Regin ADD:IO User manual

en
WE TAKE BUILDING
AUTOMATION PERSONALLY
MANUAL
ADD:IO

Rev. A, 2019-10-23
THANK YOU FOR CHOOSING REGIN!
Ever since Regin was established in 1947, we have developed and mar eted products and systems that create good
levels of indoor comfort. Today, we are an important player with one of the mar et's broadest ranges for building
automation.
Our goal is to ma e real estates in the world more energy efficient. Regin is an international group and our products
sells in over 90 countries. Than s to our global presence with strong local representation, we are well aware of the
requirements of the mar et, as well as of how our products and systems function under the most variable conditions.
Every year, Regin ma es substantial investments in the development of our systems and HVAC-products.
DISCLAIMER
The information in this manual has been carefully chec ed and is believed to be correct. Regin ma es no warranties
about the contents of this manual and users are requested to report errors and discrepancies to Regin, so that
corrections may be made in future editions. The information in this document is subject to change without prior
notification.
Some product names mentioned in this document are used for identification purposes only and may be the registered
trademar s of their respective companies.
© AB Regin. All rights reserved.

Table of Content
1 Introduction .................................................................................................................................5
1.1 General..............................................................................................................................5
1.2 Layout ...............................................................................................................................5
1.3 Dimensions ........................................................................................................................6
1.4 Mounting ...........................................................................................................................6
1.5 Communication..................................................................................................................7
1.6 Naming..............................................................................................................................7
2 Deployment.................................................................................................................................8
2.1 Installation recommendations...............................................................................................8
2.2 General status indicator .......................................................................................................8
2.3 System addressing ...............................................................................................................9
3 Model IO-EC16UIc-X................................................................................................................10
3.1 Terminals.........................................................................................................................10
3.2 Wiring .............................................................................................................................12
4 Model IO-EC16UId-X................................................................................................................13
4.1 Terminals.........................................................................................................................13
4.2 Wiring .............................................................................................................................15
5 Model IO-EC16UOb-X .............................................................................................................16
5.1 Terminals.........................................................................................................................16
5.2 Wiring, AC.......................................................................................................................18
5.3 Wiring, DC ......................................................................................................................18
Appendix A Technical data..........................................................................................................19
A.1 General data.....................................................................................................................19
A.2 Serial port data .................................................................................................................19
A.3 Material ...........................................................................................................................19
Appendix B Model overview .......................................................................................................20
Appendix C Input and output li t ...............................................................................................21


Introduction
1 Introduction
1.1 General
The Add:io series is intended for use in combination with EXOclever and EXOcompact to expand the
number of I/Os in a system. Each unit expands the system with 16 I/Os. An EXOclever controller can be
expanded with unlimited I/Os and an EXOcompact with up to 50 I/Os.
The units are programmable in EXOdesigner, the same environment used for all other EXO controllers.
1.2 Layout
All available Add:io models have a similar design and layout. It is shown in Figure 1-1.
Number Description
1 DO or DI indications
2 General status indications
3 Push-in terminals
4 Grooves for DIN-rail mounting on short- or backside
5DIP-switches for system addressing
Figure 1-1 Add:io layout with status indications
1
2
3
4
4
5
Add:iomanual, Rev. A 5

Introduction
1.3 Dimen ion
[mm]
1.4 Mounting
The controllers are designed to be mounted on a DIN-rail. They can be mounted in two ways, either on their
bac side or stac ed on the short side with a high pac ing density as a result. When stac ed they fit smoothly
together thus requiring minimal space (see Figure 1-2)
Figure 1-2 Stacked units
102
136
140
46
6 Add:iomanual, Rev. A

Introduction
1.5 Communication
The EFX-port is the communication channel used between the Add:io and a master controller (e.g.
EXOclever). EFX is RS485-based communication.
1.6 Naming
All Add:io models are named the following way:
IO-ECzzyyy-X IO-EC = Add:io family naming
zz = Number of IOs
yyy = IO-type, e.g. UId
-X = EFX communication
Add:iomanual, Rev. A 7

Deployment
2 Deployment
2.1 In tallation recommendation
Follow these guidelines regarding shielded cables:
✓Only use shielded cables when the installation environment requires it.
✓No need for shielded cables between modules, if installed in close proximity
✓Connect shield to chassis ground at only one end of the cable.
For RS485 communication, the terminal Nis only required between systems not sharing the same ground
potential. When used, do not connect it to the cable screen. Note that it may be a single wire, but must be
drawn together.
When the cable length is less than 30 m in RS485, a terminator is not required in normal cases. The use of
terminators will decrease signal integrity thus try without first. When used, match the terminator value to
the characteristic impedance of the cable.
NNoottee!! Do not mix and u e one GND for everal input .
The technical earth terminal in the IO module power connector i not intended a a connection for
cable creen .
When connecting and measuring an external transmitter in an UI port this is done between terminals UIx
and GNDx (where x is the channel number between 1…16). Note that the intention is to use the
corresponding GND for the connected UI, especially when measuring sensitive signals or using DI pulse
(fast) mode.
Wiring examples can be found under each specific Add:io model in the following chapters.
2.2 General tatu indicator
The Add:io has a general status indicator mounted at the middle right front side, see Figure 1-1, which can be
inspected both when the unit is mounted on its bac and side. This indicator changes colour depending on its
actual status as shown in Table 2-1.
Table 2-1 Status indication at the front
LED status Controller status
Green, solid Power on and communication is established
Red, solid Battery problem
Yellow, blink 2.5 Hz Identification (wink)
Orange, blink 1 Hz IO-board is not in contact with CPU-board (via EFX)
The status indications that are present on the side, see Figure 1-1, are only active when the universal inputs or
outputs are configured as DI and DO. The indicator colours are shown in Table 2-2.
Table 2-2 Status indications on the side
UI configuration LED colour IO status
DI Green ON
DO Yellow ON
8 Add:iomanual, Rev. A

Deployment
2.3 Sy tem addre ing
The module has to be given an address between 0-255 in order to be able to communicate with it in a
system. The address is set with the 8-bit DIP-switch mar ed with Module Address on the Add:io unit. The
least significant bit (LSB) is mar ed Bit 1 and the most significant bit (MSB) is mar ed Bit 8.
A switch is activated by setting it to 1. In Figure 2-1 the address is set to 3.
Figure 2-1 DIP-switches for system addressing
Bit 1
7 6 5 4 3 2
0
I
Bit 8
Add:iomanual, Rev. A 9

Model IO-EC16UIc-X
3 Model IO-EC16UIc-X
3.1 Terminal
Terminal Label Notes
1 G+ Supply voltage
2 G0- Supply voltage, system ground (0 V)
3 Technical earth (EMI), connect to earth rail
10 N Communication port: port earth
11 A Communication port: inverted (-) data signal line
12 B Communication port: non-inverted (+) data signal line
20 GND1 Universal ground channel 1
21 UI1 Universal input channel 1
22 GND2 Universal ground channel 2
23 UI2 Universal input channel 2
24 GND3 Universal ground channel 3
25 UI3 Universal input channel 3
26 GND4 Universal ground channel 4
27 UI4 Universal input channel 4
28 GND5 Universal ground channel 5
29 UI5 Universal input channel 5
30 GND6 Universal ground channel 6
Bit 8
Bit 1
10 Add:iomanual, Rev. A

Model IO-EC16UIc-X
Terminal Label Notes
31 UI6 Universal input channel 6
32 GND7 Universal ground channel 7
33 UI7 Universal input channel 7
34 GND8 Universal ground channel 8
35 UI8 Universal input channel 8
36 GND9 Universal ground channel 9
37 UI9 Universal input channel 9
38 GND10 Universal ground channel 10
39 UI10 Universal input channel 10
40 GND11 Universal ground channel 11
41 UI11 Universal input channel 11
42 GND12 Universal ground channel 12
43 UI12 Universal input channel 12
44 GND13 Universal ground channel 13
45 UI13 Universal input channel 13
46 GND14 Universal ground channel 14
47 UI14 Universal input channel 14
48 GND15 Universal ground channel 15
49 UI15 Universal input channel 15
50 GND16 Universal ground channel 16
51 UI16 Universal input channel 16
Bit1…Bit8 Bit1 = LSB
Bit8 = MSB
The module address is set with 8 DIP-switches
Add:iomanual, Rev. A 11

Model IO-EC16UId-X
4 Model IO-EC16UId-X
4.1 Terminal
Terminal Label Notes
1 G+ Supply voltage
2 G0- Supply voltage, system ground (0 V)
3 Technical earth (EMI), connect to earth rail
10 N Communication port: port earth
11 A Communication port: inverted (-) data signal line
12 B Communication port: non-inverted (+) data signal line
20 GND1 Universal ground channel 1
21 UI1 Universal input channel 1
22 GND2 Universal ground channel 2
23 UI2 Universal input channel 2
24 GND3 Universal ground channel 3
25 UI3 Universal input channel 3
26 GND4 Universal ground channel 4
27 UI4 Universal input channel 4
28 GND5 Universal ground channel 5
29 UI5 Universal input channel 5
30 GND6 Universal ground channel 6
Bit 8
Bit 1
Add:iomanual, Rev. A 13

Model IO-EC16UId-X
Terminal Label Notes
31 UI6 Universal input channel 6
32 GND7 Universal ground channel 7
33 UI7 Universal input channel 7
34 GND8 Universal ground channel 8
35 UI8 Universal input channel 8
36 GND9 Universal ground channel 9
37 UI9 Universal input channel 9
38 GND10 Universal ground channel 10
39 UI10 Universal input channel 10
40 GND11 Universal ground channel 11
41 UI11 Universal input channel 11
42 GND12 Universal ground channel 12
43 UI12 Universal input channel 12
44 GND13 Universal ground channel 13
45 UI13 Universal input channel 13
46 GND14 Universal ground channel 14
47 UI14 Universal Input channel 14
48 GND15 Universal ground channel 15
49 UI15 Universal Input channel 15
50 GND16 Universal ground channel 16
51 UI16 Universal Input channel 16
Bit1…Bit8 Bit1 = LSB
Bit8 = MSB
The module address is set with 8 DIP-switches
14 Add:iomanual, Rev. A

Model IO-EC16UOb-X
5 Model IO-EC16UOb-X
5.1 Terminal
Terminal Label Notes
1 G+ Supply voltage
2 G0- Supply voltage, system ground (0 V)
3 Technical earth (EMI), connect to earth rail
10 N Communication port: port earth
11 A Communication port: inverted (-) data signal line
12 B Communication port: non-inverted (+) data signal line
20 AGND Analog ground
21 UO1 Universal output channel 1
22 UO2 Universal output channel 2
23 GDO Fused power for digital output
24 AGND Analog ground
25 UO3 Universal output channel 3
26 UO4 Universal output channel 4
27 GDO Fused power for digital output
28 AGND Analog ground
29 UO5 Universal output channel 5
30 UO6 Universal output channel 6
Bit 8
Bit 1
16 Add:iomanual, Rev. A

Model IO-EC16UOb-X
Terminal Label Notes
31 GDO Fused power for digital output
32 AGND Analog ground
33 UO7 Universal output channel 7
34 UO8 Universal output channel 8
35 GDO Fused power for digital output
36 AGND Analog ground
37 UO9 Universal output channel 9
38 UO10 Universal output channel 10
39 GDO Fused power for digital output
40 AGND Analog ground
41 UO11 Universal output channel 11
42 UO12 Universal output channel 12
43 GDO Fused power for digital output
44 AGND Analog ground
45 UO13 Universal output channel 13
46 UO14 Universal output channel 14
47 GDO Fused power for digital output
48 AGND Analog ground
49 UO15 Universal output channel 15
50 UO16 Universal output channel 16
51 GDO Fused power for digital output
Bit1…Bit8 Bit1 = LSB
Bit8 = MSB
The module address is set with 8 DIP-switches
Add:iomanual, Rev. A 17

Technical data
Appendix A Technical data
A.1 General data
Supply voltage 24 V AC/DC (18…26 V AC / 22…30 V DC)
Power consumption, nominal IO-EC16UOb-X: 7.8 VA / 3.5 W
IO-…UIc and …UId: 4.5 VA / 1.8 W
Protection class IP20
Ambient humidity Max. 95 % RH
Ambient temp. (working) 0…55 °C
Ambient temp., electronics
(working)
0…55 °C
Storage temperature -20…+70 °C
Mounting DIN-rail
Number of modules 8
Inputs/Outputs 16 per Add:io
Display No
Indication type LED for communication information
Dimensions, external (WxHxD) 140 x 136 x 46 mm
Weight (incl. packaging) 0.30 kg
A.2 Serial port data
Port type RS485
Default protocol EFX
Supported protocols EFX slave
Port isolation Yes
Communication speed 115200 bps
Cable length max 200 m
Cable connection Push-in connectors
A.3 Material
Material, housing Polycarbonate (PC)
Add:iomanual, Rev. A 19
Other manuals for ADD:IO
1
This manual suits for next models
3
Table of contents
Other Regin I/O System manuals
Popular I/O System manuals by other brands

National Instruments
National Instruments USB-9421 USER GUIDE AND SPECIFICATIONS

suprema
suprema Lift I/O installation guide

National Instruments
National Instruments FlexRIO NI 6581B Getting started guide

iSMA
iSMA iSMA-B-MINI Series user manual

MG
MG R7F4HEIP-DA16A instruction manual

Meilhaus Electronic
Meilhaus Electronic ME-5100 Series manual