Schako EasyBus EasyS-MV2 User manual

Construction subject to change
No return possible Version: 2016-06-29 | Page 1
Contents
Safety instructions............................................................................... 2
General information ............................................................................ 2
Warranty ............................................................................................. 2
Recycling.............................................................................................. 2
General information about EasyBus.................................................... 2
Module overview................................................................................. 2
EasyF-ADC connections ....................................................................... 3
EasyF-AAC connections ....................................................................... 3
EasyF-VDC connections ....................................................................... 4
EasyF-VAC connections........................................................................ 4
EasyF-VMP connections ...................................................................... 5
EasyF-RMM connections ..................................................................... 5
EasyF-IOM connections ....................................................................... 6
EasyF-I8M connections........................................................................ 6
Programming of the EasyF modules.................................................... 7
Cable length......................................................................................... 8
Module mounting................................................................................ 8
Flat cable system ................................................................................. 8
Switch cabinet mounting..................................................................... 8
Wiring of the EasyS-MV1/-Mv2 ........................................................... 9
Modbus communication ..................................................................... 9
Terminating resistor ............................................................................ 9
Programming of EasyS-MV2 .............................................................. 10
Circuit diagram for an Easy network ................................................. 14
Modbus register ................................................................................ 18
Read and write register of EasyF-ADC and -AAC ............................... 19
Read and write register EasyF-VDC and EasyF-VAC........................... 25
Read and write register for EasyF-RMM............................................ 31
Read and write register EasyF-IOM ................................................... 34
Read and write register EasyF-I8M.................................................... 37
Read and write register EasyF-VMP .................................................. 40
EasyBus
Signalling and Switching Bus System
Installation, Operating and Maintenance

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Safety instructions | Recycling
Construction subject to change
No return possible Version: 2017-11-13 | Page 2
SAFETY INSTRUCTIONS
Before installing and commissioning the EasyBus
components, carefully read the entire manual. Take note in
particular of the operating instructions containing hazard
symbols and warning signs. Their non-observance could result
in damage to the unit and slight to serious personal injuries.
Should you have any questions, after reading through the
entire manual, please contact SCHAKO.
An exclamation mark within a triangle
indicates information which must be observed
by the user. Non-observance may result in
damage to the module or loss of data.
A lightning flash within a triangle warns
against
electric shock or impairment of the electrical
safety of the device.
This symbol indicates important information in
these operating instructions which must be
observed.
GENERAL INFORMATION
Inspection, installation, connection and commissioning of
the EasyBus components may be carried out by skilled
personnel only in compliance with current regulations.
The EasyBus components must not come into contact with
liquids.
The EasyBus components must not be operated with wet
hands.
Control and safety elements must not be modified without
approval by the manufacturer or the regional sales
representative.
The electric connections and their proper functioning are
the responsibility of the installer.
SCHAKO will not be responsible for any damage caused by:
incorrect installation due to non-observance of the
instructions of the present manual.
installation and maintenance not carried out by skilled
personnel.
non-observance of the operating conditions of the EasyBus
components.
improper use of the EasyBus components or under
inadmissible conditions according to the present manual.
WARRANTY
The warranty for the EasyBus components is two years from
the acceptance date for manufacturing errors. This does not
apply to the included electric components to which the
warranty of the manufacturer in question applies. The
warranty does not cover damage to the unit caused by
components that do not belong to the equipment
components. The warranty only covers the return and
replacement of defective parts.
RECYCLING
Contact a certified electronic waste disposal company for
environmentally friendly recycling and disposal of EasyBus
components.
GENERAL INFORMATION ABOUT EASYBUS
The signalling and switching bus system SCHAKO EasyBus can
be used, among other things, for activating and monitoring
mechanical and electrical fire dampers with
24V DC or 230V AC spring return actuator, smoke extraction
dampers, smoke detectors and volumetric flow controllers
with 0(2)-10V activation or air diffusers with 2/3-point
motorised drives.
MODULE OVERVIEW
For individual areas, we are offering the following modules
for signal processing and monitoring:
Type Description Function
EasyS-MV1
EasyS-MV2 Master Modulation of the bus
signal
EasyF-ADC
EasyF-AAC
Motorised drive
module
Control of a motorised
drive and detection of its
end positions
EasyF-VDC
EasyF-VAC
EasyF-VMP
Analogue closed-
circuit and open-
circuit control
module
Closed-circuit and open-
circuit control of steadily
controlling drives
EasyF-RMM Smoke detector
module
Monitoring and
evaluation of the smoke
detectors
EasyF-IOM Input / output
module
Monitoring of up to 4
inputs and switching of 4
outputs
EasyF-I8M Input module Monitoring of up to 8
digital inputs
EasyF-ETX Radio transmitter
Radio limit switch for
mechanical fire dampers
EasyF-RXE
Receiver module
for radio
transmitters
Evaluation and
transmission of the
signals from radio
transmitters

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
EasyF-ADC connections | EasyF-AAC connections
Construction subject to change
No return possible Version: 2017-11-13 | Page 3
EASYF-ADC CONNECTIONS
General:
The EasyF-ADC module is used for connecting and controlling
a 24V DC motorised actuator, for example, of a fire damper
or a smoke extraction damper.
The EASYF-ADC is equipped with the corresponding
connections for the preassembled spring return actuators by
Belimo.
Cons.
No. Figure Description Terminal /
pin
Terminals for connection to the EasyBus network 230 V AC
1
230V AC/50Hz Terminal 1
230V AC/50Hz Terminal 2
Zero conductor Terminal 3
Zero conductor Terminal 4
Programming and visualisation
2
7-segment display and
Programming key
Hardware contact
3
Smoke detector
contact Terminal 1
Voltage +24VDC Terminal 2
Voltage +24V DC Terminal 3
Ground (GND) Terminal 4
Connection plug for the motor
4
Opening control Pin 1
Ground (GND) Pin 2
Closing control Pin 3
Connection plug for the end positions
5
Damper open >80° Pin 1
Ground Pin 2
Ground Pin 3
Damper closed <5° Pin 4
Reserve Pin 5
Reserve Pin 6
EASYF-AAC CONNECTIONS
General:
The EasyF-AAC module is used for connecting and controlling
a 230V AC motorised actuator, for example, of a fire damper
or a smoke extraction damper.
Cons.
No. Figure Description Terminal /
pin
Terminals for connection to the EasyBus network 230 V AC
1
230V AC/50Hz Terminal 1
230V AC/50Hz Terminal 2
Zero conductor Terminal 3
Zero conductor Terminal 4
Programming and visualisation
2
7-segment display and
programming key
Terminals for the motor
3
230V AC/50Hz Terminal 1
Zero conductor Terminal 2
Opening control Terminal 3
Neutral conductor N Terminal 4
Closing control Terminal 5
Hardware contact
4
Contact NO Pin 1
Voltage +24V DC Pin 2
Connection plug for the end positions
5
Damper open >80° Terminal 1
Ground Terminal 2
Ground Terminal 3
Damper closed <5° Terminal 4
Reserve Terminal 5
Reserve Terminal 6
1
3
4
5
2
1
3
4
5
2

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
EasyF-VDC connections | EasyF-VAC connections
Construction subject to change
No return possible Version: 2017-11-13 | Page 4
EASYF-VDC CONNECTIONS
General:
The EasyF-VDC module is used for connecting and controlling
two independent steadily regulating
DC drives, for example VAV (Variable Air Volume) or valves.
The two independent analogue 0-10 V inputs can receive the
signal, for example of a CO
2
sensor, a temperature sensor,
etc., and be used, for example, for monitoring the air quality
or the like.
Cons. No. Figure Description Terminal / pin
Terminals for connection to the EasyBus network 230 V AC
1
230V AC/50Hz Terminal 1
230V AC/50Hz Terminal 2
Zero conductor Terminal 3
Zero conductor Terminal 4
Programming and visualisation
2
7-segment display and
Programming key
Terminals of the analogue inputs
3 + 4
0 to 10V DC input Terminal 1
24V DC Terminal 2
Ground (GND) Terminal 3
Terminals for the motors
5 + 6
0 to 10 V input
effective value Terminal 1
0 to 10 V output
control signal Terminal 2
24 V DC Terminal 3
Ground Terminal 4
EASYF-VAC CONNECTIONS
General:
The EasyF-VAC module is used for connecting and controlling
two independent steadily regulating
AC drives, for example VAV (Variable Air Volume) or valves.
2 drives can be connected to each EasyF-VDC module.
Cons. No. Figure Description Terminal / pin
Terminals for connection to the EasyBus network 230 V AC
1
230V AC/50Hz Terminal 1
230V AC/50Hz Terminal 2
Zero conductor Terminal 3
Zero conductor Terminal 4
Visualisation
2
7-segment display
Terminals for the VAV motors
3 + 5
GND (GO) Terminal 1
24V AC (G) Terminal 2
0-10V VAV control
signal Terminal 3
0-10V VAV
effective value Terminal 4
Parameterisation
4
Programming key
1
3
4
2
5
6
1
3
2
4

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
EasyF-VMP connections | EasyF-RMM connections
Construction subject to change
No return possible Version: 2017-11-13 | Page 5
EASYF-VMP CONNECTIONS
General:
The EasyF-VMP module is used for connecting and controlling
two MP-Bus-capable drives.
Cons. No. Figure Description
Terminals for connection to the EasyBus network
230 V AC
1
230V AC/50Hz
230V AC/50Hz
Zero conductor
Zero conductor
Programming and visualisation
2
7-segment display
and
programming key
Terminals for the motors
3 + 4
Ground (GND)
24V DC
Control signal 0 - 10V
Effective signal 0 -
10V
EASYF-RMM CONNECTIONS
General:
The EasyF-RMM module is used for connecting the smoke
detectors (RMSII-L) to the 230 V EasyBus network and is used
for duct monitoring.
Cons. No. Figure Description
Terminals for connection to the EasyBus network 230 V AC
1
230V AC/50Hz
230V AC/50Hz
Zero conductor
Zero conductor
Programming and visualisation
2
7-segment display and
programming key
9-pin Sub D connector for connecting the smoke detectors
3 + 4
GND Pin 1
Fault NO Pin 2
Centre contact fault Pin 3
Fault NC Pin 4
Test Pin 5
Alarm NC Pin 6
Centre contact alarm Pin 7
Alarm NO Pin 8
+24V DC Pin 9
1
3
4
2
1
3
4
2

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
EasyF-IOM connections | EasyF-I8M connections
Construction subject to change
No return possible Version: 2017-11-13 | Page 6
EASYF-IOM CONNECTIONS
General:
The EasyF-IOM module is equipped with 4 digital inputs and
potential-free changeover contact outputs, which can be
switched or monitored independently of one another.
To the contact marked with + of the EasyF-IOM module, a 24
V DC voltage is applied and then switched via a suitable
contact. Each completed actuation can then be visualised.
Likewise, the EasyF-IOM module allows up to four different
switching functions to be carried out via the potential-free
outputs. At each output, up to 6 A can be switched at 30 V DC
or 250 V AC.
Cons.
No. Figure Description Terminal /
pin
Terminals for connection to the EasyBus network 230 V AC
1
230V AC/50Hz Terminal 1
230V AC/50Hz Terminal 2
Zero conductor Terminal 3
Zero conductor Terminal 4
Programming and visualisation
2
7-segment display and
programming key
Terminals of the 4 potential-free inputs
3
Signal feedback input A Terminal 1
24V DC input A Terminal 2
Signal feedback input B Terminal 3
24V DC input B Terminal 4
Signal feedback input C Terminal 5
24V DC input C Terminal 6
Signal feedback input D Terminal 7
24V DC input D Terminal 8
Terminals for the 4 changeover outputs
(Max. current 6 A at 230V AC or 24V DC)
4
Centre contact COM output A Terminal 1
NO contact NO output A Terminal 2
NC contact NC output A Terminal 3
Centre contact COM output B Terminal 4
NO contact NO output B Terminal 5
NC contact NC output B Terminal 6
Centre contact COM output C Terminal 7
NO contact NO output C Terminal 8
NC contact NC output C Terminal 9
Centre contact COM output D Terminal 10
NO contact NO output D Terminal 11
NC contact NC output D Terminal 12
EASYF-I8M CONNECTIONS
General:
The EasyF-I8M module is equipped with 8 digital inputs that
can be monitored independently of one another.
To the contact marked with + of the EasyF-I8M module, a 24
V DC voltage is applied, which can be switched via a suitable
contact. Each completed actuation can then be visualised.
The switching/wiring states are visualised via LEDs.
Cons.
No. Figure Description Terminal /
pin
Terminals for connection to the EasyBus network 230 V AC
1
230V AC/50Hz Terminal 1
230V AC/50Hz Terminal 2
Zero conductor Terminal 3
Zero conductor Terminal 4
Programming and visualisation
2
7-segment display and
programming key
Terminals of the 8 potential-free inputs
3
+
4
Signal feedback input A Terminal 1
24V DC input A Terminal 2
Signal feedback input B Terminal 3
24V DC input B Terminal 4
Signal feedback input C Terminal 5
24V DC input C Terminal 6
Signal feedback input D Terminal 7
24V DC input D Terminal 8
1
3
4
21
3
4
2

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Programming of the EasyF modules |
Construction subject to change
No return possible Version: 2017-11-13 | Page 7
PROGRAMMING OF THE EASYF MODULES
Each EasyF module requires its own address and must be set
to the corresponding channel of the associated master.
For this, a 7-segment display and a programming key are
integrated in each module. They can be used to make
settings.
7-segment display
Programming key
Status indicator of the module:
Module is connected to the EasyBus network
Then the following indications are displayed on the 7-
segment display (factory settings) (A 000; C 01)
Programming the module:
The procedure shows, by way of example, how to change the
address from 001 to 005.
EasyF module is in function
Hold down the programming key >3s
flashes three times
" appears
Hold down the programming key >3s
appears (flash frequency of the point 3x)
Set the desired number by pressing the key, if
required
Hold down the programming key >3s
appears (flash frequency of the point 2x)
Set the desired number by pressing the key, if
required
Hold down the programming key >3s
" appears (flash frequency of the point 1x)
Set the desired number by pressing the key, if
required
Press the programming key until a "
isdisplayed
Hold down the programming key >3s
" flashes
" appears (flash frequency of the point 2x)
Set the desired number by pressing the key, if
required
Hold down the programming key >3s
appears (flash frequency of the point 1x)
Hold down the programming key >3s
After that, the address and the channel are visualised and the
programming of this module is completed.
The address and the channel are constantly visualised.
Flash frequency of the point
Place 100 10 1
7-
segment
display
•
•
•
Flash
frequency
3x 2x 1x

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Cable length | Switch cabinet mounting
Construction subject to change
No return possible Version: 2017-11-13 | Page 8
CABLE LENGTH
The standard cable length from the module to the consumer
(BSK, ERK, RM) is 1 m including prepared connection option.
The max. cable length from the module to the bus line is 1.5
m.
The total cable length from the switch cabinet to the last
terminal of the EasyF module with 128 modules must not
exceed a length of 1000 m.
Moreover, a distance of at least 5 cm between two flat cables
is recommended if cables are installed, for example in ducts,
tracks, etc.
MODULE MOUNTING
To ensure connection, a minimum distance of 40 mm from
the four side surfaces to walls, ventilation ducts or similar is
recommended.
For removing the module cover, a minimum distance of 100
mm from the top side of the cover is recommended.
In addition, it is recommended to fasten the module at a
distance of max. 100 mm from edges of the inspection
opening to provide a good accessibility to the module during
commissioning or service activities.
FLAT CABLE SYSTEM
H corresponds to the cable thickness
R corresponds to the smallest recommended bending radius
When using the connection socket (-MASD), it is
recommended to fasten it using cable ties or the like.
The recommended distance between points for fastening of
the flat cable is between at least 500 mm and a maximum of
1500 mm.
(source: Installation instructions by Woertz)
The cable manufacturer always recommends to use an
additional strain relief by means of cable ties (see figures).
This reduces the tractive forces at the connection socket.
According to EN 61535 A1, tractive forces of 100 ±2 N are
allowed for a cable diameter of more than 16 mm.
SWITCH CABINET MOUNTING
When mounting the EasyS-W01 or –W02 switch cabinet, the
minimum distance of 0.8 m from the ground is
recommended. A minimum distance of 0.2 m (on the right or
left) is also recommended. This distance from a side surface is
also recommended for the EasyS-A01 to –A05 switch
cabinets.
For fastening the EasyS-W01 to W02 switch cabinets, select
the corresponding fastening material depending on the
masonry.

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Wiring of the EasyS-MV1/-Mv2 | Terminating resistor
Construction subject to change
No return possible Version: 2017-11-13 | Page 9
PLC
WIRING OF THE EASYS-MV1/-MV2
The master device manages up to 128 users and forms the
interface with a PLC.
The master executes all data traffic tasks between the
EasyBus network and the control unit (PLC). The master also
performs bus monitoring and system diagnostics.
Terminal assignment:
1
L 230V AC/50Hz
L 230V AC/50Hz
N Zero conductor
N Zero conductor
2
7-segment display
3
D Data RS485 Half
Duplex
D/ Data/ RS485 Half
Duplex
0V Reference for
RS485/RS232
TX RS232 data transfer
RX RS232 receiving data
1 Fire contact
2 Feedback
4
Programming key
MODBUS COMMUNICATION
The EasyS-MV1 /-MV2 can communicate either via
RS485 Half Duplex or RS232. The corresponding interface is
selected by changing the jumper position.
The wiring of the two communication protocols is different.
Furthermore, the shielding of CV 2x2x0.75mm² must be
earthed at one end.
Connection RS485:
Connection RS232:
TERMINATING RESISTOR
A Modbus network (e.g. RS-485 network) must be terminated
at the network ends.
The terminating resistor can be activated by inserting the
jumper at EasyS-MV1 or EasyS-MV2. The following figure
shows the activated terminating resistor. The following figure
shows the activated terminating resistor. In this case, the
jumper is inserted.
PLC
PLC
1
3
2
4

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Programming of EasyS-MV2 |
Construction subject to change
No return possible Version: 2017-11-13 | Page 10
PROGRAMMING OF EASYS-MV2
The programming is carried out via the programming key on
the upper module plug-in card. The menus and menu settings
are visualised via a 7-segment menu.
Go to the programming mode by pressing the programming
key for a long period (>3s). In this mode, select the
corresponding menu by briefly pressing the key and confirm
by pressing it again (>3s). After that, this menu can be edited.
Status displays of EasyS-MV2
When the master is switched on, it shows its firmware
version.
Number 8 corresponds to the firmware version of EasyBus
2.0.
The numbers from 1 to 4 represent the firmware versions of
the variant EasyBus 1.0
The 01 represents the corresponding firmware version. They
differ from other versions by small alterations and bugfixes
Status displays of EasyBus master:
Display State of
EasyS-MV2
Meaning
Stop Master is in standby. No
communication takes place in
EasyBus network.
Run Once the connection to the PLC
via Modbus is established and the
users are detected, the master
switches automatically to this
state.
Scan Master collects information
about the die EasyBus users
Fire contact
active
All bus users go to safety position
Time out No connection to the PLC
Programming of EasyS-MV2
In the Modbus submenu, briefly press the programming key
to select the submenu items
- "o" (positive opening operation of the peripheral devices)
- "S" (scan without automatic addressing)
- "S." (scan with automatic addressing)
- "C" (channel change)
- "b" (Modbus submenu)
and hold down the programming key for a long period (>3s)
to display and adjust the corresponding settings. To confirm
the entry, hold down the programming key (>3s) until the
corresponding parameter has been completely set (max. 3
digits). After that, the 7-segment display goes out briefly, the
master restarts and switches to the status display.
The following section explains the corresponding
programming of the submenus.
Display "C"
Positive opening operation
Scan without self-addressing
Scan with self-addressing
Channel configuration
Status display
0 / 1 / F
Display "o"
Dis
p
la
y
"S"
Display "S."
Display "b" Modbus configuration

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Programming of EasyS-MV2 |
Construction subject to change
No return possible Version: 2017-11-13 | Page 11
Scan with self-addressing
General information about addressing:
To set up an EasyBus network, at least one EasyS-MV2 and
one EasyS-FV1, at least one (up to max. 128) EasyF module
and a Modbus interface are required. The prerequisite for the
communication between an EasyS-MV2 and the users (at
least one (up to max. 128) of the EasyF modules is a complete
scan of the EasyBus network. The EasyF modules require a
unique address for it. This address can be assigned to each
module manually or automatically by the Easy-MV2. The
following sections describe options for assigning addresses.
Scan with automatic addressing:
Master is in function
Hold down the programming key >3s
flashes
Press the programming key until " appears
Hold down the programming key >3s
flashes three times
Hold down the programming key >3s
appears (flash frequency of the point 2x)
If required, select the desired number
bypressingthekey
Hold down the programming key >3s
appears (flash frequency of the point 1x)
If required, select the desired number
bypressingthekey
Hold down the programming key >3s
7-segmentdisplaygoesoutbriefly
" flashes during the scan
After a successful scan, the EasyS-MV2 switches to the
corresponding Modbus status 0 or 1.
If several networks in a building have been
set up, the corresponding channels of
EasyS-MV2 must be adjusted
correspondingly. The channels 01 to 99 are
available.
If no module on the selected channel
is found, the master cannot switch to the
status "1". A new scan with the correct channel leads to a
successful scan of the network.
It is further recommended that the other EasyBus networks
are switched off during a
scan.
Scan without self-addressing
If an EasyBus network has already been set up and addresses
have been assigned to the modules, the EasyBus network is
scanned, but the EasyS-MV2 does not set address.
Master is in function
Hold down the programming key >3s
flashes
Press the programming key until " appears
Hold down the programming key >3s
flashes three times
Hold down the programming key >3s
appears (flash frequency of the point 2x)
If required, select the desired number
bypressingthekey
Hold down the programming key >3s
appears (flash frequency of the point 1x)
If required, select the desired number
bypressingthekey
Hold down the programming key >3s
7-segmentdisplaygoesoutbriefly
" flashes during the scan
After a successful scan, the EasyS-MV2 switches to the
corresponding Modbus status 0 or 1.
If several networks in a building have been
set up, the corresponding channels of
EasyS-MV2 must be adjusted
correspondingly. The channels 01 to 99 are
available.
If no module on the selected channel is found,
the master cannot switch to the status "1". A new scan with
the corresponding channel of the EasyF module causes the
master to switch to status 1.
It is further recommended that the other EasyBus networks
are switched off during channel change.

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Programming of EasyS-MV2 |
Construction subject to change
No return possible Version: 2017-11-13 | Page 12
Changing the channel
To prevent interference or influences between two or several
EasyBus networks, it is recommended to use different
channels for each network.
In this submenu, the channel of the previously scanned EasyF
modules can be changed from the switch cabinet without the
need to go to the module on site.
Master is in function
Hold down the programming key >3s
flashes
Press the programming key until appears
Hold down the programming key >3s
flashes three times
Hold down the programming key >3s
appears (flash frequency of the point 2x)
If required, select the desired number
bypressingthekey
Hold down the programming key >3s
appears (flash frequency of the point 1x)
If required, select the desired number
bypressingthekey
Hold down the programming key >3s
7-segmentdisplaygoesoutbriefly
" flashes briefly
The display goes out briefly and then the master switches to
the corresponding Modbus status.
If several networks in a building have been
installed, the corresponding channels of
EasyS-MV2 must be adjusted
correspondingly. The channels 01 to 99 are
available.
It is further recommended that the other EasyBus networks
are switched off during channel change.
Activation of positive opening operation:
This function can be activated only for modules with assigned
addresses and after a successful scan.
Master is in function
Hold down the programming key >3s
flashes
Press the programming key until appears
Hold down the programming key >3s
flashes three times and remains then visualised
EasyBus users go to the open position
Deactivation of positive opening operation:
Positive opening operation is active
Hold down the programming key >1s
appears
The deactivation functions only for
modules detected during a scan and having
an address.
The hardware contact is not deactivated.
Configuration of the Modbus parameters
At the EasyS-MV2, the Modbus interface can be
parameterised. The following values are set ex works:
Modbus address: 1
Baud rate 2 (19200 baud)
Parity 2 (pair)
Stop bit 2
Channel 01
Address entry
Speed entry
Parity entry
Time out entry
Display "b"
Display "A"
Display "b"
Display "P"
Display "t"

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Programming of EasyS-MV2 |
Construction subject to change
No return possible Version: 2017-11-13 | Page 13
In the Modbus submenu, briefly press the programming key
to select the submenu items
- "A" (Modbus address)
- „b“ (baud rate)
- "P" (parity)
- "t" (time out)
and hold down the programming key for a long period (>3s)
to display and adjust the corresponding settings. To confirm
the entry, hold down the programming key (>3s) until the
corresponding parameter has been completely set (max. 3
digits). Afterwards, the following submenu items "b", "P" and
"t" and their specific settings must be confirmed by holding
down the programming key (>3s). After that, the 7-segment
display goes out, the master restarts and switches to the
status display.
Place 100 10 1
7-
segment
display
•
•
•
Flash
frequency
3x 2x 1x
Example of procedure for changing the Modbus address from
001 to 005
Master is in function
Hold down the programming key >3s
flashes
Press the programming key until appears
Hold down the programming key >3s
appears
Hold down the programming key >3s
appears (flash frequency of the point 3x)
Hold down the programming key >3s
appears (flash frequency of the point 2x)
Hold down the programming key >3s
appears (flash frequency of the point 1x)
Press the programming key until a
isdisplayed
Hold down the programming key >3s
flashes
If no further changes to other submenu items must be carried
out, the programming can be finished at this point. After a
few seconds, the master will switch to the status display, the
change has been applied.
If changes must be also made to the submenus "b" (baud
rate), "P" (parity) and "t" (time out), they can be carried out
analogous to the Modbus address change.
Submenu Factory
setting
Number
of digits
Possible
values
Explanation
001 3
001 to
247
2 1
1 9600 baud
2 19200 baud
3 38400 baud
4 57600 baud
5 115200 baud
2 1
1 None
2 Even
3 Odd
01 2
01 to 99 *10s

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Circuit diagram for an Easy network |
Construction subject to change
No return possible Version: 2017-11-13 | Page 14
CIRCUIT DIAGRAM FOR AN EASY NETWORK

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Circuit diagram for an Easy network |
Construction subject to change
No return possible Version: 2017-11-13 | Page 15

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Circuit diagram for an Easy network |
Construction subject to change
No return possible Version: 2017-11-13 | Page 16

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Circuit diagram for an Easy network |
Construction subject to change
No return possible Version: 2017-11-13 | Page 17

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Modbus register |
Construction subject to change
No return possible Version: 2017-11-13 | Page 18
MODBUS REGISTER
READ REGISTER OF EASY-MV2
WRITE REGISTER OF EASYS-MV2
Modbus
Address Value
0Stop
1Run
2Scan
3fire
4 All open slave
Quantity of slave 1 0-128
Quantity error of slave 2 0-128
Fire 3 0-1 1 = Fire
EasyBus cycle time 4 0-16000 [ms]
Firmware version 5 8xx In decimal
Channel 8 1-99
Read Analog (Function 4)
Status master 0
Modbus
Address Value
Write Analog (Function 16)
Control maste
r
01Run
3Fire

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Read and write register of EasyF-ADC and -AAC |
Construction subject to change
No return possible Version: 2017-11-13 | Page 19
READ AND WRITE REGISTER OF EASYF-ADC AND -AAC
Eas
y
Bus Modbus RTU
Eas
y
Bus Modbus RTU
Address Read (bits) -
status Address Write (bits) - control
F O C E S
1
300
3 2 1 0 1
300
0
2 7 6 5 4 2 1
3 11 10 9 8 3 2
4 15 14 13 12 4 3
5
301
3 2 1 0 5 4
6 7 6 5 4 6 5
7 11 10 9 8 7 6
8 15 14 13 12 8 7
9
302
3 2 1 0 9 8
10 7 6 5 4 10 9
11 11 10 9 8 11 10
12 15 14 13 12 12 11
13
303
3 2 1 0 13 12
14 7 6 5 4 14 13
15 11 10 9 8 15 14
16 15 14 13 12 16 15
17
304
3 2 1 0 17
301
0
18 7 6 5 4 18 1
19 11 10 9 8 19 2
20 15 14 13 12 20 3
21
305
3 2 1 0 21 4
22 7 6 5 4 22 5
23 11 10 9 8 23 6
24 15 14 13 12 24 7
25
306
3 2 1 0 25 8
26 7 6 5 4 26 9
27 11 10 9 8 27 10
28 15 14 13 12 28 11
29
307
3 2 1 0 29 12
30 7 6 5 4 30 13
31 11 10 9 8 31 14
32 15 14 13 12 32 15
33
308
3 2 1 0 33
302
0
34 7 6 5 4 34 1
35 11 10 9 8 35 2
36 15 14 13 12 36 3
37
309
3 2 1 0 37 4
38 7 6 5 4 38 5
39 11 10 9 8 39 6
40 15 14 13 12 40 7
41
310
3 2 1 0 41 8
42 7 6 5 4 42 9
43 11 10 9 8 43 10
44 15 14 13 12 44 11
45
311
3 2 1 0 45 12
46 7 6 5 4 46 13
47 11 10 9 8 47 14
48 15 14 13 12 48 15
E = Erro
r
C = Close
O = Open
F = Smoke detecto
r
S = Control fire dampe
r

EasyBus - Signalling and Switching Bus System
Installation, Operating and Maintenance Instructions
Read and write register of EasyF-ADC and -AAC |
Construction subject to change
No return possible Version: 2017-11-13 | Page 20
49
312
3 2 1 0 49
303
0
50 7 6 5 4 50 1
51 11 10 9 8 51 2
52 15 14 13 12 52 3
53
313
3 2 1 0 53 4
54 7 6 5 4 54 5
55 11 10 9 8 55 6
56 15 14 13 12 56 7
57
314
3 2 1 0 57 8
58 7 6 5 4 58 9
59 11 10 9 8 59 10
60 15 14 13 12 60 11
61
315
3 2 1 0 61 12
62 7 6 5 4 62 13
63 11 10 9 8 63 14
64 15 14 13 12 64 15
65
316
3 2 1 0 65
304
0
66 7 6 5 4 66 1
67 11 10 9 8 67 2
68 15 14 13 12 68 3
69
317
3 2 1 0 69 4
70 7 6 5 4 70 5
71 11 10 9 8 71 6
72 15 14 13 12 72 7
73
318
3 2 1 0 73 8
74 7 6 5 4 74 9
75 11 10 9 8 75 10
76 15 14 13 12 76 11
77
319
3 2 1 0 77 12
78 7 6 5 4 78 13
79 11 10 9 8 79 14
80 15 14 13 12 80 15
81
320
3 2 1 0 81
305
0
82 7 6 5 4 82 1
83 11 10 9 8 83 2
84 15 14 13 12 84 3
85
321
3 2 1 0 85 4
86 7 6 5 4 86 5
87 11 10 9 8 87 6
88 15 14 13 12 88 7
89
322
3 2 1 0 89 8
90 7 6 5 4 90 9
91 11 10 9 8 91 10
92 15 14 13 12 92 11
93
323
3 2 1 0 93 12
94 7 6 5 4 94 13
95 11 10 9 8 95 14
96 15 14 13 12 96 15
97
324
3 2 1 0 97
306
0
98 7 6 5 4 98 1
99 11 10 9 8 99 2
100 15 14 13 12 100 3
101
325
3 2 1 0 101 4
102 7 6 5 4 102 5
103 11 10 9 8 103 6
104 15 14 13 12 104 7
This manual suits for next models
11
Table of contents
Popular Control Unit manuals by other brands

Elmo
Elmo VILLEGGIO user manual

Paradox
Paradox Digiplex EVO PRT3 Programming instructions

Glowworm
Glowworm Ultracom 24cx instructions

Abus
Abus ESMO50001 Installation instructions and user guide

Electronics
Electronics 250-N instruction manual

CleaverBrooks
CleaverBrooks CB780E Installation and operating instructions