S&C PureWave SMS-250 User manual

October 3, 2016
© S&C Electric Company 2015-2016, all rights reserved Instruction Sheet 659-525
S&C PureWave® SMS-250 Storage Management System
Power Conversion System
263 kW/263 kVA, 380 V
Supersedes Instruction Sheet 657-525 dated April 6, 2015
Table of Contents
Section Page Section Page
Introduction
Qualified Persons ..............................2
Read this Instruction Sheet ......................2
Retain this Instruction Sheet .....................2
Proper Application..............................2
Warranty .....................................2
Warranty Qualifications..........................2
Safety Information
Understanding Safety-Alert Messages .............3
Following Safety Instructions .....................3
Replacement Instructions and Labels...............3
Location of Safety Labels ........................4
Safety Precautions.............................5
Breaker Protection Curves......................6
Shipping and Handling
Packing .....................................7
Location of Mounting Hardware ...................7
Inspection ....................................8
Handling .....................................8
Installation, Assembly, and Setup
System Design ............................... 10
Concrete Pad Specifications..................... 10
Pad Requirements ............................ 10
Shimming, Grouting, and Caulking
the PCS Enclosure.......................... 11
Mounting.................................... 11
Cable Terminations ............................ 12
Battery Connection ............................ 12
Power Connections............................ 12
Wiring Methods .............................. 12
Lugs for Battery and Power Connections ........... 12
Earth Reference and Bonding ................... 13
Communications Signal Reference Requirements .... 13
Control and Grounding Connections............... 14
Connection Checks............................ 14
Torques ..................................... 14
Base Covers ................................. 14
Inspection Recommendations
Before Completing the Installation ................ 15
Pre-Startup Checklist .......................... 15
Annual Inspections ............................ 15
Installation

2S&C Instruction Sheet 659-525
Qualified Persons WARNING
The equipment covered by this publication must be installed, operated, and maintained by
qualified persons who are knowledgeable in the installation, operation, and maintenance
of energy storage equipment along with the associated hazards. A qualified person is one
who is trained and competent in:
• The skills and techniques necessary to distinguish exposed live parts from nonlive parts
of electrical equipment
• The skills and techniques necessary to determine the proper approach distances
corresponding to the voltages and arc flash levels to which the qualified person will
be exposed
• The proper use of the special precautionary techniques, personal protective equipment,
insulating and shielding materials, and insulated tools for working on or near exposed
energized parts of electrical equipment
These instructions are intended only for such qualified persons. They are not intended to
be a substitute for adequate training and experience in safety procedures for this type of
equipment.
Read this
Instruction Sheet NOTICE
Read this instruction sheet thoroughly before operating and maintaining the PureWave
SMS-250 Storage Management System. Familiarize yourself with the Safety Information
and Safety Precautions on pages 3 through 5. The latest version of this instruction sheet
is available online in a PDF format at sandc.com/Support/Product-Literature.asp
Retain this
Instruction Sheet
This instruction sheet is a permanent part of your power conversion system (PCS). It does
not include instruction sheets from the original battery manufacturer. Information sheets
such as this one can be placed inside a compartment in the PCS enclosure, where they it
can be easily retrieved for future use.
Proper Application WARNING
The equipment in this publication must be selected for a specific application. The
application must be within the ratings furnished for the equipment. Refer to S&C General
Brochure 659-G358 for the S&C PureWave SMS-250 Storage Management System. Fail-
ure to do so can result in damage to equipment.
Warranty The warranty and/or obligations described in S&C’s standard conditions of sale, as set
forth in Price Sheet 150, plus any special warranty provisions, as set forth in the applicable
product-line specication bulletin, are exclusive. The remedies provided in the former for
breach of these warranties shall constitute the immediate purchaser’s or end user’s exclusive
remedy and a fulllment of all seller’s liability. In no event shall the seller’s liability to the
immediate purchaser or end user exceed the price of the specic product that gives rise
to the immediate purchaser’s or end user’s claim. All other warranties, whether express
or implied or arising by operation of law, course of dealing, usage of trade, or otherwise,
are excluded. The only warranties are those stated in Price Sheet 150, and THERE ARE
NO EXPRESS OR IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR
A PARTICULAR PURPOSE. ANY EXPRESS WARRANTY OR OTHER OBLIGATION
PROVIDED IN PRICE SHEET 150 IS GRANTED ONLY TO THE IMMEDIATE PURCHASER
AND END USER, AS DEFINED THEREIN. OTHER THAN AN END USER, NO REMOTE
PURCHASER MAY RELY ON ANY AFFIRMATION OF FACT OR PROMISE THAT RELATES
TO THE GOODS DESCRIBED HEREIN, ANY DESCRIPTION THAT RELATES TO THE
GOODS, OR ANY REMEDIAL PROMISE INCLUDED IN PRICE SHEET 150.
Warranty
Qualifications
The seller’s warranties are contingent upon the installation and adjustment of the S&C
PureWave SMS-250 Storage Management System in accordance with S&C’s applicable
instruction sheets, data sheets, and/or data bulletins.
Introduction

S&C Instruction Sheet 659-525 3
Understanding
Safety-Alert
Messages
Several types of safety-alert messages may appear throughout this instruction sheet and
on labels attached to the PCS. Familiarize yourself with these types of messages and the
importance of these various signal words:
DANGER
“DANGER” identifies the most serious and immediate hazards that will likely result in
serious personal injury or death if instructions, including recommended precautions, are
not followed.
WARNING
“WARNING” identifies hazards or unsafe practices that can result in serious personal injury
or death if instructions, including recommended precautions, are not followed.
CAUTION
“CAUTION” identifies hazards or unsafe practices that can result in minor personal injury if
instructions, including recommended precautions, are not followed.
NOTICE
“NOTICE” identifies important procedures or requirements that can result in product or
property damage if instructions are not followed.
Following
Safety Instructions
If you do not understand any portion of this instruction sheet and need assistance, contact
your nearest S&C Sales Ofce or S&C Authorized Distributor. Their telephone numbers
are listed on S&C’s website sandc.com. Or call S&C Headquarters at (773) 338-1000; in
Canada, call S&C Electric Canada Ltd. at (416) 249-9171.
NOTICE
Read this instruction sheet thoroughly and carefully before
installing or operating your S&C PureWave SMS-250.
Replacement
Instructions
and Labels
If you need additional copies of this instruction sheet, contact your nearest S&C Sales
Ofce, S&C Authorized Distributor, S&C Headquarters, or S&C Electric Canada Ltd.
It is important that any missing, damaged, or faded labels on the equipment be replaced
immediately. Replacement labels are available by contacting your nearest S&C Sales Office,
S&C Authorized Distributor, S&C Headquarters, or S&C Electric Canada Ltd.
Safety Information

4S&C Instruction Sheet 659-525
Breaker Protection Curves
A B C
Reorder Information for Safety Labels
Location Safety Alert Message Description Part Number
ADANGER KEEP OUT. RISK OF ELECTRICAL SHOCK … PE-70479-1
B★NOTICE REAR CLEARANCE … PE-70482-1
CDANGER ARC FLASH AND SHOCK … PE-70483-1
★ Label is on the left and right sides of the PCS enclosure.
Location of Safety Labels
AC
C
C
B B
Symbols and Terminal Markings
The “
” symbol represents the power on button. When the “
” button with the symbol is pressed, the breaker
places the equipment into a fully-powered state
Equipment grounding conductor.
The “ ” symbol represents the power off button. When the button with the “ ” symbol is pressed, the breaker
disconnects the load side from the power source. The dc breaker disconnects the SMS-250 from the battery.
The ac breaker disconnects the ac output to the load.
Direct current, also indicated as dc.
Alternating current, also indicated as ac.

S&C Instruction Sheet 659-525 5
Safety Precautions
1. QUALIFIED PERSONS. Access to the PureWave
SMS-250 must be restricted only to qualified persons.
See “Qualified Persons” on page 2.
2. SAFETY PROCEDURES. Always follow safe
operating procedures and rules.
3. PERSONAL PROTECTIVE EQUIPMENT. Always use
suitable protective equipment, such as rubber gloves,
rubber mats, hard hats, safety glasses, and flame
retardant clothing, in accordance with safe operating
procedures and rules.
4. SAFETY LABELS. Do not remove or obscure any of
the “DANGER,” “WARNING,” “CAUTION,” or “NOTICE”
labels.
5. ENCLOSURE. Do not open access doors unless the
system is offline or otherwise authorized by S&C Electric
Company.
6. MAINTAINING PROPER CLEARANCE. Always main-
tain proper clearance from energized components,
ensuring the dead-front access panels are in place after
maintenance or before operation.
7. HAZARDOUS VOLTAGES. Hazardous dc voltage is
present even without utility power connected. Hazard-
ous voltages should also be expected in all intercon-
necting components and lines.
To maintain safety, the user should use a padlock
on the door of the power conversion system (PCS)
enclosure. The door and the use of the padlock provide
protection against inadvertent contact with hazardous
voltages.
8. GROUNDING. For grounding purposes, the proceeding
must be followed:
• The power conversion system base ground bar in
the cable-termination area must be connected to a
suitable earth ground for testing before energizing
the unit and at all times when energized.
• The overall ground system should be sufficient to
limit the Ground Potential Rise (GPR), step voltage,
and touch voltage to acceptable limits as determined
by the utility’s practices and the National Electric
Safety Code.
9. ENERGIZED COMPONENTS. Always consider all parts
live until de-energized, locked open, and tested.
10. ADDITIONAL CONNECTIONS. The user should not
attempt to connect any additional logic controls or power
connections to the PureWave SMS-250 (beyond the
connections shown on the interconnect drawing) with-
out having received written approval from S&C Electric
Company.
11. INSULATED HAND TOOLS. To use insulated hand
tools, the proceeding must be followed:
• Insulated hand tools are required when working on or
around any energized equipment. Use only properly
rated tools for the energy present.
• Tool inventories should be kept to ensure that all tools
that enter the system enclosure are removed prior to
energizing the system.
12. EMERGENCY PROCEDURES AND EQUIPMENT. For
emergency procedures:
• The owner should develop policies and procedures
for handling emergency situations.
• It is the responsibility of the owner to develop site-
specific emergency action plans for response to such
situations.
13. ADDITIONAL SAFETY INSTRUCTIONS. Consult the
battery supplier for additional safety instructions and
procedures regarding the battery used in the PureWave
SMS-250.
DANGER
The PureWave SMS-250 operates at hazardous voltage. Failure to observe these
precautions below will result in serious personal injury or death.
Some of these precautions may differ from your company’s operating procedures and
rules. Where a discrepancy exists, follow your company’s operating procedures
and rules.

6S&C Instruction Sheet 659-525
Breaker Protection Curves
The power conversion system has a xed output. The ac and dc breakers are congured at the factory with the following
protection curve:
Current in Amperes

S&C Instruction Sheet 659-525 7
Shipping and Handling
Packing
The power conversion system enclosure ships in one
piece. See Figure 1.
NOTICE
The Human Machine Interface (HMI) computer and batteries
for the PureWave SMS-250 are shipped separately.
Location of Mounting Hardware
The mounting brackets and hardware can be found bagged
and in the front lower lip of the PCS enclosure between
the bottom dead-front access panel and the bottom part of
the enclosure. See Figure 2.
NOTICE
Find and install all mounting hardware before starting up
the PureWave SMS-250. Failure to do so can result in
equipment damage.
Figure 1. Power conversion system enclosure.
Figure 2. Location of mounting brackets and hardware.
Mounting brackets and
hardware location

8S&C Instruction Sheet 659-525
Inspection
Examine the shipment for external evidence of damage as
soon after receipt as possible, preferably before removal
from the carrier’s conveyance. Check the bill of lading to
make sure all shipping skids and containers listed thereon
are present.
If there is visible loss and/or damage:
1. Notify the delivering carrier immediately.
2. Ask for a carrier inspection.
3. Note the condition of shipment on all copies of the
delivery receipt.
4. File a claim with the carrier.
If concealed damaged is discovered:
1. Notify the delivering carrier within 15 days of receipt
of shipment.
2. Ask for a carrier inspection.
3. File a claim with the carrier.
Also notify S&C Electric Company in all instances of
loss and/or damage.
Handling
NOTICE
The PCS enclosure shall be lifted according to lifting draw-
ing PEA-1610-4-IN and any other project-specific lifting
drawings supplied with the PureWave SMS-250. Lifting
equipment such as spreader bars and hoist sling straps
are provided by others.
To avoid damaging the PCS enclosure when placing it at
the desired location, observe normal recommended proce-
dures as well as the following general instructions.
CAUTION
The PCS installer must ensure ALL lifting equipment,
beams, slings, chains, spreader bars, and apparatus are
properly rated for the identified load. Failure to do so can
result in equipment damage and personal injury.
NOTICE
Before to lifting the PCS enclosure, ensure that all doors
are closed and locked.The doors contribute to the structural
integrity of the system and, if left opened, increase the risk
of damage to the enclosure during lifting.
WARNING
When handling the PCS enclosure with an overhead hoist,
observe standard lifting practices as well as the following
general instructions. Failure to follow these procedures can
result in serious personal injury and equipment damage.
Shipping and Handling

S&C Instruction Sheet 659-525 9
Shipping and Handling
This point should be at least
45 inches (1143 mm) above
the top of the PCS enclosure
Step 1
To lift and place the PureWave SMS-250 PCS, follow these
procedures:
(a) If spreader bars are used for lifting, make sure the
spreader bar(s) are secured.
(b) Arrange the hoist slings so the lifting forces are
distributed equally. See Figure3 for an illustration
of lifting the PCS enclosure. The equipment must be
lifted with a crane or forklift.
(c) Avoid sudden starts and stops when lifting.
(d) Properly place the PCS on the concrete pad. See
Figure 4 for the location of cable entry conduit and
mounting bracket installation areas. For further
details, refer to drawing PEA-1610-4-IN and the
other project specic lifting drawings supplied with
the PureWave SMS-250.
(e) Remove the sling straps.
Figure 3. Proper lifting of the power conversion system
enclosure.
Figure 4. Conduit and bracket measurements for pad-mounting.
Dimensions are in inches [millimeters]

10 S&C Instruction Sheet 659-525
System Design
The PureWave SMS-250 is a storage management system,
that can be connected to 380 Vac directly or, using an auto
transformer, to 400, 415, or 480 Vac, 3-phase, 50/60 Hz (to
match system frequency), 380-Vac delta primary, 265 kVA.
The storage management system consists of a
263-kW/263-kVA power converter housed in a weatherproof
enclosure suitable for outdoor or indoor mounting on a
concrete or equivalent pad, which can be applied either
with or without a 618- to 850-Vdc battery pack, depending
on the application-specific requirements. For specific appli-
cations that do not require a battery pack, the PureWave
SMS-250 assembly will be supplied without the dc circuit
breaker, dc EMI filter and dc bus terminations.
The PureWave SMS-250 can use a modular design
capable of parallel operation to achieve a rating of up to
526 kW/526 kVA.
Concrete Pad Specifications
NOTICE
The concrete pad is provided by others.
The concrete pad on which the PCS enclosure will be
placed should be sized to accommodate the unit and its
external mounting brackets. The pad should be poured
with a maximum pitch of 1⁄2degree and should have a
atness within 1⁄8inch (3.175 mm).
The pad should extend beyond the edge of the enclosure
by an adequate amount to prevent the pad from cracking
or breaking when the Hilti Kwik Bolt TZ anchor bolts are
installed to bolt the PCS enclosure to the pad.
Pad Requirements
General Requirements
The concrete pad contractor shall provide and be respon-
sible for determination and execution of the methods of
construction and for all safety precautions taken dur-
ing construction. Site visits by the structural engineer
will not include inspection of the means of construction.
All construction shall be in accordance with local code
requirements. Please contact S&C Electric Company
for recommendations in accordance with equipment
requirements.
Pad Dimensions and Mounting Provisions
The concrete pad contractor is responsible for pad design
and dimensions. Reference the separately supplied draw-
ing for the footprint dimensions and stub-up locations.
Both ac and dc cable boxes are required to be supplied
and installed by the installer for the power conductor con-
nection compartment to aid in conductor terminations
and connections.
Installation, Assembly, and Setup

S&C Instruction Sheet 659-525 11
Installation, Assembly, and Setup
Step 2
Shimming, Grouting, and Caulking
the PCS Enclosure
To shim, grout, and caulk the PureWave SMS-250 PCS
enclosure, follow these procedures:
(a) After placing the PCS enclosure at the desired
location, check whether there are any gaps between
the enclosure and the concrete pad.
(b) If there are gaps, install shims until the enclosure is
level.
(c) Apply grout at the bottom of the enclosure as
necessary to prevent entry of insects or debris into
the enclosure. The grout should be recessed
sufciently to permit a bead of caulk between the
enclosure base and concrete pad.
(d) Apply a bead of caulk (S&C part number 6943-010,
DAP Premium Polyurethane Waterproof Concrete
& Masonry Sealant 300 ml Gray) around the outer
edge of the bottom ange (where it meets the
concrete pad) to provide a seal around the base of
the PCS. The purpose of the caulk is to further
prevent ingress of insects and debris into the
enclosure.
Step 3
Mounting
(a) Anchor the PCS enclosure to the concrete pad. Use
⅜-inch diameter ×2-inch embed Hilti Kwik Bolt TZ
anchors for each bracket. The anchor brackets
should be located at each corner, as shown in Figure
5. Tighten the bolts again three to ve days after the
initial installation.
NOTICE
If seismic rating is required, ⅜-inch diameter ×2-inch
embed Hilti Kwik Bolt TZ anchors must be installed at
each mounting bracket location.
Failure to do so can result in
damage to equipment.
(b) After pulling the cables, seal all conduit entrances
on the outside with room temperature vulcanization
silicone sealant and on the inside with duct seal
foam to prevent water from entering the PCS
enclosure.
Figure 5. Mounting points.

12 S&C Instruction Sheet 659-525
Cable Terminations
NOTICE
For internal bus and cabling connections, refer to
installation drawing PEA-1610-4-IN and any project
specic drawings supplied with the PureWave SMS-250.
See Figure 6 for the location of the cable termination area
.
Step 4
Battery Connection
The battery must be supplied with an adequate protection
fuse and a disconnect breaker. The battery-protection fuse
must be sized correctly for the short-circuit current capac-
ity of the battery. The battery supplier shall include the
battery disconnect switch in the battery module.
Terminate the dc cables from the separate battery pack
(if supplied) to the dc inputs in the cable-termination area.
The positive terminal of the battery must connect to the
positive terminal on the PureWave SMS 250. The negative
terminal of the battery must connect to the negative terminal
on the PureWave SMS 250.
Note that battery voltage is floating from the earth refer-
ence. The battery enclosure must be bonded as indicated
in the Earth Reference and Bonding section.
Power Connections
Terminate the ac cables to the line inputs (L1, L2, and L3)
in the cable-termination area.
Wiring Methods
All wiring methods must be in accordance with the National
Electrical Code and ANSI/NFPA 70.
Lugs for Battery and Power Connections
Use the following recommended lugs or equivalent:
• Panduit LCA4/0-12-X (COPPER)
• T&B CTL40L-12 (COPPER)
Figure 6. Location of the cable termination area.
Installation, Assembly, and Setup

S&C Instruction Sheet 659-525 13
Installation, Assembly, and Setup
Earth Reference and Bonding
Earth Reference Requirements:
A low-impedance earth reference connection is required
for the PureWave SMS-250 equipment. The earth (ground)
reference system should be tailored to reect the char-
acteristics of the site and the requirements of the facility
and shall use a grounding interface that meets the needs
of the local electric utility’s system and that complies with
all applicable national and local electrical codes and stan-
dards. The PureWave SMS-250 uses power converters that
switch at frequencies up to 5 kHz. For S&C PureWave SMS-
250 equipment and systems rated less than 1000 kVA, the
resistance of the SMS-250 earth reference connection to
earth is required to be 25 ohms or less at both the nominal
power frequency of 50 or 60 Hz, and at the 5-kHz switching
frequency of the SMS-250 power conversion system.
Any associated battery equipment must have its own
direct earth reference connection. It is not permitted to
only ground the battery equipment through the PureWave
SMS-250 earth reference connections.
Bonding Requirements:
Besides the importance of creating an earth reference,
bonding is required between interconnected electrical
equipment to establish a low impedance path that minimizes
the potential difference between two metallic objects,
minimizes electric shock hazards, provides lightning
protection, and establishes references for electronic signals.
All cable tray, conduit, and raceway systems installed to
interconnect power, control, and communications wiring to
and from the S&C PureWave SMS-250 shall be electrically
continuous by bonding together at each individual section.
Each individual cable tray, conduit, and raceway section,
including pull boxes, junction boxes, and outlet boxes,
shall be bonded to the facility earthing system within 2 feet
(600 mm) of each end and at intervals not exceeding
50 feet (15 meters) along the run. All cable trays, conduits,
and raceways shall be securely bonded to all brackets,
hangers, and structural members to which they are
attached. The resistance of each bonding connection
shall not exceed 5 milliohms. The total bonding resistance
between the PureWave SMS-250 cabinet and any battery
cabinet/enclosure shall be no more than 1 ohm.
Communications Signal
Reference Requirements
All communications systems that interface with the
PureWave SMS-250 equipment must be designed for
operation in a multipoint earth (ground) reference system.
See examples of ground plan diagrams in Figures 7 and 8.
Figure 7. Example of a ground plan diagram showing the
S&C PureWave SMS-250 cabinet, the SMS-250 autotrans-
former option, and a battery system.
Figure 8. Example of a ground plan diagram showing two
S&C PureWave SMS-250 cabinets and a pad-mount isola-
tion transformer (var-only application—no battery system).
AUTO
TRANSFORMER
OPTION
BATTERY
SYSTEM
SMS-250 MINIMUM 72”
CLEARANCE
TO BATTERY
LEGEND
GROUND CONDUCTOR #4/0 AWG BARE 7
STRAND COPPER
10 FT. CU CLAD STEEL, 5/8 INCH DIA
#1 AWG CU TO #4/0 AWG CU EXOTHERMIC
CONN. OR APPROVED LISTED SWAGE
CONNECTION
TERMINATION TO GROUND CONDUCTOR
(1 AWG MINIMUM) BARE COPPER, 10 MM
THREADED STUD, SINGLE HOLE, LISTED
SWAGE LUG
GROUND CONDUCTOR TO SMS-250
EQUIPMENT (#1 AWG MINIMUM) BARE 7
STRAND COPPER
GROUND CONDUCTOR #4/0 AWG BARE 7
STRAND COPPER
10 FT. CU CLAD STEEL, 5/8 INCH DIA
NEMA TWO HOLE PAD OR GROUND CLAMP
TO #4/0 CU CONNECTOR
#4/0 AWG CU TO #4/0 AWG CU
EXOTHERMIC CONN. OR APPROVED
LISTED SWAGE CONNECTION
PAD MOUNT
TRANSFORMER
SMS-250 SMS-250
LEGEND
#1 AWG CU TO #4/0 AWG CU EXOTHERMIC
CONNECTION OR APPROVED LISTED
SWAGE CONNECTION
TERMINATION TO GROUND CONDUCTOR
(1 AWG MINIMUM) BARE COPPER, 10 MM
THREADED STUD, SINGLE HOLE, LISTED
SWAGE LUG
GROUND CONDUCTOR TO SMS-250
EQUIPMENT (#1 AWG MINIMUM) BARE 7
STRAND COPPER

14 S&C Instruction Sheet 659-525
Step 5
Control and Grounding Connections
For control and grounding connections:
(a) Install control and communication cabling using the
entry location in the cable termination area.
(b) Attach the ground bus of the PCS to the system
ground in accordance with the installation drawing.
(c) Seal the conduits with duct-sealing compound to
prevent water from entering the system through the
conduits.
Connection Checks
Check all eld-installed cables and wiring to the power
conversion system by performing a “point-to-point” check
on all of the wiring to verify the system is wired, labeled,
and terminated per drawing PEA-1610-4-IN and any
project-specic drawings supplied with the PureWave
SMS-250. Note any problems found and corrective actions
applied.
Torques
Check all factory and eld-bolted electrical connections
inside the PCS enclosure and verify they are torqued to
the proper tightness. See Table 1 for torque requirements.
Table 1. Torque requirements.
ASSEMBLY PA RT HARDWARE TOOL
TORQUE
[N-M]
TORQUE
[FT-LBS]
Dead-Front
Access
Panels
Panels M8 Serrated
Flange
13mm
Socket 13.6 10
EMI
Fasteners
M5x12
Screw
#2
Phillips 3.9 2.9
Bus
Connections N/A M10 Flange
Nut/Bolt
15mm
Socket 54.2 40
Islanding
Tra y
Tra y M8 Serrated
Flange
13mm
Socket 13.6 10
CT Terminal
Block
#10-32
Terminals
Slot
Driver 21. 5
Terminal
Blocks M4 Terminals Slot
Driver 1. 7 1.25
Programmable
Logic Controller M3 Mounting #1
Phillips 1. 1 0.8
Base Covers
Install the base covers (if not already installed) at the
front and back forklift entries of the enclosure. They are
typically stored on the inside of the enclosure door. See
Figure 9.
Figure 9. Location of base covers.
Base cover
storage
location
Base covers
Installation, Assembly, and Setup

S&C Instruction Sheet 659-525 15
Step 6
Before Completing the Installation
Before completing the installation:
(a) Replace and secure the dead-front access panels.
(b) Close and lock the door of the power conversion
system (PCS) enclosure(s).
(c) Wipe down the exterior of the PCS enclosure(s)
with a clean damp cloth. Renish any scratches or
abrasions.
If touch-up paint is in-hand, the area to be touched up
should be cleaned to remove all oil and grease. Sand the
area, removing any traces of rust that may be present, and
make sure all edges are feathered before applying primer.
Pre-Startup Checklist
The pre-startup checklist will be provided and should be
reviewed and lled out by the installing contractor. The
document must be signed and faxed to S&C Electric
Company at (414) 423-8766.
Annual Inspections
After the PureWave SMS-250 is commissioned and the unit is
online, inspection and maintenance should be scheduled for
the PCS on an annual basis to ensure the proper operation of
the system. Schedules for maintenance should be reviewed
by the customer based upon the given site conditions and, if
required, the frequency of the recommended maintenance
should increase to ensure the reliability of their PureWave
SMS-250.
Inspection Recommendations

Other manuals for PureWave SMS-250
3
Table of contents
Other S&C UPS manuals