Richcomm NetmateLite User instructions

Richcomm System Technologies Co.,Ltd
Tel:+86 20 6685 4299
Fax: +86 20 8230 6916
www.richcomm.com.cn/e
2
Hello
Installation Requirement
The monitored UPS with RS232 communication port or internal slot;
The computer(best administrators computer) with Ethernet port
A complete network environment.
Note: Please read this user manual before installation.

Richcomm System Technologies Co.,Ltd
Tel:+86 20 6685 4299
Fax: +86 20 8230 6916
www.richcomm.com.cn/e
3
1. Ports Definition
NetmateLite/NetmateLite Mini/NetmateLite SE Available
①Ethernet Port: UTP 10/100M RJ45 Ethernet port.
②USB Port: For initial configuration;
③S1 (Green): Running indicator, flash is normal;
④S2 (Green): SNMP running indicator, flash is normal, flash frequency is determined by
SNMP inquire cycle;
⑤S3 (Red): Device status indicator (red), continuous on shows connected well with UPS and
have communication, flash shows device disconnected or communication failed;
⑥Default: Factory default switch;
⑦RS232 Port(External card): Connect with UPS;

Richcomm System Technologies Co.,Ltd
Tel:+86 20 6685 4299
Fax: +86 20 8230 6916
www.richcomm.com.cn/e
4
⑧Gold Finger: Insert in UPS internal slot;
NetmateLite Mini1/NetmateLite Mini2 Available
①Ethernet Port: UTP 10/100M RJ45 Ethernet port.
②PW (Red): Power status indicator, often light shows device power is connected, no light
means not connect power.
③S1 (Green): Running indicator, slow flash normal;
④S2 (Green): SNMP running indicator, flash normal, flash frequency is determined by
SNMP inquire cycle;
⑤S3 (Red): Device status indicator (red), continuous on shows connected well with UPS and
have communication, flash shows device disconnected or communication failed;
⑥4 Pin Serial Port: Connect with UPS;
⑦Gold Finger: Insert in UPS internal slot;

Richcomm System Technologies Co.,Ltd
Tel:+86 20 6685 4299
Fax: +86 20 8230 6916
www.richcomm.com.cn/e
6
2.2 Hardware Installation
External SNMP Cards
Procedure:
①Use DB9 pin cable connect external card with UPS by RS232 port
②Use T568B network cable connect to network
③Use power adapter connect to power supply(12V DC)
Internal SNMP Cards
Procedure:
①Insert internal SNMP card to solt
②Use T568B network cable connect to network
To Network
To Power

Richcomm System Technologies Co.,Ltd
Tel:+86 20 6685 4299
Fax: +86 20 8230 6916
www.richcomm.com.cn/e
7
2.3 Set Network Segment
For initial configuration, we should set a same network segment before login in web interface, the
default IP address of SNMP cards are: 192.168.0.100, so network segment should be set like
192.168.0.XXX

Richcomm System Technologies Co.,Ltd
Tel:+86 20 6685 4299
Fax: +86 20 8230 6916
www.richcomm.com.cn/e
9
2.5Login Web Monitoring Interface
All above steps finished, open a web browser(suggest IE/firefox/chrome etc), input default IP
address 192.168.0.100 and enter
Input user name and password , default user name & Password are both “admin”.
(Users can change the User name and Password by the post setting)

Richcomm System Technologies Co.,Ltd
Tel:+86 20 6685 4299
Fax: +86 20 8230 6916
www.richcomm.com.cn/e
10
2.6Web Monitoring Interface
After input the user name and password, the monitoring homepage will come out soon, and then we
can check the UPS current status and do other software setting
3. Software Setting Introdution
3.1 UPS Information
Sub-Menu:
System Information
Device Information
Current Status
Remote Control
3.1.1 System Information
This page is to display UPS basic information and network information. The info shown here are
provided by NetmateLite SNMP card itself and parameter settings

Richcomm System Technologies Co.,Ltd
Tel:+86 20 6685 4299
Fax: +86 20 8230 6916
www.richcomm.com.cn/e
11
A, IPAddress
This part will automatically display when users finish the [Network Setting]
B, Subnet Mask
This part will automatically display when users finish the [Network Setting]
C, Gateway
This part will automatically display when users finish the [Network Setting]
D, System Name
This part will automatically display when users finish the [SNMP Setting]
E, SystemAdministrator
This part will automatically display when users finish the [SNMP Setting]
F, System Installation Position
This part will automatically display when users finish the [SNMP Setting]
G, Other information will be provided by NetmateLite monitoring system
3.1.2 Device Information
This part is to display each part of device information (UPS basic information, Battery Information
and Rated Information). The contents will change according to user setting and UPS real status. UPS
Manufacturer/Model/Version are provided by the UPS automatically.

Richcomm System Technologies Co.,Ltd
Tel:+86 20 6685 4299
Fax: +86 20 8230 6916
www.richcomm.com.cn/e
12
3.1.3 Current Status
This part is to display the UPS current running status. We can clearly know about the UPS current
running status,when an abnormal alert happens, figures will turn in red font.
Single-phase UPS Montoring
Basic Information
The current figures like Input Voltage/Input Frequency/Battery Voltage/Battery Content/UPS
Temperature/Output Voltage/Output Max Voltage/Output Min Voltage/ Current Load are display
here.

Richcomm System Technologies Co.,Ltd
Tel:+86 20 6685 4299
Fax: +86 20 8230 6916
www.richcomm.com.cn/e
13
3.1.4 Remote Control
This part is to set switch on/off control command for instant self-test, switch off, restart UPS and
beeper.
3.2 Parameter Setting
Sub-Menu:
System Setting
Network Settings
SNMPSettings
E-mail Settings
User Settings
IPPOWER Settings
3.2.1 System Setting
Basic Parameter Settings
This part is to set UPS basic parameters and the communication protocol is default, Baud Rate/
Offline Times/Alarm Times/Inquiry/Battery Quantity/ Battery Type/System Date Time need to be set
according to real UPS information (Please refer to the UPS user manual)

Richcomm System Technologies Co.,Ltd
Tel:+86 20 6685 4299
Fax: +86 20 8230 6916
www.richcomm.com.cn/e
14
3.2.2Network Settings
In this page, user can modify the IP address, subnet mask, gateway information, NTP server, time
zone and work mode of NetmateLite according to the real network segment, but the IP address
should not be conflicted with other device IP in a same network.
Also support system reboot.
3.2.3 SNMPSettings
This page is to set relevant settings, when NetmateLite is match with SNMP software, including
Basic Setting,Authorization Settings and TRAP Settings.

Richcomm System Technologies Co.,Ltd
Tel:+86 20 6685 4299
Fax: +86 20 8230 6916
www.richcomm.com.cn/e
15
Basic Setting
A, System Name
Name the NetmateLite.
B, SNMPSystem Administrator
Set the snmp system administrator of the NetmateLite.
C, SNMPSystem Installation Position
Set NetmateLite installation location.
The basic setting is convenient for centralized monitoring and management when there are a lot of
UPS. Users can fast and sinply inquire every UPS
Trap Setting
Receiver IP Address is used to receive traps sent by NetmateLite. Users can set 6 Trap receivers IP

Richcomm System Technologies Co.,Ltd
Tel:+86 20 6685 4299
Fax: +86 20 8230 6916
www.richcomm.com.cn/e
16
address at most. Support to choose whether receive the traps.
This part is to set SNMP users’ IP address, community and relevant authorization. Users can set 6
SNMP user IP address, and can choose the authorization which includes No Authorization, Readable
and Readable/Writeable.
3.2.4 E-mail Setting

Richcomm System Technologies Co.,Ltd
Tel:+86 20 6685 4299
Fax: +86 20 8230 6916
www.richcomm.com.cn/e
17
3.2.5 User Setting
This page is to set the user information which is used to login NetmateLite via Web.
3.2.6 IP POWER Setting
This part is to set the authorized address, all the authorized address can be remote centralized
managed via RichComm IP Power software. Authorization item includes Control and Access.
This manual suits for next models
2
Table of contents
Popular Adapter manuals by other brands

Linksys
Linksys WPC54GS - Refurb Wrls-g Notebook Adr Spdbstr No... Quick installation

Canon
Canon Scan Kiosk II Setup and administration guide

NETGEAR
NETGEAR XET1001 - Powerline Network Adapter installation guide

Philips
Philips SWA2092W Specifications

NETGEAR
NETGEAR MA111 user manual

Linksys
Linksys PLE200 - PowerLine AV EN Adapter Bridge Quick installation