Rheem RXGW-BO1 User manual

INSTALLATION AND VENTING INSTRUCTIONS
RXGW-BO1
Chimney Adapter Kit For Upflow Only,
Category 1, Fan Assisted 80+ Furnaces
THESE INSTRUCTIONS MUST REMAIN WITH THE FURNACE AFTER INSTALLATION
Furnaces acceptable for use with RXGW-B01 Chimney Adapter are also identified by a label located
on the furnace top plate as shown below:
THIS APPLIANCE IS CSA
CERTIFIED FOR USE WITH
RXGW-BO1 CHIMNEY ADAPTER
WARNING
This vent kit must be installed by a qualified service technician exactly as specified
in these instructions and all applicable State and local codes. In the absence of
local codes, installations must conform to the latest edition of the National Fuel
Gas Code (ANSI Z233.1) or National Standard of Canada for natural gas and
propane installations (CAN/CGA B149.1 & .2). Failure to follow these instructions
may result in fire, explosion, or the production of carbon monoxide causing
structure damage, personal injury or loss of life.
WARNING
Do Not Use This Kit to Vent Category II, III, or IV Furnaces
Do Not Use This Kit on Standing Pilot Furnaces
92-101682-01-02
WARNING
This kit must be installed by a qualified service technician exactly as specified
in these instructions and all applicable State and local codes. In the absence of
local codes, installations must conform to the latest edition of the National Fuel
Gas Code (ANSI Z233.1). Failure to follow these instructions may result in
fire, explosion, or the production of carbon monoxide causing structure
damage, personal in ury or loss of life.

INTRODUCTION
This instruction manual covers the use of a Chimney adapter kit for installations having tile-lined
masonry chimneys. The chimney adapter will reduce the amount of condensation in the flue system and
prevent excessive and premature deterioration of the tile and brick mortar joints. This kit may only be
installed if the following requirements are met:
1. The 99% winter design temperature shall not be lower than 100F for exterior chimneys. (Refer to
Figure G-19 in the National Fuel Gas Code).
2. Chimney construction shall conform to the Standard for Chimneys, Fireplaces, Vents, and Solid
Fuel Burning Appliances (ANSI/NFPA 211).
3. The furnace must bear a factory applied label stating the Chimney Adapter kit number that may
be used.
4. An operational draft hood equipped water heater may be common vented with the furnace.
Additional draft hood equipped appliances may also be added to the venting configuration.
5. Type B double-wall metal vent must be used for all furnace and water heater vent connectors.
6. Furnace oversizing must not exceed 70% of the winter design heating load.
Refer to the National Fuel Gas Code (NFPA54) or B149.1 &.2 (Canada) for information on chimney
sizing information. The following “Table 1” has been extracted from NFPA54:
Table 1
Exterior Masonry Chimney Installations with Type B double wall vent connectors*
Minimum Internal Area of Chimney (Square Inches)
28 38 50 63 78113
Vent Height
(Feet) NAT+NAT NAT+NAT NAT+NAT NAT+NAT NAT+NAT NAT+NAT
6 71 103 143 188 246 NR
8 82 119 163 218 278 408
10 90 131 177 236 302 454
15 106 152 212 283 365 546
20 122 172 243 325 419 648
30 137 198 278 381 496 749
35 NRNR281 401 524 792
*NOTES: NR=Vent Configuration is NOT RECOMMENDED
Table 2
Furnce Input Rate
Maximum Lateral
B-Vent Connector
Length
50,000 Btu/hr 7.5
75,000 Btu/hr 7.5
100,000 Btu/hr 7.5
125,000 Btu/hr 9
150,000 Btu/hr 9
Refer to the National Fuel Gas Code (NFPA54) for information on chimney sizing information. The
following “Table 1” has been extracted fromNFPA54:

Table 3
Chimney Liner Nominal Size and Inside Area
Masonry Chimney Tile LinerFurnace Input
Rate Maximum
Chimney Height Double Wall
Pipe Vent
Diameter Max. Nominal
Liner Size Max. Inside
Diameter Max. Equivilent
Area
Btu/hr Feet Inches Inches x Inches Inches Square Inches
50,000 20 5 8x8 7.4 42.7
75,000 30 5 8x8 7.4 42.7
75,000 20 5 8x12 9.0 63.6
100,000 35 6 8x8 7.4 42.7
100,000 30 6 8x12 9.0 63.6
125,000 35 6 8x8 7.4 42.7
125,000 35 6 8x12 9.0 63.6
150,000 35 7 12x12 10.4 83.3
Note: Size for two-stage appliances based on minimum input-rate.
INSTALLATION
1. Disconnect electrical power to the furnace.
2. Turn off gas supply.
3. Remove knockout on furnace top panel.
4. Insert wiring leads through the knockout opening.
5. Install Chimney Vent Adapter on top of furnace flue collar.
6. Adjust Chimney Adapter so that cooling coil, if used, does not interfere.
7. Attach straight conduit connector to the knockout opening on furnace top-plate .
8. Remove one lead from rollout switch and use the female lead of the adapter to replace it.
9. Insert male lead of adapter wiring into disconnected rollout switch lead.
10. Use wire tie to route all wiring away from areas of excessive heat.
11. Complete the venting installation per NFGC guidelines.
12. Turn on gas supply.
13. Reconnect power supply.
RXGW-B01 WIRING DIAGRAM
(TYPICAL)
(MAIN LIMIT
CONTROL) CHIMNEY
ADAPTER
(RXGW-B01)
(ROLLOUT
CONTROL)
R R
LC
MRLC MRLC


TESTING
1. Check water heater and furnace draft hoods for spillage after 5 minute operation
2. Disconnect electrical power to the furnace
3. Remove B-vent connector from chimney adapter
4. Jumper pressure switch terminals to bypass switch and allow furnace to operate if
pressure switch opens.
5. Restore electrical power and adjust thermostat to call for heat.
6. Allow furnace to operate for a period of 2 minutes, then block chimney adapter outlet
100%. Furnace should shutoff within 3 minutes.
7. REMOVE JUMPER WIRE FROM PRESSURE SWITCH!!
8. Remove blockage and reconnect Type-B vent connector to chimney adapter
9. Wait 5 minutes, then manually reset chimney adapter temperature switch.
99% Winter Design Temperatures for the Contiguous United States
From the National Fuel Gas Code 223.1-112

CHIMNEY INSPECTION CHART
For additional requirements, refer to the National Fuel Gas CodeNFPA54/ANSI Z223.1 and
ANSI/NFPA 211 Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances in the USA, or
the Canadian Installation Codes CAN/CGA-B149.1 and .2 in Canada.
Yes
No
No
Yes
No Reline
Yes Repair
Yes No
No Yes
Yes
No
No
Yes
Crown
condition
Acceptable?
Repair
crown
Is clay tile liner in
Chimney properly
installed?
Is liner in
good
condition?
Repair existing liner
or reline chimney as
needed
Does cleanout contain
debris? Mortarm tile,
metal vent fuel oil
Remove all debris
Clay tile
misalignment, missing
sections gaps?
Is chimney serving a
second draft hood
equipped appliance?
Chimney may be
used with Rheem
Chimney Adapter
Line chimney with properly sized, listed flexible
metal liner or type B-vent as outlined in NFGC,
NSCNGPIC, or NFPA211 vent sizing tables and
liner or vent manufacturers Installation Instructions.
No
Yes
F r additi nal requirements, refer t the Nati nal Fuel Gas C de NFPA54/ANSI Z223.1 and
ANSI/NFPA 211 Chimneys, Fireplaces, Vents, and S lid Fuel Burning Appliances in the USA.


CM 0614
Table of contents