Resol DeltaSol BS/4 User manual

*48005962*
48005962
Thank you for buying this RESOL product.
Please read this manual carefully to get the best performance from this unit.
Please keep this manual carefully.
DeltaSol®BS/4
www.resol.com
Manual
en
Solar controller
Manual for the
specialised craftsman
Installation
Operation
Functions and options
Troubleshooting
(Version 2)

2
en
© 20151016_48005962_DeltaSol_BS4_V2.monen
Safety advice
Please pay attention to the following safety advice in order to avoid danger and
damage to people and property.
Instructions
Attention must be paid to the valid local standards, regulations and directives!
Information about the product
Proper usage
The solar controller is designed for electronically controlling standard solar thermal
systems in compliance with the technical data specied in this manual.
Improper use excludes all liability claims.
CE Declaration of Conformity
The product complies with the relevant directives and is therefore
labelled with the CE mark. The Declaration of Conformity is available
upon request, please contact RESOL.
Note
Strong electromagnetic elds can impair the function of the controller.
ÎMake sure the controller as well as the system are not exposed to
strong electromagnetic elds.
Target group
These instructions are exclusively addressed to authorised skilled personnel.
Only qualied electricians should carry out electrical works.
Initial installation must be effected by the system owner or qualied personnel
named by the system owner.
Description of symbols
WARNING! Warnings are indicated with a warning triangle!
ÎThey contain information on how to avoid the dan-
ger described.
Signal words describe the danger that may occur, when it is not avoided.
• WARNING means that injury, possibly life-threatening injury, can occur.
• ATTENTION means that damage to the appliance can occur.
Note
Notes are indicated with an information symbol.
ÎArrows indicate instruction steps that should be carried out.
Disposal
• Dispose of the packaging in an environmentally sound manner.
• Dispose of old appliances in an environmentally sound manner. Upon request we
will take back your old appliances bought from us and guarantee an environmen-
tally sound disposal of the devices.
Subject to technical change. Errors excepted.

3
en
1 Overview ..............................................................................................4
2 Installation ...........................................................................................5
2.1 Mounting........................................................................................................................5
2.2 Electrical connection...................................................................................................6
2.3 Data communication / Bus..........................................................................................7
2.4 System overview ..........................................................................................................7
2.5 Systems...........................................................................................................................8
3 Operation and function ....................................................................16
3.1 Buttons.........................................................................................................................16
4 System-Monitoring-Display ..............................................................16
4.1 System screen.............................................................................................................17
4.2 Other indications.......................................................................................................17
5 Commissioning..................................................................................18
6 Channel overview ..............................................................................20
6.1 Display channels .........................................................................................................20
6.2 Adjustment channels.................................................................................................23
7 Troubleshooting.................................................................................31
8 Accessories ........................................................................................34
8.1 Sensors and measuring instruments......................................................................35
8.2 VBus®accessories......................................................................................................35
8.3 Interface adapters ......................................................................................................35
9 Index ...................................................................................................36
Contents
DeltaSol®BS/4 Solar controller
The RESOL controller for standard solar thermal systems.
The DeltaSol
®
BS controller provides a clear operating concept and is equipped
with the illuminated combined display with system-monitoring. Flashing symbols for
sensors, pumps and valves enable an immediate allocation of temperatures, tempera-
ture differences and active actuators.Thus, adjusting and monitoring the solar system
is quick and easy.

4
en
1 Overview
• 3 basic systems to choose from
• Drainback option
• Heat quantity measurement
• Tube collector function, thermal disinfection function
• Commissioning menu
• Unit °F and °C selectable
• HE pump control via adapter
Technical data
Inputs: 4 Pt1000 temperature sensors
Outputs: 2 semiconductor relays
Switching capacity: 1 (1) A 240 V~ (semiconductor relay)
Total switching capacity: 2 A 240 V~
Power supply: 100 … 240 V~ (50 … 60 Hz)
Supply connection: type Y attachment
Standby: 0.74 W
Temperature controls class: I
Energy efciency contribution: 1 %
Mode of operation: type 1.C.Y action
Rated impulse voltage: 2.5 kV
Data interface: RESOL VBus®
VBus®current supply: 35 mA
Functions: function control, operating hours counter, tube collector function,
heat quantity measurement and pump speed control
Housing: plastic, PC-ABS and PMMA
Mounting: wall mounting, also suitable for mounting into patch panels
Indication / Display: System-Monitoring-Display for visualisation of systems,
16-segment and 7-segment display, 8 symbols for indication of system status and
operating control lamp
Operation: 3 buttons at the front of the housing
Protection type: IP 20/ DIN EN 60529
Protection class: II
Ambient temperature: 0 … 40 °C
Degree of pollution: 2
Dimensions: 172 x 110 x 49 mm
104 mm
4.1"
130 mm
5.1“
2.6"
66 mm
4.3"
110 mm
6.8"
172 mm
1.1"
28 mm
0.4" / 11 mm
1.9" / 49 mm
0.5" / 13 mm
6.1" / 155 mm
Upper fastening point
Lower fastening point

en
5
InstallationIndications, functions and optionsMessages Commissioning Operation and function
2 Installation
2.1 Mounting
WARNING! Electric shock!
Upon opening the housing, live parts are exposed!
ÎAlways disconnect the device from power supply
before opening the housing!
Note
Strong electromagnetic elds can impair the function of the con-
troller.
ÎMake sure the controller as well as the system are not exposed to
strong electromagnetic elds.
The unit must only be located in dry interior rooms.
The controller must additionally be supplied from a double pole switch with contact
gap of at least 3 mm.
Please pay attention to separate routing of sensor cables and mains cables.
In order to mount the device to the wall, carry out the following steps:
ÎUnscrew the crosshead screw from the cover and remove it along with the
cover from the housing.
ÎMark the upper fastening point on the wall. Drill and fasten the enclosed wall
plug and screw leaving the head protruding.
ÎHang the housing from the upper fastening point and mark the lower fastening
point (centres 130 mm).
ÎInsert lower wall plug.
ÎFasten the housing to the wall with the lower fastening screw and tighten.
ÎCarry out the electrical wiring in accordance with the terminal allocation (see
page 6).
ÎPut the cover on the housing.
ÎAttach with the fastening screw.
display
button
T4A fuse
cable glands and
strain relief
cover

en
6
Installation Indications, functions and options MessagesCommissioningOperation and function
2.2 Electrical connection
WARNING! Electric shock!
Upon opening the housing, live parts are exposed!
ÎAlways disconnect the device from power supply
before opening the housing!
ATTENTION! ESD damage!
Electrostatic discharge can lead to damage to electronic com-
ponents!
ÎTake care to discharge properly before touching the
inside of the device!
Note
Connecting the device to the power supply must always be the last step
of the installation!
Note
It must be possible to disconnect the device from the mains at any time.
ÎInstall the mains plug such that it is accessible at any time.
ÎIf this is not possible, install a switch that can be accessed.
Do not use the device if it is visibly damaged!
The power supply of the device must be 100 … 240 V~ (50 … 60 Hz). Attach exible
cables to the housing with the enclosed strain relief and the corresponding screws.
The controller is equipped with 2 semiconductor relays to which a load such as a
pump, a valve, etc. can be connected:
• Relay 1 • Relay 2
18 = Conductor R1 16 = Conductor R2
17 = Neutral conductor N 15 = Neutral conductor N
13 = Grounding terminal ⌯14 = Grounding terminal ⌯
Note
The pump speed must be set to 100% when auxiliary relays or valves are
connected.
The mains connection is at the following terminals:
19 = Neutral conductor N
20 = Conductor L
12 = Grounding terminal ⌯
VBus®
DE-45527 Hattingen
DeltaSol BS/4 V2
12
S1 S2 S3
3456
LNR1NR2N
201918171615
S4
78 141312
1 (1)A100 ... 240V~
1 (1)A100 ... 240V~
R1
R2
T4A
VBus
910
CU 72091163 01
100 ... 240V~
50-60 Hz
Temp. Sensor Pt1000
IP 20
Made in Germany
mains terminals
fuse
load terminalssensor terminals grounding
terminals
Connect the temperature sensors (S1 to S4) to the corresponding terminals
with either polarity:
1 / 2 = Sensor 1 (e. g. collector sensor)
3 / 4 = Sensor 2 (e. g. store sensor)
5 / 6 = Sensor 3 (e. g. store sensor top)
7 / 8 = Sensor 4 (e. g. return sensor)

en
7
InstallationIndications, functions and optionsMessages Commissioning Operation and function
2.3 Data communication / Bus
The controller is equipped with the RESOL VBus®for data transfer and energy
supply to external modules. The connection is to be carried out at the terminals
marked VBus (any polarity).
One or more RESOL VBus®modules can be connected via this data bus, such as:
• RESOL DL2 Datalogger
• RESOL DL3 Datalogger
• VBus®/ PWM interface adapter
Furthermore, the controller can be connected to a PC or integrated into a net-
work via the RESOL VBus®/ USB or VBus®/ LAN interface adapter (not included).
Different solutions for visualisation and remote parameterisation are available on
the RESOL website www.resol.com.
Note
More accessories on page 34.
2.4 System overview
1
Standard solar system (page 8)
2
Solar system with afterheating (page 10)
3
Standard solar system with heat dump
(page 14)

en
8
Installation Indications, functions and options MessagesCommissioningOperation and function
2.5 Systems
Arrangement 1:
The controller calculates the temperature difference between collector sensor S1
and store sensor S2. If the difference is larger than or identical to the adjusted
switch-on temperature difference (DT O), the solar pump will be activated by the
relay, and the store will be loaded until the switch-off temperature difference (DTF)
or the maximum store temperature (S MX) is reached.
Sensors S3 and S4 can optionally be connected for measurement purposes. S3 can
optionally be used as the reference sensor for the store emergency shutdown op-
tion (OSEM).
If heat quantity measurement (OHQM) is activated, S4 is to be used as the return
sensor.
If the drainback option (ODB) is activated, relay 2 can be used for activating a booster
pump. For this purpose, the booster function (OBST) has to be activated.
Mains
3322
S1
S2
S4 / TR
R1
S3
Example Drainback
system
(with booster pump)
S1
S3
S2
S4/TR
R1 R2

en
9
InstallationIndications, functions and optionsMessages Commissioning Operation and function
Display channels
Channel Description Connection
terminal Page
INIT x* ODB initialisation active - 20
FLL x* ODB lling time active - 20
STAB x* ODB stabilisation in progress - 20
COL x Temperature collector S1 20
TST x Temperature store S2 20
S3 x Temperature sensor 3 S3 21
S4 x Temperature sensor 4 S4 21
TR x* Temperature return sensor S4 21
n % x Speed R1 R1 21
hP x Operating hours R1 R1 22
hP1 x* Operating hours R1 (if OBST is activated) R1 22
hP2 x* Operating hours R2 (if OBST is activated) R2 22
kWh x* Heat quantity in kWh - 21
MWh x* Heat quantity in MWh - 21
TIME x Time - 22
Adjustment channels
Channel Description Factory setting Page
Arr x System 1 22
DT O x Switch-on temperature difference 6.0 K [12.0 °Ra] 23
DT F x Switch-off temperature difference 4.0 K [8.0 °Ra] 23
DT S x Set temperature difference 10.0 K [20.0 °Ra] 23
RIS x Rise R1 2 K [4 °Ra] 24
nMN x Minimum speed 30 % 24
S MX x Maximum store temperature 60 °C [140 °F] 24
OSEM xStore emergency shutdown option OFF 24
EM x Collector emergency temperature 130 °C [270 °F] 25
Collector emergency temperature if ODB is activated: 95 °C [200 °F] 25
OCC x Collector cooling option OFF 25
CMX x* Maximum collector temperature 110 °C [230 °F] 25
OSYC x System cooling option OFF 25
DTCO x* Switch-on temperature difference cooling 20.0 K [40.0 °Ra] 25
DTCF x* Switch-off temperature difference cooling 15.0 K [30.0 °Ra] 25
OSTC x Store cooling option OFF 25
OHOL x* Holiday cooling option OFF 25
THOL x* Holiday cooling temperature 40 °C [110 °F] 25
OCN x Collector minimum limitation option OFF 26
Adjustment channels
Channel Description Factory setting Page
CMN x* Minimum collector temperature 10 °C [50 °F] 26
OCF x Antifreeze option OFF 26
CFR x* Antifreeze temperature 4.0 °C [40.0 °F] 26
OTC x Tube collector option OFF 27
TCST x* OTC starting time 07:00 27
TCEN x* OTC ending time 19:00 27
TCRU x* OTC runtime 30 s 27
TCIN x* OTC standstill interval 30 min 27
OHQM x Heat quantity measurement option OFF 28
FMAX x* Maximum ow rate 6.0 l 28
MEDT x* Antifreeze type 1 28
MED% x* Antifreeze concentration
(only if MEDT = propylene or ethylene glycol)
45 % 28
ODB x Drainback option OFF 28
tDTO x* ODB switch-on condition - time period 60 s 29
tFLL x* ODB lling time 5.0 min 29
tSTB x* ODB stabilisation time 2.0 min 29
OBST s* Option booster function OFF 29
MAN1 x Manual mode R1 Auto 29
MAN2 x Manual mode R2 Auto 29
ADA1 xHE pump control OFF 29
LANG x Language dE 29
UNIT x Temperature unit °C 29
RESE x Reset - back to factory settings 30
######## Version number
Legend:
Symbol Description
x Channel is available
x* Channel is available, if the corresponding option is activated.

en
10
Installation Indications, functions and options MessagesCommissioningOperation and function
Arrangement 2:
The controller calculates the temperature difference between collector sensor S1
and store sensor S2. If the difference is larger than or identical to the adjusted
switch-on temperature difference (DTO), the solar pump will be activated by relay
1, and the store will be loaded until the switch-off temperature difference (DTF) or
the maximum store temperature (S MX) is reached.
Sensor S3 is used for a thermostat function which operates relay 2 for afterheat-
ing or heat dump purposes when the adjusted thermostat switch-on temperature
(AH O) is reached.This function can optionally be combined with up to three ad-
justable time frames.
S3 can optionally be used as the reference sensor for the thermal disinfection func-
tion (OTD).
Sensor S4 can optionally be connected for measurement purposes. If heat quantity
measurement (OHQM) is activated, S4 is to be used as the return sensor.
Mains
3
3 32 22
S1
S2
S4 / TR
R1
S3

en
11
InstallationIndications, functions and optionsMessages Commissioning Operation and function
Display channels
Channel Description Connection
terminal Page
INIT x* ODB initialisation active - 20
FLL x* ODB lling time active - 20
STAB x* ODB stabilisation in progress - 20
COL x Temperature collector S1 20
TSTB x Temperature store 1 base S2 20
TSTT x Temperature store 1 top S3 20
TDIS s* Thermal disinfection temperature (thermal disinfection) S3 20
S4 x Temperature sensor 4 S4 21
TR x* Temperature return sensor S4 21
n1 % x Speed R1 R1 21
h P1 x Operating hours R1 R1 22
h P2 x Operating hours R2 R2 22
kWh x* Heat quantity in kWh - 21
MWh x* Heat quantity in MWh - 21
CDIS s* Countdown of monitoring period (thermal disinfection) - 21
SDIS s* Display of starting time - 22
DDIS s* Heating period display - 22
TIME x Time - 22
Adjustment channels
Channel Description Factory setting Page
Arr x System 2 22
DT O x Switch-on temperature difference 6.0 K [12.0 °Ra] 23
DT F x Switch-off temperature difference 4.0 K [8.0 °Ra] 23
DT S x Set temperature difference 10.0 K [20.0 °Ra] 23
RIS x Rise R1 2 K [4 °Ra] 24
n1MN x Minimum speed R1 30 % 24
S MX x Maximum store temperature 60 °C [140 °F] 24
OSEM xStore emergency shutdown option OFF 24
EM x Collector emergency temperature 130 °C [270 °F] 25
Collector emergency temperature if ODB is activated: 95 °C [200 °F] 25
OCC x Collector cooling option OFF 25
CMX x* Maximum collector temperature 110 °C [230 °F] 25
OSYC x System cooling option OFF 25
DTCO x* Switch-on temperature difference cooling 20.0 K [40.0 °Ra] 25
DTCF x* Switch-off temperature difference cooling 15.0 K [30.0 °Ra] 25
OSTC x Store cooling option OFF 25
OHOL x* Holiday cooling option OFF 25
THOL x* Holiday cooling temperature 40 °C [110 °F] 25
OCN x Collector minimum limitation option OFF 26
Adjustment channels
Channel Description Factory setting Page
CMN x* Minimum collector temperature 10 °C [50 °F] 26
OCF x Antifreeze option OFF 26
CFR x* Antifreeze temperature 4.0 °C [40.0 °F] 26
OTC x Tube collector option OFF 27
TCST x* OTC starting time 07:00 27
TCEN x* OTC ending time 19:00 27
TCRU x* OTC runtime 30 s 27
TCIN x* OTC standstill interval 30 min 27
OHQM x Heat quantity measurement option OFF 28
FMAX x* Maximum ow rate 6.0 l 28
MEDT x* Antifreeze type 1 28
MED% x* Antifreeze concentration 45 % 28
AH O s Switch-on temperature for thermostat 1 40 °C [110 °F] 12
AH F s Switch-off temperature for thermostat 1 45 °C [120 °F] 12
t1 O s Thermostat switch-on time 1 00:00 12
t1 F s Thermostat switch-off time 1 00:00 12
t2 O s Thermostat switch-on time 2 00:00 12
t2 F s Thermostat switch-off time 2 00:00 12
t3 O s Thermostat switch-on time 3 00:00 12
t3 F s Thermostat switch-off time 3 00:00 12
ODB x Drainback option OFF 28
tDTO x* ODB switch-on condition - time period 60 s 29
tFLL x* ODB lling time 5.0 min 29
tSTB x* ODB stabilisation time 2.0 min 29
OTD s Thermal disinfection option OFF 13
PDIS s* Monitoring period 01:00 13
DDIS s* Heating period 01:00 13
TDIS s* Disinfection temperature 60 °C [140 °F] 13
SDIS s* Starting time 00:00 13
MAN1 x Manual mode R1 Auto 29
MAN2 x Manual mode R2 Auto 29
ADA1 xHE pump control OFF 29
LANG x Language dE 29
UNIT x Temperature unit °C 29
RESE x Reset - back to factory settings 29
######## Version number
Legend:
Symbol Description
x Channel is available
x* Channel is available, if the corresponding option is activated.

en
12
Installation Indications, functions and options MessagesCommissioningOperation and function
System-specic functions
The following adjustments are used for the specic functions in system 2. The chan-
nels described are not available in any other system.
Thermostat function
Afterheating
Use of surplus
energy
The thermostat function works independently from the solar operation and can be
used for using surplus energy or for afterheating.
• AH O < AH F
thermostat function for afterheating
• AH O > AH F
thermostat function for using surplus energy
The symbol ⓶will be shown on the display if the second relay output is activated.
Reference sensor for the thermostat function is S3.
AH O
Thermostat switch-on temperature
Adjustment range: 0.0 … 95.0 °C
[30.0 … 200.0 °F]
Factory setting: 40.0 °C [110.0°F]
AH F
Thermostat switch-off temperature
Adjustment range: 0.0 … 95.0 °C
[30.0 … 200.0 °F]
Factory setting: 45.0 °C [120.0°F]
t1 O, t2 O, t3 O
Thermostat switch-on time
Adjustment range: 00:00 … 23:45
Factory setting: 00:00
t1 F, t2 F, t3 F
Thermostat switch-off time
Adjustment range: 00:00 … 23:45
Factory setting: 00:00
In order to block the thermostat function for a certain period, there are 3 time
frames t1 … t3.
If the thermostat function is supposed to run from 06:00 a.m. to 09:00 a.m. only,
adjust t1 O to 06:00 a.m. and t1 F to 09:00 a.m.
If the switch-on and switch-off times of a time frame are set to an identical value,
the time frame will be inactive. If all time frames are set to 00:00, the thermostat
function is solely temperature dependent (factory setting).

en
13
InstallationIndications, functions and optionsMessages Commissioning Operation and function
Thermal disinfection of the upper DHW zone
OTD
Therm. disinfection function
Adjustment range: OFF / ON
Factory setting: OFF
PDIS
Monitoring period
Adjustment range:
0 … 30:0 … 24 h (dd:hh)
Factory setting: 01:00
DDIS
Disinfection period
Adjustment range:
0:00 … 23:59 (hh:mm)
Factory setting: 01:00
TDIS
Disinfection temperature
Adjustment range:
0 … 95 °C [30 … 200 °F]
Factory setting: 60 °C [140°F]
This function helps to contain the spread of Legionella in DHW stores by system-
atically activating the afterheating.
For thermal disinfection, the temperature at the reference sensor will be moni-
tored. Protection is ensured when, during the monitoring period, the disinfection
temperature is continuously exceeded for the entire disinfection period.
The monitoring period starts as soon as the temperature at the reference sensor
falls below the disinfection temperature. When the monitoring period ends, the
allocated reference relay activates the afterheating. The disinfection period starts,
if the temperature at the allocated sensor exceeds the disinfection temperature.
Thermal disinfection can only be completed when the disinfection temperature
is exceeded for the duration of the disinfection period without any interruption.
Starting time delay
SDIS
Starting time
Adjustment range: 0:00 … 24:00 (time)
Factory setting: 00:00
If the starting delay option is activated, a starting time for the thermal disinfection
with starting delay can be adjusted.The activation of the afterheating is then delayed
until that starting time after the monitoring period has ended.
If the monitoring period ends, for example, at 12:00 o'clock, and the starting time
has been set to 18:00, the reference relay will be energised with a delay of 6 hours
at 18:00 instead of 12:00 o'clock.
Note
If the thermal disinfection option is activated, the display channels TDIS,
CDIS,SDIS and DDIS.

en
14
Installation Indications, functions and options MessagesCommissioningOperation and function
Arrangement 3:
The controller calculates the temperature difference between collector sensor S1
and store sensor S2. If the difference is larger than or identical to the adjusted
switch-on temperature difference (DTO), the solar pump will be activated by relay
1, and the store will be loaded until the switch-off temperature difference (DTF) or
the maximum store temperature (S MX) is reached.
If the maximum collector temperature (CMX) is reached, the solar pump will be
activated by R1 and the 3-port valve by R2 in order to direct the surplus energy
to a heat dump. For safety reasons, excess heat dump will only take place as long
as the store temperature is below the non-adjustable shutdown temperature of
95 °C [200 °F].
Sensors S3 and S4 can optionally be connected for measurement purposes. S3 can
optionally be used as the reference sensor for the store emergency shutdown op-
tion (OSEM).
If heat quantity measurement (OHQM) is activated, S4 is to be used as the return
sensor.
Mains
33 32 22
S1
S2
S4 / TR
R1
S3
R2

en
15
InstallationIndications, functions and optionsMessages Commissioning Operation and function
Display channels
Channel Description Connection
terminal Page
COL x Temperature collector S1 20
TST x Temperature store S2 20
S3 x Temperature sensor 3 S3 21
S4 x Temperature sensor 4 S4 21
TR x* Temperature return sensor S4 21
n % x Speed relay R1 21
h P1 x Operating hours R1 R1 22
h P2 x Operating hours R2 R2 22
kWh x* Heat quantity in kWh - 21
MWh x* Heat quantity in MWh - 21
TIME x Time - 22
Adjustment channels
Channel Description Factory setting Page
Arr x System 3 23
DT O x Switch-on temperature difference 6.0 K [12.0 °Ra] 23
DT F x Switch-off temperature difference 4.0 K [8.0 °Ra] 23
DT S x Set temperature difference 10.0 K [20.0 °Ra] 23
RIS x Rise R1 2 K [4 °Ra] 24
nMN x Minimum speed 30 % 24
S MX x Maximum store temperature 60 °C [140 °F] 24
OSEM xStore emergency shutdown option OFF 24
EM x Collector emergency temperature 130 °C [270 °F] 25
CMX s Maximum collector temperature 110 °C [230 °F] 25
OCN x Collector minimum limitation option OFF 26
CMN x* Minimum collector temperature 10 °C [50 °F] 26
OCF x Antifreeze option OFF 27
CFR x* Antifreeze temperature 4.0 °C [40.0 °F] 27
OTC x Tube collector option OFF 27
TCST x* OTC starting time 07:00 27
TCEN x* OTC ending time 19:00 27
TCRU x* OTC runtime 30 s 27
TCIN x* OTC standstill interval 30 min 27
OHQM x Heat quantity measurement option OFF 28
FMAX x* Maximum ow rate 6.0 l 28
MEDT x* Antifreeze type 1 28
MED% x* Antifreeze concentration
(only if MEDT = propylene or ethylene glycol)
45 % 28
MAN1 x Manual mode R1 Auto 29
MAN2 x Manual mode R2 Auto 29
ADA1 xHE pump control OFF 30
LANG x Language dE 30
UNIT x Temperature unit °C 30
RESE x Reset - back to factory settings 30
######## Version number
Legend:
Symbol Description
x Channel is available
x* Channel is available, if the corresponding option is activated.

en
16
Installation Indications, functions and options MessagesCommissioningOperation and function
3 Operation and function
3.1 Buttons
2 backwards (-)
1 forwards (+)
3 Ⓢ(selection /
conrmation)
Operating control
LED
The controller is operated via the 3 push buttons below the display.
Button 1 (+) - Scrolling forwards, increasing adjustment values.
Button 2 (-) - Scrolling backwards, reducing adjustment values.
Button 3 (OK) -conrming / selecting.
During normal operation, display channels will be displayed.
ÎIn order to scroll between display channels, press buttons 1 and 2.
Access to adjustment channels:
ÎUse button 1 in order to scroll to the last display channel, then press and hold
down button 1 for approx. 2 s.
If an adjustment channel is shown on the screen, will be displayed on the
right-hand side next to the channel name.
ÎPress button 3 in order to select an adjustment channel.
starts ashing.
ÎAdjust the desired value with buttons 1 and 2.
ÎBriey press button 3.
permanently appears, the adjusted value has been saved.
4 System-Monitoring-Display
System-Monitoring-Display
The System-Monitoring-Display consists of 3 blocks: channel display, tool bar and
system screen.
Channel display
The channel display consists of 2 lines. The upper display line is an alphanumeric
16-segment display. In this line, mainly channel names and menu items are displayed.
In the lower 16-segment display, values are displayed.
Tool bar
The additional symbols in the tool bar indicate the current system state.

en
17
InstallationIndications, functions and optionsMessages Commissioning Operation and function
4.1 System screen
The system selected is indicated in the System-Monitoring-Display. It consists of
several system component symbols which are – depending on the current status of
the system – either ashing, permanently shown or not indicated.
Collector
with collector sensor
Temperature sensor
Store
with heat exchanger
Pump
3-port valve
Only the ow direction or
current switching position is
indicated.
Afterheating
with burner symbol
4.2 Other indications
System screen
• Pumps are ashing when the corresponding relay is switched on.
• Sensor symbols are ashing, if the corresponding sensor display channel is selected.
• Sensors are ashing quickly in the case of a sensor fault.
• Burner symbol is ashing if the afterheating is active.
Operating control LED
Green: Everything OK
Red / green ashing: Initialisation active
Red ashing: Manual mode
Sensor fault (sensor symbol is ashing quickly)
Permanently
shown
Flashing Status indications:
Relay 1 active
Relay 2 active
Maximum store temperature exceeded
+ Store emergency shutdown active
Collector emergency shutdown active
Collector cooling active
System cooling active
+ Store cooling active
Holiday cooling option activated
+ Holiday cooling active
Collector minimum limitation active
Antifreeze function activated
Antifreeze function active
+ Manual mode relay 1 ON
+ Manual mode relay 2 ON
Manual mode relay 1 /2 OFF
Sensor fault

en
18
Installation Indications, functions and options MessagesCommissioningOperation and function
5 Commissioning
2 backwards (-)
1 forwards (+)
3 (selection /
conrmation)
ÎConnect the device to the mains.
The controller runs an initialisation phase in which the operating control LED ashes
red / green.
When the controller is commissioned or when it is reset, it will run a commission-
ing menu. The commissioning menu leads the user through the most important
adjustment channels needed for operating the system.
Adjustment mode ashing
Operation
Changing a value ashing
Conrming a value not ashing
to the next
parameter
1
1
3
3
2
2
1. Language
ÎAdjust the desired menu language.
LANG
Language selection
Selection: dE, En, Fr
Factory setting: dE
2. Temperature unit
ÎAdjust the desired unit.
UNIT
Temperature unit
Selection: °F, °C
Factory setting: °C
3. Time
ÎAdjust the clock time.
First of all adjust the hours, then the minutes.
TIME
Real time clock
4. Arrangement
ÎAdjust the desired system.
For a detailed description of the systems to choose
from, see page 8.
Arr
System selection
Adjustment range: 1 … 3
Factory setting: 1
If the system selection is changed later on, any previ-
ous adjustments which have been made in the other
channels will be lost.Therefore, changing the system is
always followed by a security enquiry.
Commissioning

en
19
Messages InstallationIndications, functions and optionsMessages Commissioning Operation and function
Only con rm the security enquiry if you are
sure that you wish to change the system selec-
tion.
Security enquiry
ÎIn order to con rm the security enquiry, press
button 3.
5. Maximum store temperature
ÎAdjust the maximum store temperature.
S MX
Adjustment range: 4 … 95 °C [40 … 200 °F]
Factory setting: 60 °C [140 °F]
Note
The controller is also equipped with a
non-adjustable emergency shutdown, deacti-
vating the system if the store reaches 95 °C
[200 °F].
6. Minimum speed
ÎAdjust the minimum speed for the corresponding
pump.
nMN
Speed control
Adjustment range: 30 … 100 %
Factory setting: 30
Note
The pump speed must be set to 100% when
auxiliary relays or valves are connected.
Commissioning
Con rmation
Completing the commissioning menu.
After the last channel of the commissioning menu has
been adjusted and con rmed, the controller asks for
con rmation of the adjustments.
ÎIn order to con rm the adjustments made in the
commissioning menu, press button 3.
The controller is then ready for operation and nor-
mally the factory settings will give close to optimum
operation.
Note
The adjustments carried out during commis-
sioning can be changed anytime in the cor-
responding adjustment channel. Additional
functions and options can also be activated or
deactivated (see page 23).

en
20
Installation Indications, functions and options MessagesCommissioningOperation and function
Display of collector temperatures
COL
Collector temperature
Display range: -40 … +260 °C [-40 … +500 °F]
Indicates the collector temperature.
Display of store temperatures
TST,TSTB,TSTT,TDIS
Store temperatures
Display range: -40 … +260 °C [-40 … +500 °F]
Indicates the store temperatures.
• TST : Store temperature
• TSTB : Store temperature base
• TSTT : Store temperature top
• TDIS : Thermal disinfection temperature
(replaces TSTT if, during thermal disinfection, the heating period DDIS is active)
TSTB,TSTT and TDIS are only available if Arr = 2
6 Channel overview
6.1 Display channels
Note
The display and adjustment channels as well as the adjustment ranges de-
pend on the system selected, the functions and options as well as on the
system components connected to the controller.
Display of drainback time periods
Initialisation
INIT
ODB initialisation active
Indicates the time adjusted in tDTO, running backwards.
Filling time
FLL
ODB lling time active
Indicates the time adjusted in tFLL, running backwards.
Stabilisation
STAB
ODB stabilisation in progress
Indicates the time adjusted in tSTB, running backwards.
Other manuals for DeltaSol BS/4
1