SANJIANG JTW-ZD-920KE User manual

Version:1023151027E
-1-
Instruction Manual of JTW-ZD-920KE Point-type Heat Fire Detector
------ Please read this Manual carefull
y
before installin
g
and usin
g
the
p
roduct. -----
I. Product overview
JTW-ZD-920KE point-type fixed temperature heat detector (Detector hereunder) is a two-wire
switch-type temperature-sensing detector. As a non-polar two-wire connection is adopted in the detector,
it is compatible in conventional switch-type alarm control systems and
monitoring alarm systems. The detector can also be connected with
intelligent bus fire alarm control systems via a interface module. The detector
monitors temperature in the workplace in real time. While monitoring, the red
indicator blinks and the working current is low. When the work site
temperature has exceeded the preset alarm threshold, the alarm detectors
and the red indicator remain on, while the loop current is increased. The
detector’s alarm signal can be locked and is displayed by changes in the loop
current. The alarm can only be reset by the instant power disconnection.
The detector is applicable in places where fire might generate volume heat, i.e. in industrial and civil
buildings such as in the kitchen, boiler room, generator room, drying plant, and smoking room. However,
it is not suitable for places where volume smoke and low heat is generated during a fire, or a place
where a smoldering fire might occur.
II. Product features
Designed with an upper cover and a lower cover, it can be installed, debugged and maintained
conveniently.
It can monitor temperature in the workplace in real time
Non-polarity, two-bus connection that ensures convenient installation and maintenance.
III. Technical parameters
1. Executive standard: GB4716-2005
2. Working voltage: DC24V (allowance: DC18V ~ 30V)
3. Working current: during monitoring <50uA @ DC 24V
In alarm mode 1mA~10mA (depends on the loop current limiting resistance)
4. Working indicator: during monitoring, the red indicator blinks
In alarm mode: the red indicator remains on
5. Weight: about 46g
6. Production class: A2
7. Exterior size: diameter: 100mm, height: 56mm(with the base)
8. Wiring method: non-polar two-wire
9. Operating environment: Indoor, temperature: -10℃~+50℃; relative humidity: ≤95% (40℃
±2℃, without condensation)
10. Installation height: ≤8m
11. Protection area: see related provisions in GB50116-98 Code for Design of Automatic Fire
Alarm System.
12. Matched host machine: conventional switch-type fire alarm control system, or intelligent bus
fire alarm control system via a interface module.
IV. Appearanceand dimensions (see Fig.1)
-2-
(Unit: mm)
Fig.1
V. Use and engineering application
1. Fig.2 is the schematic diagram of the matched mounting base.
DZ-910K
Fig.2
Definitions of terminals(non-polarity two-wire
system):
1 – L2 Signal terminal
2 – L1 Signal terminal
3 – L1 Signal terminal
4–NoPin
Notes:Terminal 2 and 3 are connected directly
inside the detector. Connecting the detector with
the controller as Fig.3, we can find the failures
caused by dismounting the detector.
2. Wiring method:
a. Fig.3 is a schematic diagram of the connection between multiple detectors with a
conventional switch-type (current type) alarm control systems.
DZ-910K
DZ-910K
DZ-910K
Fig.3
b. Fig.4 is a schematic diagram of the connection between multiple detectors with
intelligent two-bus fire alarm control system via a interface module.
L2
L1
GND
+24V
TO+
TO-
Intelligent
two-bus fire alarm
control panel
Input module
Terminal load(4.7K)
DZ-910K
DZ-910K
DZ-910K
Fig.4
A指示灯
Screw cover
A Indicator

-3-
VI. Installation and debugging
Determine the location, mounting distance and numbers for mounting the detectors in the protection
area according to relevant provisions and regulations of GB50116-98 Code for Design of Automatic Fire
Alarm System and GB50166-2007 Code for Installation and Acceptance of Fire Alarm System.
A self-contained complete base is necessary during the installation of a detector. As shown in Fig.5,
the model, the external dimensions, the mounting hole diameter and the mounting hole spacing of the
base are DZ-910K, Φ100mm×22mm (diameter×thickness), Φ4.5mm and 44mm~65mm respectively.
C
D
DZ-910K
B
Fig.5
Wiring requirement: It is proper to use RVS twisted pairs with a section area of equal to or larger
than 1.0mm2for the signal buses L1 and L2.
Specific installation and debugging methods:
1. Make sure the type of the detector matches the type of the host machine of the fire alarm
control panel;
2. Use two M4 screws to fix the matched mounting base on the designated position via the
mounting holes C and D shown in Fig.5, as instructed in the construction drawing and make
sure the matched mounting base has been firmly installed.
3. Disconnect the power supply of the fire alarm control panel and connect the detector correctly
according to the construction drawing.
4. Place the indicator at position A of the detector (see Fig.1) and position B of the base (see
Fig.5), align them with each other, insert the detector into the base and turn the detector
clockwise until it is firmly locked.
5. After all the products are installed and checked, connect the power supply of the fire alarm
control panel.
6. When the detector is powered up normally, the red indicator of the detector will blink once about
every 3~6 seconds, which suggests that the detector has begun to operate normally.
7. Finally conduct an alarm test for the detector through some special tools or direct hot air gun
blowing. After the detector gives a fire alarm, the indicator will remain lit and the fire alarm
control panel will simultaneously give corresponding alarm prompt information. After the alarm
test, reset the fire alarm control panel and restore to the monitoring status.
-4-
VII. Precautions
1. The connected detectors shall be 50 units max when the JTW-ZD-920KE is connected with
intelligent fire alarm control systems via a interface module.
2. Never dismount the protective cover delivered with the detector too early after the field
installation and before the use of the detector, or else the detector may be contaminated.
3. It is not permitted to use open flames (such as lighters) to firing thermistor during alarm tests,
so as to avoid damage to the detector. It is recommended to use a hot air gun and other heating
equipment in a simulation alarm test.
4. The protection area and quantity of the detectors should comply with relevant provisions in
GB50116-98 Code for Design of Automatic Fire Alarm System and GB50166-2007 Code for
Installation and Acceptance of Fire Alarm System.
VIII. Maintenance
Warning: Before conducting maintenance for a detector, inform the related management
department that the monitoring will be stopped temporarily when the system maintenance.
Meanwhile, disable the logic control function of the area or system to be maintained to avoid
unnecessary alarm linkage. After the test, inform the management department to restore the
normal functions of the system.
1. According to the requirements of GB50166-2007 Code for Installation and Acceptance of Fire
Alarm Systems, each quarter, some special testing instruments should be used to test the
detector’s operation and confirm the indication state of its indicators by batch and stage; for a
detector that has been installed and used, It is recommended to have it maintained once every
two years.
2. If a detector fails due to a material defect or a manufacturing process defect under normal
conditions of use in one year following the date of its delivery, we shall repair or replace it for
free. However, the faults of the detector due to artificial damage, improper use, or authorized
adjustment, reconstruction or disassembly are not covered in the guarantee and we shall
assume no responsibilities for any the consequence thereby caused.
3. We may provide paid repair service for products with any faults beyond the guarantee range. If
you have such products that need repair, please contact us. When sending such a product to
us for repair, you are expected to provide some important information about the product, such
as the phenomenon and possible cause of the product fault, so that we can find out the cause
of the fault in the shortest time and so the information may be used as a reference in our future
product development and improvement.
IX. Fault analysis and troubleshooting
Failures Causes Methods Remarks
Alarm after
powered up Internal circuit is broken Return to the manufacturer for
repairs
Cannot work after
powered up
Internal circuit is broken Return to the manufacturer for
repairs
Bad contact to the base Inspect and reinstall the base
Cannot alarm
during test Internal circuit is broken Return to the manufacturer for
repairs
Address:3F, Guangcai New World Building, Nanshan Road, Nanshan District, Shenzhen, 518054, P.R.China
Tel:+86(755)86226969 Fax::+86(755)86223939 Http://www.fhsjdz.com
Other SANJIANG Security Sensor manuals
Popular Security Sensor manuals by other brands

Agilent Technologies
Agilent Technologies 85025A User's and service guide

resideo
resideo 5800CMBOV Quick installation guide

MSA
MSA FlameGard 5 MSIR HART manual

Parker
Parker 023-0388 Specification & installation guide

Hama
Hama 186434 operating instructions

RKI Instruments
RKI Instruments 35-3010RKA-01 manual

AMC
AMC SMILE 18 manual

ADEMCO
ADEMCO 655 installation instructions

U-Prox
U-Prox PIR quick start guide

ConTech Lighting
ConTech Lighting REXA Series installation instructions

Leuze electronic
Leuze electronic SOLID-2 Series Connecting and operating instructions

DBI SALA
DBI SALA EZ-LINE 7605060B Specific instructions