
LE8XIN Due to continuing product development, specications are subject to change without notice. © 2014 RenewAire LLC
138233_000 LE8XINMan_Feb14.indd Revised 02/2014 www.renewaire.com Page 9
FOR THE CONTROL CONTRACTOR
ON-BOARD 24VAC CLASS 2 POWER SUPPLY
This ERV is provided with a Class II 24VAC power supply system that
operates the unit’s contactor(s) for EV450 and HE1X. The ERV’s
24VAC Power Supply can also be used to power the externally
installed controls system: up to 8VA of power is available.
The unit’s power supply system includes isolation relay(s) so you
can use external controls whose contact ratings are as low as
50mA (1.2VA). Also, it is possible to operate the isolation relays
with 24VAC power from an external source (with proper wiring
connections).
A built-in circuit-breaker prevents damage to the transformer
and other low-voltage components in the event of a short-circuit
or overload. In extreme cases, the transformer itself is designed
to fail safely.
Danger of Electrical Shock when servicing an installed unit.
ALWAYS DISCONNECT POWER SOURCE BEFORE SERVICING!
More than one disconnect switch may be required.
Proper Wiring Size Selection and Wiring Installation are
the Responsibility of the Electrical Contractor.
1. Connect only to components intended for use with
24VAC power.
2. Do not interconnect the unit’s Class 2 power supply
with an external Class 2 power supply.
3. Do not undersize the low-voltage wires connected to
this device. Observe the wire length and gauge limits
indicated in this manual.
4. Do not overload this unit’s 24VAC power supply
system. Conrm that the power requirements of
devices you connect to this power supply system do
not exceed 8VA in total.
5. If an external source of 24VAC power is used to
control the unit, consult the wiring schematics and
connect the external power only to the specied
terminals in order to avoid damaging the unit or
external controls. Connect only CLASS II power to the
control terminals of this unit.
6. Unit is not equipped to receive analog signals (such
as 1-10vdc or 4-20mA).
7. Unit is not equipped to communicate directly with
Building Management Systems (such as BACNET,
LONWORKS, etc.). However, the unit can be controlled
by powered or nonpowered contacts operated by any
kind of control system.
TransformerSpecications
• Nominal Output Voltage under load: 24VAC
• Typical Output Voltage at no load: 29-31V
• Minimum contact rating for connected control device: (50mA (1.2VA)
• Circuit Breaker Trip Point: 3A
Limits of Class 2 Power Output
If limits on wire gauge and length are observed, you may connect
control devices that draw up to 8VA to the blue and red wires.
More than one device can be connected as long as total steady
state load does not exceed 8VA.
This ERV is provided with a Class II 24VAC power supply system that
operates the unit’s contactor(s) for EV450 and HE1X. The ERV’s
24VAC Power Supply can also be used to power the externally
installed controls system: up to 8VA of power is available.
OBSERVE THESE LIMITS TO WIRE LENGTH AND GUAGE,
to ensure reliable operation of the control system.
Wire Gauge #22 #20 #18 #16 #14 #12
Circuit Length (ft) 100’ 150’ 250’ 400’ 700’ 1000’
“Circuit Length” is the distance of the wire route from the ERV to the Control Device.
How to Reset the 24VAC Circuit Breaker
If the transformer is subjected to an excessive load or a short
circuit, the circuit breaker will trip to prevent the failure of the
transformer. When it trips the circuit breaker’s button pops up.
Shut off the primary-side power to the unit, and remove the
excessive load or the short. The circuit breaker can be reset
about fteen seconds after it trips by pressing in the button.
UNITS WITH 230VAC POWER SUPPLY:
Unit is shipped with transformer set for 208VAC power
supply. For 230VAC, move the black primary-side
lead from the transformer’s “208V” terminal to the
transformer’s “230V” terminal.
Do not move the black primary-side lead that is connected
to the transformer’s “COM” terminal.