
SECTION THROUGH FASCIA
FASCIA BLANKING PIECE
3. Condensate pipework should slope downwards in the
directionofwaterflow withaminimumgradientof(1” per
10’). There must not be any uphill gradients other than
in the first 18” of pipework from the Cassette.
4. When multiple Cassettes are connected to a common
condensate drain, ensure the drain is large enough to
cope with the volume of condensate from several
Cassettes.Itisalsorecommendedtohave an airventin
thecondensate pipework to preventany air locks.
DUCT COLLARS: Branch duct and fresh air duct collars
can be attached to the Cassette chassis by following the
stepsbelow:
1.Refertotherelevant illustrationforyourCassette(pages
6 -7 in this IOM) to become familiarized with knock-out
holelocations.
2. The insulation is pre-cut to aid location and removal of
the relevant section. Rub hand across surface of
insulationto reveal exact location ofknock-out.
3. Remove the metal knockout from the chassis.
4. Attach the duct collar to the chassis using self tapping
screws.
NOTE:Branchductsareroundand5-6”indiameter.
Fresh Air ducts are square and 3” in diameter.
INSULATION: Refrigerant, chilled water and condensate
pipes should be insulated right up to the Cassette chassis.
Chilledwatervalvesmustalsobeinsulatedtopreventsweat-
ing.
ASSEMBLY: Once the services have been connected the
fourfasciamountingboltscanbeunscrewedapproximately
1”from the condensate tray support channels.
ThefasciacannowbeunpackedreadyforfittingtotheCas-
sette chassis. Ensure the black fir tree fasteners holding
thefasciapolystyrene are pushed in firmlyincase of transit
vibration. If a fascia aperture needs blanking off, then take
one of the polystyrene blanking pieces and push it into the
recess in the polystyrene fascia insulation. Fit by removing
the inlet grilles and filters, locating the four fascia mounting
bolts on the chassis through the four keyhole brackets on
the fascia and then sliding the fascia sideways until it locks
into position.
NOTE: Upto two non-adjacent sides can be blanked
off.
NOTE: On electro-mechanical units, the fascia must
beinstalledwiththeEMIlogo along the same edge of
the unit as the electrical panel. On units fitted with
microprocessorcontrols,orientthefasciawiththedis-
play panel along the same edge of the unit as the
electricalpanel.
Beforetighteningthefasciatotheunit,connectthetwohalves
of the vane motor’s plug and socket connection (where ap-
plicable).
Onmicroprocessorcontrolledunits, ensure that the display
panel cable is routed to the electrical panel and securely
fastenedtoits connectoronthemicroprocessor circuitboard.
(Refer to the unit’s electrical wiring schematic). Take care
to ensure that the connector is connected in the proper ori-
entation and that the wires are not routed such that they
maybecome trapped, cut, broken orchaffed.
Thefasciacannowbetighteneduptothe Cassette chassis
until a good seal is obtained between fascia and chassis.
NOTE: Do not over tighten the bolts. To do so may
cause damage to the fascia.
With filters in place, the inlet grilles can now be fitted to the
fascia to complete the installation.
ELECTRICAL DATA
(See Appendix 1 on page 18 for wiring charts and instruc-
tions.)
All power and interconnecting wiring between units should
becarriedouttoconform with local/nationalelectricalcodes.
A fused and dedicated electrical supply of the appropriate
phase,frequencyandvoltage shouldbeinstalledbythecus-
tomer.Itisalsorecommendedthatalocal disconnect switch
be connected within 3’ of the unit. In some areas this may
beacoderequirement.
EMIequipment in its standard form is designed for anelec-
tricalsupplyof208-230V,1Ph,60Hz.When connection to a
115V, 1Ph, 60Hz supply is necessary, a factory mounted
buck boost transformer will be fitted to the unit.
Thewiresshould be capable of carryingthe maximum load
currentundernon-faultconditionsatthestipulated voltages.
Avoid large voltage drops on cable runs, particularly in low
voltage wiring. The correct cable size must be used to en-
sure a voltage drop of less than 1 volt in the control wiring.
Once the refrigeration pipe work is complete, the electrical
supply can be connected by routing the cable through the
appropriatecasingholeandconnectingthesupplyandground
cables to the unit’s power terminals. On the medium and
large cabinets, it will be necessary to remove the insulated
condensate tray support rail, adjacent to the casing hole.