HVAC system default settings, scroll down to the SYSTEM item and press
“Select”.
SYSTEM Menu
The SYSTEM menu is used to setup the thermostat for the correct HVAC system type.
HVAC System Type: Standard Gas/Electric or Heat Pump
Fan Type: Gas Heating or Electric Heating
Changeover Valve Type (for Heat Pump Systems): Changeover with Cooling or with
Heating.
When SYSTEM is selected in the Menu options, the following setup options will be
displayed in the text line.
Use the UP/Down arrow buttons to scroll to the desired setting.
Press “Select” to change a setting. The current setting for that selection will be
flashing.
Change the selection with the Up/Down arrows.
When the desired setting has been selected, Press “Select” again to save it.
Then press “Done” to exit.
System Type
For Standard Gas/Electric systems, select “Standard”. This is the default setting.
For Heat Pump systems, use the Up/Dn arrows to change to “Heat Pump”
Use the Up/Down
buttons to change
to the desired
menu item, then
press “Select”
Menu choices are
displayed in the
Status Display Line.
Press “Select” to
enter the selected
menu
Press “Done” to
exit back to the
Main Thermostat
Screen

DCN: 140-02338-01 DRAFT 20619
Page 9
Press Select to set.
Press Done to exit
Fan Type (For Standard HVAC systems only)
Fan type depends on the heating system type.
For Gas heat: select “GAS”. This is the default setting.
For Electric heat: use the Up/Dn arrows to change to “ELECTRIC”.
Press Select to set
Press Done to exit
Changeover Type (For Heat Pump HVAC systems only)
The changeover (or reversing) valve is used to change from heating to cooling operation. It
is either a changeover with cooling type or changeover with heating type. Most are
changeover with cooling, which is the default setting.
For Changeover with Cooling systems, select “WITH COOL”. This is the default
setting.
For Changeover with Heating systems, use the Up/Dn arrows to change to “WITH
HEAT”.
Press Select to set
Press Done to exit
Not sure what type Changeover system? Check the existing thermostat connections to help
determine this. If the original system had an orange wire connected to an “O” terminal,
then this is a “changeover with cool” system. If there was a brown wire connected to a
“B” terminal, then this is a “change over with heat” system. Set the Change Over setting
accordingly. (Caution: These are typical wiring colors/connections)
Note: If heating comes on when cooling is expected or vice versa, change the
“Change Over Type”to the opposite setting.
Advanced System Settings Menu
The Advanced System Settings Menu provides for addition system setup options.
These settings can affect system operation and should only be changed by qualified HVAC
installers.
To access the Advanced System Settings menu, first press and hold the Fan button to get
into the Setup menu. While in the Setup Menu, press and hold both the Fan and Down
Arrow buttons for 5 seconds. The first menu item in the Advance System Settings menu
“Display Lock”, will be displayed. Use the Up/Down arrow buttons to scroll through the
menu options to the desired setting. Press “Select” (Mode) button to change a setting.
Once it begins to flash, use the Up/Down buttons to select the desired setting. Press the
“Select”button to accept the new setting (flashing will stop).
Advanced Settings
Display Lock Range: Y or N Default: N
Y = Display LOCKED
N = Display UNLOCKED
Allows the thermostat buttons to be locked. When the buttons are locked, none of the
thermostat buttons will function.

DCN: 140-02338-01 DRAFT 20619
Page 10
To unlock the thermostat, press and hold the FAN button for 5 seconds to access the
Setup screen (it’s the only button that works in the lock mode). Access the Advanced
Settings Menu (as above) to turn the Display Lock off.
Test Mode Range Y or N Default: N
Test mode shortens the system built-in delays (like MOT and MRT)
Y= Test mode on. Reduces all delays to 10 sec for quicker system testing
N= Test mode off. Normal system delays
Aux Heat Enable (Heat Pump Systems only) Range: Y or N Default: Y
Enables the Auxiliary Heat operation.
Typically the Aux Heat will be heat-strips in a Heat Pump system
2nd Stage Heat Enable Range: Y or N Default: N
Enables the 2nd Stage Heat operation
2nd Stage Cool Enable Range: Y or N Default: N
Enables the 2nd Stage Cool operation
Minimum Run Time Range: 1- 9 Minutes Default: 3
Sets the Minimum Run Time (MRT) delay before a heating/cooling cycle can turn off.
Sets heating/cooling cycle time. Prevents rapid on/off cycling.
Minimum Off Time Range: 5-9 Minutes Default: 5
Sets the Minimum Off Time (MOT) delay before another heating/cooling cycle can begin.
Provides compressor short cycle protection. “WAIT” is displayed on screen when active.
Heat Setpoint Max Range: 30F to 109F (0C-43C)Default: 90F (32C)
Sets the maximum heating setpoint value.
Will not ramp or accept setpoints higher than this maximum.
Cool Setpoint Min Range: 33F to 112F (2C-45C)Default: 60F (15C)
Sets the minimum cooling setpoint value.
Will not ramp or accept setpoints lower than this minimum.
Heat Blower Off Delay Range: 0-90 seconds Default: 0 (off)
Sets the system blower delay off time after a heat call ends (fan purge).
Cool Blower Off Delay Range: 0-90 seconds Default: 0 (off)
Sets the system blower delay off time after a cool call ends (fan purge).
Heat - Cool Delta Range: 3 - 15 degrees. Default: 3F (1C)
Sets the minimum separation between heating and cooling setpoints.
Note! Attempts to lower the cooling setpoint below the heating setpoint will PUSH the
heating setpoint down to maintain this separation. The same applies to setting the heating
setpoint above the cooling setpoint, it will PUSH the cooling setpoint up to maintain the
setpoint delta separation.
Heating Stage 1 On Threshold Range: 1 to 6 degrees Default: 1
Sets the delta from setpoint that stage 1 heating starts.
Heating Stage 1 Off Threshold Range: 0 to 5 degrees Default: 0
Sets the delta from setpoint that stage 1 heating stops.
Stage 1 turns off at setpoint + Delta Stage 1.
Heating Stage 2 On Threshold Range: 2 to 7 degrees Default: 2

DCN: 140-02338-01 DRAFT 20619
Page 11
Sets the delta from setpoint that stage 2 heating starts.
Heating Stage 2 Off Threshold Range: 0 to 6 degrees Default: 0
Sets the delta from setpoint that stage 2 heating stops.
Stage 2 turns off at setpoint + Delta Stage 2.
Aux Heat On Threshold Range: 3 to 8 degrees Default: 3
Sets the delta from setpoint that stage 3 heating starts.
Aux Heat Off Threshold Range: 0 to 7 degrees Default: 0
Sets the delta from setpoint that stage 3 heating stops.
Stage 3 turns off at setpoint + Delta Stage 3.
Cooling Stage 1 On Threshold Range: 1 to 7 degrees Default: 1
Sets the delta from setpoint that stage 1 cooling starts.
Cooling Stage 1 Off Threshold Range: 0 to 6 degrees Default: 0
Sets the delta from setpoint that stage 1 cooling stops.
Stage 1 turns off at setpoint - Delta Stage 1
Cooling Stage 2 On Threshold Range: 2 to 8 degrees Default: 2
Sets the delta from setpoint that stage 2 cooling starts.
Cooling Stage 2 Off Threshold Range: 0 to 7 degrees Default: 0
Sets the delta from setpoint that stage 2 cooling stops.
Stage 2 turns off at setpoint - Delta Stage 2.
Restore Defaults Range: Yes, No Default: No
Restores all settings to factory defaults.
Press Yes to restore defaults
Press No to exit and not restore defaults
Z-Wave Installation
See the Operating Guide for instructions on installing the thermostat on a Z-Wave network.

DCN: 140-02338-01 DRAFT 20619
Page 12
Operation Guide
Model TBZ500
Battery Powered Z-Wave Thermostat
Backlight and Button Operation
The thermostat backlight is normally set to go out after 20 seconds of no button presses to
conserve battery power. If the backlight is off, the first button press of any button will
only turn on the backlight. Once the backlight is on, the buttons function normally.
TBZ500 Display
System Operation Modes
displayed > System is ON and heating
displayed > System is ON and cooling
Temperature
Setting
Warmer
Cooler
Fan Mode
Selection
Heating/Cooling
Mode Selection
Battery Compartment
Flip over
2xAA or 4xAA Alkaline
Batteries
Room Temperature
Text Display Line
Backlit Display
Main Thermostat Screen
$$:$$$$~
Auto
On
Done
Off
Heat-E
Cool
Auto
Select
123
FC
LOW BATT
Low Battery indicator
Display Lock indicator
Z-Wave Network Installed
indicator
Text Display Line
System Mode
indicators
Fan Mode
indicators

DCN: 140-02338-01 DRAFT 20619
Page 13
blinking > System is ON and heating. Minimum Run Time (MRT) delay is active.
blinking > System is ON and cooling. Minimum Run Time (MRT) delay is active.
Staging Indicators
“1” = Stage 1 heating or cooling is ON
“2” = Stage 2 heating or cooling is ON
“3” = Stage 3 heating (Aux Heat) is ON
For Heat Pump systems only:
“Heat-E” = Emergency heat mode active
Setting the System Mode
System Modes
Off: System is off. No heating or cooling will come on. If system was on, it will
turn off immediately.
Heat:Only heating will occur.
Cool:Only cooling will occur.
Auto: Heating or cooling will come on according to the heating and cooling
setpoints. The system will automatically switch between heating and cooling
modes as needed to maintain the setpoints.
Special Heat Pump Mode: Emergency Heat
Heat-E: An additional system mode, “Heat-E” for Emergency Heat will be
displayed if the HVAC System Type is set to Heat Pump. If there is a
compressor failure with the Heat Pump system, setting the mode to Emergency
Heat will allow the supplemental Aux Heat to come on first whenever there is a
call for heating. It also disables the compressor output to prevent further damage
to the HVAC system.
Caution! Emergency Heat should only be used for emergencies until the HVAC system
can be repaired. Running the system in Emergency Heat mode is commonly the most
expensive mode since only the electric heat strips are being used instead of the
more efficient heat pump compressor.
Press MODE
button to change
system mode

DCN: 140-02338-01 DRAFT 20619
Page 14
Setting the Heating or Cooling Temperature Setpoint
Setpoint Change
To change the setpoint, press the Up or Down arrow buttons. The screen will switch to the
setpoint change screen (as above) and show the current setpoint of the current heating or
cooling mode. Adjust setpoint temperature up or down with the arrow buttons.
Note! When in the Setpoint Change screen, pressing the MODE button will switch
the setpoint being displayed between the Heat and Cool setpoints.
Setpoint Push: The cooling setpoint cannot be set below the heating setpoint. The
thermostat will “push” the heating setpoint lower if the cooling setpoint is set below the
current heating setpoint. A 3 degree separation is maintained between the heating and
cooling setpoints. The same is true for raising the heating setpoint above the cooling
setpoint. The thermostat will “push” the cooling setpoint up to maintain the 3 degree
separation.
Lower Temperature
Raise Temperature
Press either Up or Down
arrow button to go to the
Setpoint Change screen
Setpoint Change screen
Press “Done”(FAN button) to set the setpoint and exit back to the main
thermostat screen or wait for the screen to automatically time out.
Press the Up or Down arrow
buttons to set the desired
temperature setpoint
Pressing the Up or Down
buttons will change the
setpoint 1 degree. Press and
hold the button to ramp the
setpoint.
Setpoint being changed
Press MODE
button to change
from the heat
setpoint to the
cool setpoint

DCN: 140-02338-01 DRAFT 20619
Page 15
Setting the Fan Mode
Thermostat Menu Mode
The Thermostat has a menu of setup and information displays.
To change to the Menu Mode, press and hold the FAN button for 5 seconds.
The display will change to the Menu Mode and display the Setup screen.
Use the Up/Down arrow buttons to scroll through other menu items.
Thermostat Main Screen
Press the FAN button to change the Fan mode
Fan Modes:
Auto: Fan automatically operated by the HVAC system. (normal setting)
On: Manual Fan mode. Fan stays on until mode is changed back to Auto,
independent of the heating or cooling system operation.
Press and hold the
FAN button for 5
seconds to go to
the Menu Mode
screen

DCN: 140-02338-01 DRAFT 20619
Page 16
Menu Mode Screen
Menu Mode options
SETUP User preference settings
SYSTEM Thermostat HVAC system settings
ZWAVE Z-Wave network install or remove
CLOCK Setting the thermostat time and day
INFO Displays thermostat version and setup info
SETUP Menu
User preference settings.
FAHRENHEIT OR CELSIUS. Select the temperature display mode.
BACKLIGHT TIMEOUT. Sets the time from last button press that the backlight will turn off.
Range:10-30 seconds. Note: long backlight timeouts will reduce battery life.
If the thermostat is powered from 24VAC, the backlight timeout can be set to “0” which will
keep the backlight on continuously.
SENSOR CALIBRATION Change the temperature calibration by +/- 7 degrees.
Use the Up/Dn arrow buttons to change to the desired display temperature.
SYSTEM Menu
SYSTEM TYPE. Select the system type, STANDARD or HEAT PUMP
FAN TYPE (Standard systems only).
Select fan type: GAS (typical default setting) or ELECTRIC
CHANGE OVER TYPE (Heat Pump systems only).
Select the Changeover type:
Changeover WITH COOL (typical default setting)
Changeover WITH HEAT
Use the
UP/DOWN
buttons to select
the desired menu
item
Press “Select”
to go to the
selected menu
item screen
Press “Done” to
go back to the
Thermostat
Main Screen
Menu item display

DCN: 140-02338-01 DRAFT 20619
Page 17
See Installation Guide for more information on System setup and the Advanced Systems
Menu
Z-WAVE Menu
This menu item allows the thermostat to be enrolled to the Z-Wave network. Follow the
instructions shown in the Z-Wave® Operation section (page 19) to enroll the Thermostat
onto the network.
CLOCK Menu
Set the time and day of the week.
Press select to set the DAY. The current day of the week setting will be displayed.
Press the UP/DN arrows to change the day of the week desired.
Press select to set the TIME. The current time will be displayed.
Press the UP/DN arrows to change the time.
INFO Menu
The INFO menu displays information about the thermostat. Use the Up/Dn buttons to scroll
through the various items.
Thermostat information displayed:
VERSION Thermostat firmware version
ZWAVE Z-Wave firmware version
NODE ID Z-Wave Node ID
HOME ID Z-Wave Home ID
SYSTEM TYPE displays current System Type setting (Standard or Heat Pump)
If System Type = Standard
FAN TYPE displays current Fan Type setting
If System Type = Heat Pump
CHANGEOVER TYPE displays current Change Over valve (reversing valve) setting
Thermostat Operation
Minimum Run Time (MRT)
The thermostat has a Minimum Run Time (MRT) delay after the start of any heating or
cooling call. This minimum run time assures even heating and cooling cycles. The MRT
will keep the system on, even if it reaches the setpoint room temperature, or you change
the setpoint to a temperature that would satisfy the call, until the MRT expires. Changing
the Mode to OFF will cancel the MRT and the system will turn off immediately. The MRT
can be adjusted in the Advanced Settings menu of the thermostat.
Note: The MRT status is shown in the thermostat Status display.

DCN: 140-02338-01 DRAFT 20619
Page 18
Minimum Off Time (MOT)
The thermostat has a Minimum Off Time (MOT) delay after any heating or cooling cycle
ends. This delay prevents rapid heating/cooling cycles and also provides “short cycle
protection” for the system compressor. This delay may be noticeable when you change a
setpoint and it does not respond immediately due to the MOT delay timer preventing the
system from restarting. The MOT delay time can be adjusted in the Advanced Settings
menu of the thermostat but there is a minimum of a 5 minute delay to assure compressor
protection.
Note: The MOT status is shown in the thermostat Status display.

DCN: 140-02338-01 DRAFT 20619
Page 19
Z-Wave®Operation
Thermostat Battery Operation: If the thermostat is installed in a Z-Wave network while
powered by batteries, it will be enrolled as a Z-Wave FLiRs type device. This is a power
saving mode that conserves the batteries by keeping the radio asleep most of the time.
However, in this mode, the thermostat does not act as a repeater/router in the Z-Wave
network.
Thermostat 24VAC Operation: If the thermostat is installed in a Z-Wave network while
powered by 24VAC, it will be enrolled as an always-listening device and can act as a router
node in the Z-Wave network.
Caution! Once installed in a Z-Wave network, if you change how the thermostat is
powered (from batteries to 24VAC or vice versa), you must remove and re-enrolled
the thermostat in the Z-Wave network for it to work correctly.
Adding the thermostat to a Z-Wave network.
1. Follow the instructions provided with your system for enrolling the thermostat.
2. Press and hold the FAN button on the Thermostat until the screen changes to
the Menu screen.
3. Press the UP button until ZWAVE is shown in the Status Display line then press
Select.
4. INSTALL should be shown on the status line.
5. When instructed by your system installation to add the thermostat to the network
press the “Select” button to install. Wait until SUCCESS or FAILED is shown on
the status display.
6. Press Done on the Thermostat to exit the ZWAVE screen.
7. Press Done on the Thermostat again to exit the Menu screen.
8. Once enrolled on your system’s network, continue to follow the instructions
provided to complete the enrollment and naming of the thermostat.
9. The indicator should be shown on the Thermostat Main screen indicating
the thermostat has successfully been enrolled into the Z-Wave network.
Removing the thermostat from a Z-Wave network.
It may be necessary to remove and/or reinstall the thermostat from a Z-Wave network, if
the thermostat has been previously installed on another network.
Follow the instructions supplied with your Z-Wave system to remove/uninstall a Z-Wave
device. When the system instructs you to press and release the Z-Wave button on the
thermostat, follow these steps:
1. Press and hold the FAN button for 3 seconds until the Menu screen is displayed.
2. Press the UP arrow button to scroll to the “ZWAVE” menu.
3. Press “Select” to select the ZWAVE screen.
4. The display will show “REMOVE” in the text line.
5. Press “Select” to perform the remove action.
6. “WAIT” will be displayed in the text line. The remove operation is in process.
7. “SUCCESS” will be display when the reset is completed.
8. Press “Done” to exit back to the thermostat screen.
9. Thermostat is now ready to be added to the wireless network.

DCN: 140-02338-01 DRAFT 20619
Page 20
FCC/IC
INFORMATION TO USER
This device complies with FCC part 15 FCC Rules. Operation is subject to the following
two conditions:
1. This device may not cause harmful interference and
2. This device must accept any interference, including interference that may cause
undesired operation of the device.
FCC Warning
Changes or modifications not expressly approved by the party responsible for compliance
could void the user’s authority to operate the equipment. Note: This equipment has been
tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of
the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used in accordance with the instructions,
may cause harmful interference to radio communications. However, there is no guarantee
that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
•Reorient or relocate the receiving antenna.
•Increase the separation between the equipment and receiver.
•Connect the equipment into an outlet on a circuit different from that to which
•the receiver is connected.
•Consult the dealer or an experienced radio/TV technician for help.
•This device meets the FCC and IC requirements for RF exposure in public or
uncontrolled environments.
This device complies with Industry Canada license-exempt RSS standard(s). Operation is
subject to the following two conditions: (1) this device may not cause interference, and (2)
this device must accept any interference, including interference that may cause undesired
operation of the device.
Cet appareil est conforme avec Industrie Canada RSS standard exempts de licence (s).
Son utilisation est soumise à Les deux conditions suivantes:
1. cet appareil ne peut pas provoquer d’interférences et
2. cet appareil doit accepter Toute interférence, y compris les interférences qui
peuvent causer un mauvais fonctionnement du dispositive
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada
Table of contents
Other RCS Technology Thermostat manuals
Popular Thermostat manuals by other brands

Verve
Verve VTST-9 user guide

Honeywell
Honeywell MagicStat /28 Programming and installation instructions

CTC Union
CTC Union BTG-UN user manual

Chromalox
Chromalox PK407-3 Installation, operation and renewal parts identification

Telkonet
Telkonet SS5200 Installation & maintenance guidebook

Hunter
Hunter 44132 owner's manual

Danfoss
Danfoss SET 3E installation guide

Mora armatur
Mora armatur Tronic Compact 720256 Installation instruction

Hot Yoga Heating
Hot Yoga Heating HYH-32-P user manual

Hive
Hive Active Heating installation guide

Hitachi
Hitachi ATW-RTU-02 Installation and operation manual

Neotherm
Neotherm Futura W quick guide