Display channels
Channel Description Connection
terminal Page
INIT x* ODB initialisation active - 20
FLL x* ODB lling time active - 20
STAB x* ODB stabilisation in progress - 20
COL x Temperature collector S1 20
TST x Temperature store S2 20
S3 x Temperature sensor 3 S3 21
S4 x Temperature sensor 4 S4 21
TR x* Temperature return sensor S4 21
n % x Speed R1 R1 21
hP x Operating hours R1 R1 22
hP1 x* Operating hours R1 (if OBST is activated) R1 22
hP2 x* Operating hours R2 (if OBST is activated) R2 22
kWh x* Heat quantity in kWh - 21
MWh x* Heat quantity in MWh - 21
TIME x Time - 22
Adjustment channels
Channel Description Factory setting Page
Arr x System 1 22
DT O x Switch-on temperature difference 6.0 K [12.0 °Ra] 23
DT F x Switch-off temperature difference 4.0 K [8.0 °Ra] 23
DT S x Set temperature difference 10.0 K [20.0 °Ra] 23
RIS x Rise R1 2 K [4 °Ra] 24
nMN x Minimum speed 30 % 24
S MX x Maximum store temperature 60 °C [140 °F] 24
OSEM xStore emergency shutdown option OFF 24
EM x Collector emergency temperature 130 °C [270 °F] 25
Collector emergency temperature if ODB is activated: 95 °C [200 °F] 25
OCC x Collector cooling option OFF 25
CMX x* Maximum collector temperature 110 °C [230 °F] 25
OSYC x System cooling option OFF 25
DTCO x* Switch-on temperature difference cooling 20.0 K [40.0 °Ra] 25
DTCF x* Switch-off temperature difference cooling 15.0 K [30.0 °Ra] 25
OSTC x Store cooling option OFF 25
OHOL x* Holiday cooling option OFF 25
THOL x* Holiday cooling temperature 40 °C [110 °F] 25
OCN x Collector minimum limitation option OFF 26
Adjustment channels
Channel Description Factory setting Page
CMN x* Minimum collector temperature 10 °C [50 °F] 26
OCF x Antifreeze option OFF 26
CFR x* Antifreeze temperature 4.0 °C [40.0 °F] 26
OTC x Tube collector option OFF 27
TCST x* OTC starting time 07:00 27
TCEN x* OTC ending time 19:00 27
TCRU x* OTC runtime 30 s 27
TCIN x* OTC standstill interval 30 min 27
OHQM x Heat quantity measurement option OFF 28
FMAX x* Maximum ow rate 6.0 l 28
MEDT x* Antifreeze type 1 28
MED% x* Antifreeze concentration
(only if MEDT = propylene or ethylene glycol)
45 % 28
ODB x Drainback option OFF 28
tDTO x* ODB switch-on condition - time period 60 s 29
tFLL x* ODB lling time 5.0 min 29
tSTB x* ODB stabilisation time 2.0 min 29
OBST s* Option booster function OFF 29
MAN1 x Manual mode R1 Auto 29
MAN2 x Manual mode R2 Auto 29
ADA1 xHE pump control OFF 29
LANG x Language dE 29
UNIT x Temperature unit °C 29
RESE x Reset - back to factory settings 30
######## Version number
Legend:
Symbol Description
x Channel is available
x* Channel is available, if the corresponding option is activated.