MG R7F4HEIP-DA16A User manual

EM-8005-A Rev.1 P. 1 / 7
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
EtherNet/IP I/O MODULE
(NPN discrete input, 16 points, tension clamp terminal block)
MODEL
R7F4HEIP-DA16A
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
Discrete input module.........................................................(1)
DIN rail mounter slider......................................................(2)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
■EDS FILE
EDS files are downloadable at our web site.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 70mA
■GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
• Before you remove the terminal block or mount it, make
sure to turn off the power supply and input signal for
safety.
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• Observe at the minimum of 10 mm left and right the
units for heat dissipation when mounting vertically.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
• Be sure to close the terminal cover for safety.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.

R7F4HEIP-DA16A
EM-8005-A Rev.1 P. 2 / 7
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
COMPONENT IDENTIFICATION
IP Address Setting Rotary SW
RJ-45 Modular Jack
Status Indicator LED
PC Congurator Jack
Discrete Input Status Indicator LED
Sensor Exc. / Input ConnectorsPower Supply Connector
■STATUS INDICATOR LED
ID S TAT U S COLOR FUNCTION
PWR ON Green The internal power is supplied
normally.
MS ON Green Operating in a normal condition
Blinking Red Duplicated IP address,
Internal data error
NS ON Green Link on-line and connections in
the established state
Blinking Link on-line but no connections
in the established state
ON Red Duplicated IP address
Blinking Communication timeout
LNK1 ON Green LNK1 is established
LNK2 ON Green LNK2 is established
■DISCRETE INPUT STATUS INDICATOR LED
LED green indicators shows the signal status.
ON : LED ON
OFF : LED OFF
■IP ADDRESS
Set the host address (2-digit hexadecimal number) in the
IP address using rotary switches SA1 and SA2 for the first
digit and the second digit, respectively.
When using the host address in the IP address set on the
PC configurator software (model: R7CFG), set the switches
to ‘00H’.
When the network address, Subnet Mask, and Default
Gateway need to be changed, do so on R7CFG.
(Setting range: 00H – FFH)
(Factory setting: 00H)
IP Address Host Address MSD (×1)
IP Address Host Address LSD (×10)
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
■POWER SUPPLY TERMINAL ASSIGNMENT
12345
1. FE
2. NC
3. NC
4. +24V
5. 0V
Functional Earth
—
—
Power Input (24V DC)
Power Input (0V)
Applicable connector: TFMC1,5 / 5–STF–3,5(Phoenix Contact)
(included in the package)
Applicable wire size: 0.2 − 1.5 mm
2; stripped length 10 mm
Recommended solderless terminal
• AI0,25-10YE 0.25 mm
2(Phoenix Contact)
• AI0,34-10TQ 0.34 mm
2(Phoenix Contact)
• AI0,5-10WH 0.5 mm
2(Phoenix Contact)
• AI0,75-10GY 0.75 mm
2(Phoenix Contact)
• A1-10 1.0 mm
2(Phoenix Contact)
• A1,5-10 1.5 mm
2(Phoenix Contact)

R7F4HEIP-DA16A
EM-8005-A Rev.1 P. 3 / 7
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
■SENSOR EXC. AND INPUT TERMINAL ASSIGNMENTS
Applicab
le connector: DFMC0,5/13-ST-2,54 (Phoenix Contact) (included in the package)
Applicab
le wire size: 0.14
-
0.5mm2, stripped length 7mm
R
ecommended solderless terminal:
·
AI0,14-6GY 0.14mm2 (Phoenix Contact)
·
AI0,25-6YE 0.25mm2(Phoenix Contact)
·
A0,34-7 0.34mm2(Phoenix Contact)
12345678910111213 27 28 29 30 31 32 33 34 35 36 37 38 39
14 15 16 17 18 19 20 21 22 23 24 25 26 40 41 42 43 44 45 46 47 48 49 50 51 52
PIN No.ID FUNCTION PIN No.ID FUNCTION
1 +24V1 24V DC 27 +24V2 24V DC
2X0 Input 028X8 Input 8
3 +24V1 24V DC 29 +24V2 24V DC
4 GND1 0V 30 GND2 0V
5X2 Input 231X10 Input 10
6 +24V1 24V DC 32 +24V2 24V DC
7 GND1 0V 33 GND2 0V
8X4 Input 434X12 Input 12
9 +24V1 24V DC 35 +24V2 24V DC
10 GND1 0V 36 GND2 0V
11 X6 Input 637X14 Input 14
12 +24V1 24V DC 38 +24V2 24V DC
13 GND1 0V 39 GND2 0V
PIN No.ID FUNCTION PIN No.ID FUNCTION
14 GND1 0V 40 GND2 0V
15 X1 Input 141X9 Input 9
16 +24V1 24V DC 42 +24V2 24V DC
17 GND1 0V 43 GND2 0V
18 X3 Input 344X11 Input 11
19 +24V1 24V DC 45 +24V2 24V DC
20 GND1 0V 46 GND2 0V
21 X5 Input 547X13 Input 13
22 +24V1 24V DC 48 +24V2 24V DC
23 GND1 0V 49 GND2 0V
24 X7 Input 750X15 Input 15
25 +24V1 24V DC 51 +24V2 24V DC
26 GND1 0V 52 GND2 0V

R7F4HEIP-DA16A
EM-8005-A Rev.1 P. 4 / 7
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
MOUNTING INSTRUCTIONS
■DIN RAIL MOUNTING (PARALLEL)
• Mounting
1) Set the upper hook at the rear side of the unit on the DIN
rail.
2) Push the lower part in.
1
2
• Dismounting
1) Push down the DIN rail mounter slider with the tip of a
flat-blade screwdriver.
2) Pull the lower part of the unit.
3) Remove the upper hook of the unit from the DIN rail.
1
2
3
■SURFACE MOUNTING
1) Insert the two DIN rail mounter sliders until it clicks
once, as shown below.
11
2) Mount the unit with M4 screws referring to the External
Dimensions. (Torque: 1.4 N·m)
■DIN RAIL MOUNTING (RIGHT ANGLE)
• Mounting
1) Insert the longer DIN rail mounter slider until it clicks
twice, as shown below.
2) Set the upper hook at the rear side of the unit on the DIN
rail.
3) Push the lower part in.
3
2
• Dismounting
1) Push down the DIN rail mounter slider with the tip of a
flat-blade screwdriver.
2) Pull the lower part of the unit.
3) Remove the upper hook of the unit from the DIN rail.
3
2
1

R7F4HEIP-DA16A
EM-8005-A Rev.1 P. 5 / 7
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■EXTERNAL DIMENSIONS unit: mm [inch]
115[4.53]
50[1.97]5[.20]3[.12]
72[2.83]
55[2.17]
(4[.16])
123[4.84]
138[5.43]
DIN rail
(35mm wide)
2‑4.3dia.4deep.
■CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.
*1. The network cable can be connected to either one.
RJ-45 MODULAR JACK
RJ-45 MODULAR JACK
*1
EtherNet/IP
*1
EtherNet/IP
4
5
1
24V DC
FE
0V
25
26
24
14
29
30
28
51
52
50
27
40
1
3
4
2
+24V1
X7
GND1
+24V2
X8
GND2
+24V2
X15
GND2
+24V1
GND1
+24V2
GND2
+24V1
X0
GND1
Detecting Circuit
Detecting Circuit
Detecting Circuit
Detecting Circuit
INPUT X0
INPUT X7
INPUT X8
INPUT X15
EXC. SUPPLY (IN)
EXC. SUPPLY (IN)

R7F4HEIP-DA16A
EM-8005-A Rev.1 P. 6 / 7
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
MOUNTING REQUIREMENTS unit: mm [inch]
125 [4.92]
2-M4
PC CONFIGURATOR
The following parameter items can be configured with the PC configurator software (model: R7CFG).
Refer to the users manual of the software for detailed operations.
■CHANNEL BATCH SETTING
PARAMETER SETTING RANGE DEFAULT SETTING
Conversion rate 1 ms, 5 ms, 10 ms, 20 ms, 50 ms,
70 ms, 100 ms, 200 ms
10 ms
■ETHERNET SETTING
PARAMETER SETTING RANGE DEFAULT SETTING
IP Address 0.0.0.0 – 255.255.255.255 192.168.0.250
Subnet Mask 0.0.0.0 – 255.255.255.255 255.255.255.0
Default Gateway 0.0.0.0 – 255.255.255.255 192.168.0.1
Time Out 0.0 – 3276.7 (sec.) 3.0 (sec.)

R7F4HEIP-DA16A
EM-8005-A Rev.1 P. 7 / 7
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
CHECKING ETHERNET/IP CONNECTION
■IP ADDRESS
Set the host address in the IP address using the front rotary switches.
When using the host address in the IP address set on the PC configurator software (model:R7CFG), set the switches to ‘00H’.
When the network address, Subnet Mask, and Default Gateway need to be changed, do so on R7CFG.
■CHECK WIRING
Connect an Ethernet cable to the front RJ-45 modular jack.
To configure a DLR (Device Level Ring) network, perform wiring so as to form a ring topology.
The DLR network requires at least one node as a ring supervisor.
The customer shall prepare one or more ring supervisors separately as the R7F4HEIP unit does not function as one.
■CHECK LED
When wiring is correct, LNK1 or LNK2 is turned on.
■CHECK R7F4HEIP CONNECTION
Enter “ping command” on the Windows MS-DOS as follows:
C:¥WINDOWS>ping ***.***.***.***
(***.***.***.***: Enter IP address in decimal.)
ping ***.***.***.*** with 32 bytes of data:
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
Ping statistics for ***.***.***.***
Packets:Sent=4,Received=4,Lost=0(0% loss)
Replies in case of normal connection are as shown above. If the connection cannot be established normally due to e.g. wrong
IP address, other replies such as “time over” will be received.
■CHECK CONNECTION TO THE APPLICATION SOFTWARE
Check Point 1: LINK LED
LNK1 or LNK2 turns on when the module has established normal connections with PC, PLC, hub, and so on, regardless of
data sending/receiving status.
In the case that they are not on, check power supply to the hub.
Check Point 2: MS AND NS INDICATOR
When the module has transmitted/received data correctly to/from the application software, MS and NS indicators turn on in
green.
I/O DATA DESCRIPTION
015
0: OFF 1: ON
Input 0
Input 1
Input 2
Input 3
Input 15
Input 7
Input 8
■DISCRETE INPUT MODULE
Table of contents
Other MG I/O System manuals
Popular I/O System manuals by other brands

Allen-Bradley
Allen-Bradley Compact 5000 Series user manual

ICP DAS USA
ICP DAS USA P8R8-DIO quick start guide

Allen-Bradley
Allen-Bradley ArmorBlock-LP 1792-IB16LP installation instructions

Extron electronics
Extron electronics TLP VIM user guide

National Instruments
National Instruments NI PXI-665 Series CALIBRATION PROCEDURE

ETAS
ETAS ES930.1 user guide

Measurement Computing
Measurement Computing USB-3103 user guide

SeaLevel
SeaLevel SeaRAQ 6510 user manual

EverFocus
EverFocus External I/O Box quick start guide

WAGO
WAGO I/O-SYSTEM 750 manual

Advantech
Advantech B+B SmartWorx Zlinx ZZ24D-NA-SR quick start guide

Future Desion Controls
Future Desion Controls FDC-VR18 quick start guide