
Q314 AND Q327A PILOT BURNERS
569-0519—06
Pilot Safety Control Power Unit Failure
1. Ensure pilot flame is properly adjusted.
2. Ensure power unit connections clean and tight.
3. If power unit still fails to hold in, use the W129A
Millivoltmeter to obtain the open and closed circuit
voltage generated by the thermocouple or genera-
tor.
4. Compare measured open and closed circuit voltage
values to Acceptable Range Charts in W129A Man-
ual.
5. If W129A Millivoltmeter or other meter is not avail-
able, replace thermocouple or thermopile. If this
does not correct the condition, replace power unit.
Thermocouple or Thermopile
Performance
Thermocouples and thermopiles require proper
temperature differential between the hot-junction (tip)
and coldjunction (base) to provide satisfactory operation
of gas controls. Thermocouples and thermopiles perform
less effectively when exposed to excessive cold-junction
or hotjunction temperatures.
Excessive cold-junction temperatures can be caused by
heat radiation from adjacent surfaces or high ambient air
temperatures. Excessive cold-junction temperatures can
be eliminated by shielding the pilot flame, see Fig. 10, or
constructing a baffle to direct secondary air over the pilot
burner base.
Excessive hot-junction temperatures can be eliminated
by proper pilot flame adjustment. To adjust pilot flame,
see Adjust Pilot Flame section.
Fig. 10. Proper shielding of pilot flame.
Pilot Turndown Test (30 mV safety control
systems)
The Pilot Turndown Test assures that the pilot flame
ignites the main burner within four seconds from the
time gas reaches the main burner. In this test, the pilot
flame is just sufficient enough to hold in the power unit
or just above the point of flame extinction (whichever
occurs at a higher pilot gas flow rate).
1. With the pilot and main burner operating, shut off
the main burner by either lowering the thermostat
temperature setting or turning the gas control knob
to the PILOT position.
NOTE: If using a W129A Millivoltmeter, turn the pilot
gas adjustment screw until the thermocouple
open circuit voltage is 2 mV. Omit steps 2,3, and
4 and proceed with step 5.
2. Turn the pilot gas adjustment screw clockwise
until the pilot begins to decrease in size. Then, turn
the pilot gas adjustment screw clockwise 1/4 turn
a time (waiting one minute between each turn to
allow the thermocouple to cool) until safety shutoff
power unit just drops, causing safety shutdown.
3. Turn pilot gas adjustment screw counterclockwise
slightly.
4. Relight pilot burner. The power unit should hold in.
5. Turn gas control knob to ON position and set ther-
mostat temperature setting above room tempera-
ture. Main burner should light within four seconds
without flame rollout. If not, check pilot mounting
and location instructions in Location section and
repeat Pilot Turndown Test.
6. Readjust pilot burner flame. See Adjust Pilot Flame
section.
Effective Ignition Test (750 mV Systems)
The Effective Ignition Test assures that the pilot flame
ignites the main burner within four seconds from the
time gas reaches the main burner. In this test, the pilot
flame is just sufficient to open the main gas valve.
1. Light the main burner according to the appliance
manufacturer’s instructions and allow to burn at
least five minutes.
2. Remove one thermostat lead (TH) at the gas con-
trol terminal.
3. Using the pilot gas adjustment screw, decrease the
pilot flame until it begins to pull away from the
thermopile. Allow thermopile to cool for one min-
ute.
4. Temporarily jumper the thermostat terminals (TH)
on the gas control.
5. If the main burner ignites, reduce the pilot flame by
turning the pilot adjustment screw 1/4 turn at a
time until the valve fails to pull in. Allow the ther-
mocouple to cool at least one minute between
each reduction in the pilot flame level.
6. Increase the pilot flame just enough to pull in the
gas control main valve.
7. Jumper the thermostat terminals. The main burner
should light within four seconds and without flame
roll-out. If it does not, check the Location and
Mounting instructions on page 1 and repeat steps
1 through 6.
8. If main burner still does not light, replace thermo-
pile and repeat steps 1 through 6.
9. Remove the jumper to shut off the main burner.
10. Readjust pilot burner flame. See Adjust Pilot Flame
section.
11. Reconnect the thermopile lead and ensure all con-
nections are correct and the system is functioning
properly.
TYPICAL
SHIELD
M1273A