
Installation Instructions — R15C
Installation
Verify the existing wall thickness1. e distance from the
condenser coil to the outdoor louver varies with sleeve depth,
unit(s) ship standard with several sets of baes. In addition, EMI
stocks an optional condenser-side air bae kit for chassis instal-
lation in deeper-than-standard wall sleeves. For fast, trouble-free
installation, know your wall sleeve depth when ordering.
Install the baes2. Remove sets of baes from the kit bag
supplied with unit. Install only one set of le and right side baes
on the condenser coil
by completing steps below
:
Choose the proper ing baes for your application by verifying•
selected baes come in contact with the outdoor louver.
Install Top bae•
Make sure the baes are directed inward toward the center of•
coil (see Figure 11).
Secure baes tightly into the existing holes of the condenser coil•
using the screws provided.
Contents of Install Kit
(1) Top Bae
(2) Size 1 left and right baes only
(2) Size 2 left and right baes
(2) Size 3 left and right baes
(2) Size 4 left and right baes
Install Thermostat Bulb and lter3.
Insert grommets into clips.•
Insert Sensing bulb into grommets.•
Insert ermostat Bulb assembly into middle section of indoor•
coil. (see gure 12)
Fasten lter using velcro strips.•
Install the foam tape4. Apply ”
x
”
open-cell foam strips
to both weather angles, this prevents outside air from entering
around the chassis to the room from the sides (see Figure 13).
Install 1" x 1" open cell foam to back of unit above condenser coil.
It is imperative to have a solid air seal between the wall sleeve and
the chassis. Failure to do so will result in air leakage from outdoor
to indoor causing system problems(example — coils eezing, short
cycling, and constant running of unit). If there is a need for more
foam than supplied in kit, consult the factory.
Contents of install kit
(3ft) 1"x 1" Open cell foam
(5ft) 1/2" x 1/2" Open cell foam
(6.6ft) 1" x 1/2" Open cell foam
Connecting the optional hydronic coil controls5. If the
hydronic heat option has been ordered, then the hydronic coil
will need to be eld installed on the new unit. Hydronic coils
are not factory installed and need to be ordered. e coil with
the old unit can be located in the subbase, under the chassis in a
special aachment, or above the chassis in a special aachment.
It is necessary to know where the coil is to be located and the
physical size of the coil so the new coil can be veried if ordered
for replacement. e new coil should be installed in the same
manner as the coil it is replacing.
Remove the 4-position connector assembly from kit bag supplied•
with unit (this will have 2 yellow wires aached).
Connect this 4-position connector to the 4-position connection•
located on the front of the unit.
Splice the yellow wires to the valve motor using 2-crimp pop-•
corns.
Connecting the accessory Aquastat6. If the accessory
Aquastat has been ordered then it will need to be eld installed.
Remove the black jumper wire located on the front of the unit•
(this is terminated with a 2-position connector).
Cut the jumper wire in the middle and splice the Aquastat to the•
jumper., using 2-crimp popcorns.
Place the connector back into original location. Refer to the wir-•
ing diagram on the unit for details.
Secure the chassis7. Ensure all seals are in the proper loca-
tions, the correct baesareaached to the condenser coil, and in
the proper orientation, then slide the unit into nal position and
tighten any tie down bolts or screws as necessary.
Hard-wired units8. If the unit is hard wired, follow the in-
structions on page15 to verify existing wiring and overcurrent
protection. Remove the line cord wires from the PTAC/PTHP
power entrance terminals. Route the power supply wiring through
a strain-relief bushing and connect leads to the power entrance
terminals. Secure the strain-relief clamp. (If wiring is through
conduit, insert the conduit through the control box knockout
and secure in place.) DO NOT turn on power until completing
instructions in "Final Inspection and Startup" on page 32.
DO NOT PLUG IN the line cord, if in used condition9. .Follow
instructions in "Final Inspection and Startup" on page 32.
Replacement Packaged Terminal Air-Conditioning / Heat Pum
Insta
ation, O
eration, an
Maintenance Manua
•
The Right Fit for Comfort 16 P/N 240008223, Rev. K [05/14/2012]