Security Chimneys CAX1 User manual

1
INSTALLATION
INSTRUCTIONS
1" air Double Wall for Special Gas Vent
Category I, II, III, and IV Applications.
5”to 36”DiameterVent for use on Positive, Neutral and Negative Pressures
up to 35”W.C.
This installation manual will enable you to obtain a safe, ecient and dependable
installation of this vent system. Please read and understand these instructions
before beginning your installation.
Do not alter or modify the components of this chimney system under any circum-
stances. Any modication of alteration of the vent system or approved accesso-
ries, including but not limited to the appliance it is connected to, may void the
warranty, listings and approvals of this system and could result in an unsafe and
potentially dangerous installation.
A. Examine all components for possible shipping damage prior to installation.
B. Proper joint assembly is essential for a safe installation. Follow these
instructions exactly as written: Check severeness of joints upon completion of
assembly.
C. This venting system must be free to expand and contract.This venting system
must be supported in accordance with these instructions.
D. Check for unrestricted vent movement through walls, ceilings, and roof
penetrations.
E. Dierent manufacturers have dierent joint systems and adhesives. Do not mix
pipe, ttings, or joining methods from dierent manufacturers.
WARNINGS
FAILURE TO FOLLOWTHESE INSTALLATION INSTRUCTIONS COULD CAUSE FIRE,
CARBON MONOXIDE POISONING, OR DEATH. IF YOU ARE UNSURE OF INSTALLA-
TION REQUIREMENTS, CALLTHE PHONE NUMBER LISTED ONTHE BACK OF THESE
INSTRUCTIONS.
A MAJOR CAUSE OF CHIMNEY RELATED FIRE IS FAILURETO MAINTAIN REQUIRED
CLEARANCES (AIR SPACES)TO COMBUSTIBLE MATERIALS. IT IS OF UTMOST IM-
PORTANCE THATTHIS VENT SYSTEM BE INSTALLED ONLY IN ACCORDANCE WITH
THESE INSTRUCTIONS
PI HYBRIDCAX1 LS470 REV. 00 08-08-19
Listed to standards:
UL-1738
ULC-S636 Type ‘‘BH’’ vent
Report #
SAVE THESE INSTRUCTIONS
FOR FUTURE REFERENCE
MODEL CAX1-(BC) (5" TO 36")

2
TABLE OF CONTENTS
SECTION A:
General Information for All MODELS
CAX1-(BC)
Introduction................................................................... page 2
Testing/ listing information............................................ page 2
Part numbers ................................................................. page 3
Eective length.............................................................. page 3
Clearances to combustibles ........................................... page 3
General installation requirements ................................. page 4
Chimney weight ............................................................ page 4
Support methods and height......................................... page 5
Guying and Bracing........................................................ page 5
Horizontal installation requirements ............................. page 6
Vertical installation requirements ................................. page 6
Roof/oor penetration .................................................. page 7
Maintain proper slope ................................................... page 7
Wall penetration ........................................................... page 7
Condensate drains ......................................................... page 8
SECTION B:
Specic Information for Model CAX1-(BC) (5" to 36")
Typical Installation ........................................................ page 9
Guying and Bracing ....................................................... page 10
Joint Assembly .............................................................. page 11
Straight Sections ........................................................... page 12
Installation steps forVariable Length (LV)
............................ page 13
CAPS .............................................................................. page 15
Elbows ........................................................................... page 15
Oset ............................................................................ page 16
Adapters ........................................................................ page 16
Supports ........................................................................ page 17
Ventilated Anchor Plate with Length ............................. page 18
Heavy Duty Wall Support .............................................. page 19
Heavy Duty Wall Guide .................................................. page 20
Full Angle Ring .............................................................. page 20
Half Angle Ring ............................................................. page 20
Location of supports ...................................................... page 21
Flashings and Storm Collar ............................................ page 22
Maintenance instructions .............................................. page 23
Warranty & Product Reference information ................... page 23
SECTION A:
GENERAL INFORMATION FOR ALL MODEL
CAX1-(BC)
INTRODUCTION
CAX1-(BC) double wall (5"TO 36") is a special stainless steel vent system
for gas red appliances listed as Category I, II, III, and IV in USA UL
1738 or in Canada asType BH Gas Venting as noted in ULC-S636, with
a maximum operating temperature of 480°F (250°C), and a maximum
rated positive pressure of 35” water column. Must be installed by an
experienced professional familiar with the operation and maintenance of
heating appliances and venting. Before installing this product, examine
all components for possible shipping damage and read the complete
installation manual.
Failure to follow proper installation procedures, including vent pitch and
improper appliance connections, may cause unsafe conditions. Security
Chimneys International Limited recommends the system to be inspected
once a year by a qualied service technician.
TESTING/LISTING INFORMATION
Security Chimney International, Ltd. Model CAX1-(BC) (5" TO 36") venting
system is listed with Intertek Testing Services (ETL) to UL/ULC standards:
U.S.A.
• UL-1738
Special Gas Category I, II, III
and IV appliances
This product must be installed in accordance with local building code
requirements as well as national codes: USA - National Fuel Gas code AN-
SI-Z223.1 or NFPA Standard 54, or NFPA 211. CANADA - CAN/CSA B-149.1
Natural Gas and Propane Installation code as applicable.
CANADA
• ULC-S636
Type BH GasVent Class I/II

3
PART NUMBERS
These instructions identify major model CAX1-(BC) parts by name and
part number.
Example:
CAX1 36” length with inside diameter 14”made of SS 316 inner ue
and SS 304 outer casting.
CAX1 30° elbow with inside diameter 22”made of 316L and SS 304
Outer Casing.
CAX1 wall support for 8”diameter chimney made of stainless 439.
Use only factory-supplied components. Failure to do so will void
the certication and the warranty of the chimney system.
EFFECTIVE LENGTH
CAX1-(BC) (5" to 36")
The eective length is the length of the part when it is
assembled.
Example:
CAX1 14 L36 BC
Model Dia. Part Material
CAX1 22 E30 BC
Model Dia. Part Material
CAX1 8 WSHD P
Model Dia. Part Material
Eective Length
L36 »36-1/8”
L24 »24-1/8”
L18 »17-5/8”
L12 »11-5/8”
CLEARANCES TO COMBUSTIBLES
Table 1 shows the required MINIMUM AIRSPACE CLEARANCE TO COMBUSTIBLES.
“Combustibles”include framing lumber, drywall, plywood, paneling, insulation,
wiring, and other building materials.
Auxiliary parts such as combination Roof Supports, RoofThimble, Flashings, and
Wall Thimble outer shields are intended to be attached directly to the framing
or to ceilings, oors, or walls in accordance with their respective instructions.
These parts, which are installed in contact with wood or other combustibles, are
designed and tested to assure that they do not overheat at points of contact.
NOTES:
1. Unenclosed requires at least two sides open.
2. Reduced clearances may be attained by using non-combustible enclosures.
3. Combustible material is any material made of or surfaced with wood,
compressed paper, plant bers, or other materials that are capable of being
ignited or burned. Such material shall be considered combustible even
though it is ame-proofed, re-retardant treated, or plastered.
(Source: NFPA 54/ANSI Z223.1)
4. Design any enclosure to permit inspection of the system.
5. Do not place insulation in any required clearance spaces surrounding the
vent system unless these instructions suggest otherwise and the insulation
is specied or supplied.
6. When using Viton caulking, follow the manufactures required drying times.
Minimum Clearance to Combustibles Double Wall CAX1-(BC)
Diameter
Rated
Operating
Temp
Max
Operating
Temp
Enclosed
(4 sides)
Unenclosed
(2 sides max.)
Horiz. Vert. Horiz. Vert.
5”to 36” 480°F
(250°C)
550°F
(288°C) N/A 2” 6” 2”
Table 1 - Minimum Clearances to Combustible for CAX1-(BC)
Material Code Designations
B Type 316 Stainless Steel
C Type 304 Stainless Steel
P Type 439 Stainless Steel

4
GENERAL INSTALLATION REQUIREMENTS
When venting Category I, II, III, or IV appliances or CAX1-(BC) must be
used for the entire length of the system. Do not mix pipe, ttings, or
joining methods from dierent manufacturers. See the catalog for
a complete list of parts and products. Every vent system must
be planned and installed for optimum performance and safety.The
venting system must be free to expand and contract and must be sup-
ported in accordance with these instructions (Check for unrestricted
vent movement through walls, ceilings, and roof penetrations). Refer
to the gas appliance manufacturer’s instructions to determine venting
requirements and limitations with respect to installation and use of
the appliance. It is the responsibility of the installer to contact
local building and re ocials concerning any installation
restrictions and/or inspection requirements that may apply.
Permits may be required before starting an installation.
• If required by the appliance manufacturer, a DrainTee Cap must be
located as close as possible to the appliance ue outlet. Depending
on the arrangement of the vent, more than one drain may be
required. Unless a DrainTee Cap is supplied with the appliance, install
a CAX1-(BC) Drain Tee Cap.
• More than one Category II, III, IV appliance may not be connected into
the same vent system, unless the appliance manufacturer specically
approved such a system and the appliance are designed for multiple
venting. Cat. II, III or IV appliances MAY NOT be common vented with
Cat. I, natural draft appliances. This limitation can be removed if an
engineering analysis demonstrates normal and safe operation of
appliances.
• CAX1-(BC) must not come in contact with plumbing or electrical
systems.
• Maintain rated clearances to combustibles over the entire length of the
vent system.
• CAX1-(BC) shall not be routed into, through, or within any vent, such
as an existing masonry or factory-built chimney, that is connected to
another appliance.
CHIMNEY WEIGHT
Chimneyweightisgiveninpoundsper foot for eachdiameter. Itisimportant
to know the weight of the chimney section for chimney support or guiding.
Chimney weight (table 2) along with the maximum chimney height
(table 3) is necessary to calculate the proper anchor strength needed with
supports.
CHIMNEY WEIGHT IN LB/FT
INSIDE DIAMETER (in) CAX1-(BC)
5 3.5
6 4.1
7 4.8
8 5.5
9 6.2
10 6.9
11 7.6
12 8.3
13 9.0
14 9.7
16 11.0
18 12.4
20 13.8
22 15.2
24 16.6
26 17.9
28 19.3
30 20.7
32 22.1
34 23.5
36 24.8
Table 2- Chimney weight for CAX1-(BC)
Example: Model CAX1-(BC) 6” diameter section of 25 feet in length, weight in lb/ft = 4.1.
Total length 4.1 x 25 = 102.5 lbs.
GENERAL INFORMATIONS FOR SUPPORTS AND GUIDES
1. Severalsupportandguidingmethodsareusedtoanchorachimneyagainst
upward, downward and angular placement.
2. These supports and guides prevent bending stresses on the chimney
elbows and joints.
3. Certain limitations apply for proper installation of supports and guides.
For supports, seeTable 3, and for Distance between Guides/supports, see
Table 4.
4. ForTypical installation, see Figure 5.

5
GUYING AND BRACING
1. Proper guying and bracing is essential for part of the vent that extends
above the roof or parapet wall.The vent at this point is subject to wind
conditions and needs special attention for proper stabilization. See Figure 6.
2. If the vent above the roof does not exceed dimension H, no special
guying or bracing is required. However, to protect the ashing from lateral
movement, a guide must be installed at the roof level. See Figure 6.
3. For vent height above the roof that needs guying or bracing, a support, a
small length and a expansion length must be installed near the roof level to
absorb the thermal expansion and minimize this eect on the guy wire or
brace.
4. When using guy wire, the cable must be slightly slack or loose to allow
thermal expansion.
5. When using rigid bracing, the maximum vertical height between supports
must be reduced to 5’to compensate thermal expansion.
MAXIMUM HEIGHT LIMITS FOR EACH TYPE OF SUPPORT FOR MODEL CAX1BC
Parts Flue Diameter
Ø (in) Height (ft)
Anchor Plate (AP)
(For non-combustible application only)
Ø5 to Ø22 133
Ø24 to Ø36 82
Anchor Plate with Length (APL)
(For non-combustible application only)
Ø5 to Ø22 142
Ø24 to Ø36 87
Anchor Plate Ventilated
(APV)
Ø5 to Ø22 133
Ø24 to Ø36 82
Anchor plate with length (APVL) Ø5 to Ø22 142
Ø24 to Ø36 87
Base supportedTee (T90 or T45)
Ø5 to Ø22 52
Ø24 to Ø36 32
Wall Support Heavy Duty (WSHD) Ø5 to Ø22 53
Ø24 to Ø36 32
Table 3 : Maximum Height Limits for each Type of Support for CAX1-(BC)
MVS : MaximumVertical Spacing between Guides/Supports
MHS: Maximum Horizontal Spacing between Guides/Supports
MDE: Maximum Distance between Elbows
H: Maximum Freestanding Height above the Roof
S: Maximum Suspended Length
SUPPORT AND GUIDE SPACING FOR MODEL CAX1-(BC)
Inside
diameter
(in)
MVS
MHS (ft) MDE (ft) H (ft) S (ft)
Interior (ft.) Exterior (ft)
5 10 8 12 12 10 50
6 10 8 12 12 10 50
7 10 8 12 12 10 50
8 10 8 12 12 10 50
9 10 8 12 12 10 50
10 10 8 12 12 10 50
11 10 8 12 12 10 50
12 10 8 12 12 10 50
13 10 8 12 12 10 50
14 10 8 12 12 10 50
16 10 8 12 12 10 50
18 10 8 12 12 10 50
20 10 8 12 12 10 50
22 10 8 12 12 10 50
24 10 8 12 12 10 50
26 20 20 15 15 13 50
28 20 20 15 15 13' 6" 50
30 20 20 15 15 13' 9" 50
32 20 20 15 15 14' 3" 50
34 20 20 15 15 14' 6" 50
36 20 20 15 15 15 50
Table 4: Support and Guide Spacing for Model CAX1-(BC).

6
HORIZONTAL INSTALLATION REQUIREMENTS
• Whenventingthroughasidewall,terminatethesystemnotlessthan12”
(.3m) above the ground and above the snow line in geographical areas
where snow accumulates. The termination area must be kept clear of
snow and ice at all times. See Figure 1.
• Terminate the system at least 7’ (2.1m) above a public walkway or
driveway, no less than 6’(1.8m) from the combustion air intake of any
appliance or 3’(.9m) from any other building opening, gas utility meter,
service regulator or the like. Less distance is permitted if specied in
the appliance’s installation instructions. It also shall terminate at least
3’(.9M) above any forced air inlet within 10’(3.1m) and shall terminate
at least 4’(1.2m) below, 4’horizontally from, or 1’(.3m) above any door,
window, or gravity air inlet into any building as provided in the National
Fuel Gas Code ANSI Z223.1 and NFPA 54. See Figure 1. Proper judgment
may require greater distances depending on the side of the equipment
installedortoallowforsnowdriftingorfallingfromfallingfromoverhead
roofs or trees. The termination should be far enough away from trees,
shrubs, or decorative items to prevent damage.
• Thetotalhorizontalventlengthfromtheapplianceuecollartotheoutside
termination shall be in accordance with the appliance manufacturer’s
instructions.
Figure 2-Vertical Installation Requirements
VERTICAL INSTALLATION REQUIREMENTS
1. The vent system must terminate at least 3 feet above the roof line and
at least 2 feet higher than any portion of the building within 10 feet.
See Figure 2. This limitation can be removed if an engineering analysis
demonstrates normal and safe operation of appliance.
2. When terminated at a height of more than 10 feet, the stack must be
supported by a Guy Section.
3. TheventsystemmustterminatewithoneoftheCAX1-(BC)terminations.
Except;
a) Category I appliances (natural draft) must use a Rain Cap. It is
optionalonCategoryII. Thislimitationcanberemovedifanengineer-
ing analysis demonstrates normal and safe operation of appliance.
b) Vent systems without provisions for draining rain water must use a
Rain Cap.
c) Terminations or approved mechanical vent devices specied or
provided by the appliance manufacturer are permitted.
4. The total continuous distance of the vent system from the appliance ue
collar to the termination shall not exceed that specied in the appliance
manufacturer’s installation instructions. When venting natural draft
appliancestheterminationmustbeatleast5feetabovethetopmostdraft
hood. Otherwise a listed mechanical draft inducing device is required.
This limitation can be removed if an engineering analysis demonstrates
normal and safe operation of appliance.
5. In cold climates do not install a condensate drain on the exterior of the
building. Doingsomayresultindangerousicyconditionsonsurfacesnear
the drain and may cause damage to the vent system and/or the building
exterior. SecurityChimneyswillNOTbeheldliableforanypersonalinjury
or property damage due to any formation of ice.
6. Vertical supports are required after every transition to vertical. Vertical
supports are also required after every oset elbow.
7. Unless CAX1-(BC) is installed in a re rated shaft, a roof thimble and
support is required when penetration re rated oors, walls or ceilings.
2 ft. above structures within 10 ft.
7 ft above
public
walkways and
drives
1 ft. above doors and windows
4 ft below any window
or fresh air inlet
1 ft. above ground or
snow line
Sidewalk
Figure 1 - Horizontal Termination Requirements
4 ft. horizontally from door and
windows
10’
2’

7
MAINTAIN PROPER SLOPE
• Install with a continuous 1/4” per foot (minimum) slope, as is required
by the National Fuel Gas Code for all gas-red appliances.
• Vent systems for condensing appliances must have a continuous 1/4”
per foot (minimum) slope toward the appliance or a condensate drain.
Always check the appliance manufacturer’s instructions for proper drain
requirements.
• CAX1-(BC) oers a range of tees and elbows that are built incorporating
a 2 degree slope, we recommend that you use these to generate your
slope.
• Some appliances require the venting system to be sloped toward the
horizontal termination.
• Remember,ifyouraisetheapplianceorlowertheceilingyoumustadjust
the slope of the vent to maintain the 1/4”per foot minimum. See Figure
5 & 26.
ROOF / FLOOR PENETRATION
1. A roof thimble (RT) or roof thimble insulated (RTI) for cold climate must
be installed every time the vent system passes through a oor or roof.
2. Prepare the roof / oor by cutting a square opening. See Table 5.
3. Install the roof thimble. You may cut the radiation sleeve if it is too long.
See Figure 3.
4. For roof installation, install a ashing.
Support or Guide
Roof thimble
Opening dimension See Table 5 for
all Models
Air gap
or insulated
Flashing
Figure 3 - Roof penetration
Figure 4 -Wall Penetration
Wall Thimble
(WT/WTI)
Air gap or insulated Two half plate
Termination
Add sealant
Opening dimension
Table 5 for opening
for all Models
2”Minimum overlap
WALL PENETRATION
1. Prior to installation, determine proper location of wall thimble (WT) or
wall thimble insulated (WTI) so that a minimum slope of 1/4” (6mm)
per foot is maintained in the horizontal section of vent to ensure proper
ow of condensation.
2. Prepare the wall by cutting a square opening. See Table 5 for opening
for all Models.
3. Install the wall thimble by inserting the larger of the two parts on the
appliance (interior side). See Figure 4.
4. Next, apply a bead of sealant around the edges of the exterior (smaller
of the two parts) wall thimble component. Then install this part of the
wall thimble by inserting the smaller collar into the other component
from the previous step.
NOTE: The two horizontal cylinders of the thimble must engage a
minimum of two inches.
5. Fasten both sides of the wall thimble using screws or nails.
6. Once the thimble is installed, vent pipe can be inserted into the thimble.
7. Close the gap between the thimble and the vent by installing the two
half plate and fasten it using screws or nails.
8. Install horizontal termination to complete the assembly.
9. Once assembly is completed, apply a bead of high-temp sealant around
thepipeandtheexteriortwohalfplatesofthethimbletoprotectagainst
weather.
10. Theairgapislledwithinsulationwhenusingtheinsulatedwallthimble
(WTI).

8
OPENING DIMENSIONS FOR WALL/ROOF PENETRATION
FOR MODEL CAX1-(BC)
Inside
Diameter
(in)
Wall Thimble
(WT)
Wall
Thimble
Insulated
(WTI)
Roof
Thimble
(RT)
Roof
Thimble
Insulated
(RTI)
5 19 x 19 19 x 19 11 x 11 11 x 11
6 20 x 20 20 x 20 12 x 12 12 x 12
7 21 x 21 21 x 21 13 x 13 13 x 13
8 22 x 22 22 x 22 14 x 14 14 x 14
9 23 x 23 23 x 23 15 x 15 15 x 15
10 24 x 24 24 x 24 16 x 16 16 x 16
11 25 x 25 25 x 25 17 x 17 17 x 17
12 26 x 26 26 x 26 18 x 18 18 x 18
13 27 x 27 27 x 27 19 x 19 19 x 19
14 28 x 28 28 x 28 20 x 20 20 x 20
16 30 x 30 30 x 30 22 x 22 22 x 22
18 32 x 32 32 x 32 24 x 24 24 x 24
20 34 x 34 34 x 34 26 x 26 26 x 26
22 36 x 36 36 x 36 28 x 28 28 x 28
24 38 x 38 38 x 38 30 x 30 30 x 30
26 40 x 40 40 x 40 32 x 32 32 x 32
28 42 x 42 42 x 42 34 x 34 34 x 34
30 44 x 44 44 x 44 36 x 36 36 x 36
32 46 x 46 46 x 46 38 x 38 38 x 38
34 48 x 48 48 x 48 40 x 40 40 x 40
36 50 x 50 50 x 50 42 x 42 42 x 42
Table 5: Opening Dimensions for Model CAX1-(BC).
Dimensions are in inches.
CONDENSATE DRAINS
When an internal condensate drain is NOT part of the appliance:
1. A Drain length (DL) or aTee with a drain tee cap (DTC) is strongly recom-
mended.Install this drainas closeas possibleto the applianceue collar.
2. A condensate drain is required for every 30 feet of horizontal vent and
at the bottom of a vertical stack.
3. Use the Drain length for a straight horizontal run. Rotate the tting so
that the drain tube is as vertical as possible.
4. Use aTee at a transition from horizontal to vertical, and attach the Drain
Tee Cap to the appropriate branch of the tee.
5. A condensate drain tube kit is available to direct the condensate to an
appropriate location. A trap loop must be formed into the drain hose
and must be a diameter that is at least four times the appliance’s rated
stack pressure in inches of water column or minimum 3 inches. Secure
the loop with a cable tie.
6. Flue gas condensate can have a low (3 to 5) PH level, follow all local and
national codes and regulations for the draining of acidic condensate.
7. In cold climate, do not install a condensate drain on the exterior of the
building.Doingsomayresultindangerousicyconditionsonsurfacesnear
the drain and may cause damage to the vent system and the building
exterior. Security Chimneys™ will NOT be held liable for any injury or
property damage due to formation of ice.

9
SECTION B
SPECIFIC INFORMATION MODEL CAX1BC 5”TO 36”
TYPICAL INSTALLATION FOR CAX1BC
°
V
°
°
Figure 5-Typical installation for CAX1-(BC)

10
4
4
3
4
4
6
MAXIMUM HEIGHT
SEE TABLE 3
4
7
• If Dimension“H”exceeds the value In theTable 7 & 8, use bracing
or cable guying to stabilize chimney section above the roof.
See Figure 6
Figure 6 - Height with rigid bracing or guying option for CAX1-(BC) Figure 7- Maximum freestanding Height for CAX1-(BC)
TYPICAL INSTALLATION FOR CAX1BC 5” TO 36”

11
EXPECTED NUMBER OF TUBES (11 oz) PER JOINT ASSEMBLY
(FOR S-2100, S-650, S-375 OR VITON) for CAX1-(BC)
Inner Duct Diameter (in) Number of Tubes Per Joint Assembly
5 to 10 1/5
11 to 16 1/4
18 to 22 1/3
24 to 28 1/2
20 to 36 3/4
TABLE 6 - Expected number of tubes (11 oz) ofViton® or S-650 per Joint
Assembly (depending of application) or S-375 for exterior weathering.
JOINT ASSEMBLY
All components have a male and female end: the male end has a Centering
Flue Extension and a black Viton® O-ring on it (bottom side).
CAUTION: Each section must have on its male end. If not, it may
impair the sealing eectiveness. For any VERTICAL installation (except for
Variable Length (LV), no need for caulking when using the O-ring. For any
HORIZONTAL installation, add a bead of Viton® caulking over theViton
O-ring to properly caulk.
NOTE: Diameter of the CAX1-(BC) shown in pictures for the installation
assembly are smaller then reality.
STEP 1:
Before installation, make sure there is a blackViton® O-ring on the Centering
Flue Extension.
STEP 2 (for HORIZONTAL installation only):
Only on Horizontal installation, add a bead of black Viton® caulking over the
Viton® O-ring.
NOTE: Sealant Caulking is supplied by Security and Individual tubes are
marked Fluorodyn Caulk VITON®. Codes are VITON-S for a tube of
2.5oz.or VITON-Lfor atube of 11oz. It mustbe ordered separately.
See Table 6 for number of tubes per joint.
STEP 3:
For an easier installation, place the Inner V-Band (BSIK) on the spacers
below the ange of the rst section. Join the two anged ends of the duct
section together until it squeeze theViton O-ring between both anges.
STEP 4:
Install the V-Band around the anges making sure the anges are located
within the V-Clamp.
NOTE: Do not locateV-Band hardware at the bottom side of horizontal
duct joints.
STEP 5:
Tighten the screws of the band.
NOTE: Light tapping with a hammer all around the band while
tightening bolts helps align and pull anges together.
STEP 6
Secure the Outer Casing with the Outer Band (BSE) and tighten the screws.
Joint Assembly Step 1
Joint Assembly Step 2
Joint Assembly Step 3
Joint Assembly Step 4-5
Joint Assembly Step 6

12
Figure 9- Horizontal Drain Length
STRAIGHT SECTIONS
VERTICAL DRAIN LENGTH DL
A Drain Section is used to drain water on vertical installation. It is a special
variation of an 18”pipe length with provision to drain rain or condensate
from the chimney. The pipe ue is equipped with an annular catch gutter
wall and a 1”(25) NPT nipple extending through the casing for attachment
of drain piping. See Figure 8 for details.The drain piping should include
a water leg of a height at least equal to the maximum expected operat-
ing pressure at the appliance outlet to avoid allowing ue gases to vent
through the drain. Drain Length should be installed indoors to prevent
freezing.
HORIZONTAL DRAIN LENGTH (HDL)
1. Horizontal Drain length is equipped with a 1” (25) NPT nipple, which is
attached to the inner ue and extends through the outer casing to provide a
path to drain, condensate or water from the chimney. See Figure 9.
2. A dam is attached to the inside of the inner ue adjacent to the nipple to
channel the euent to the drain.
3. The duct drain is intended for use at the end of a horizontal run where
access and drainage is needed (see Figure 9).
4.The drain coupling must be connected to a ”P”trap or approved container
(supplied by others).
Figure 10-Variable Length (LV)
Figure 11- Detail ofVariable Length
VARIABLE LENGTH (LV)
TheVariable Length (LV) has one major function. It makes up odd lengths
of duct. It must not be used for expansion compensation.
It is shipped with a anged retaining band assembly on the inner sliding
wall. See Figure 10.
The whole LV assembly includes:
• A sliding inner wall that t closely inside a standard pipe section and it is
anged on one side.
• An adjustable anged retaining band, composed of;
• Double anged sleeve
• Retaining anged collar
• An inner V-Band (BSI)
• A dierent Inner Band (BS)
• Split outer casing with anged half band on the top side only.
NOTE: Viton® caulking must be applied on each Variable Length (LV)
and must be supplied by Security Chimneys. Sealant must be
ordered separately (Not included in the LV assembly).
Figure 8-Vertical Drain Length

13
Flange to ange length adjustment can range from 7”x 281/2”
NOTE: If the ue is too long to t into the adjacent section of duct without
interfering with the ow path, it should be trimmed to desired ange
to ange length plus an overlap of 4”with the inner wall of the inlet
end duct section. The minimum overlap for the outer casing is 1”with
the inlet end section outer wall. (See Figure 12 & 14).
NOTE: If an LV joint must be joined to one of these ttings, the unanged
end of the tube should always point downward or towards downward
slope.
Figure 12 - Overlap Details forVariable Length
INSTALLATION STEPS FOR THE VARIABLE LENGTH (LV)
Step 1- Measure the distance X required for the variable length. See
Figure 13.
Figure 13-Step 1 for Installation of Variable length
Step 2 - Cut the inner wall at the dimension X found at the rst Step plus
4”. See Figure 14.
Step 3 - Cut the split outer casing on the opposite side of the anged half
at dimension X plus 1’’. See Figure 15.
Figure 14 -Step 2 -
Cut of the Sliding InnerWall
Figure 15 - Step 3 -
Cut of the Outer Casing
Cut Split Outer
casing to X + 1”
Cut Sliding Inner
Wall to X + 4”
Distance ”X”

14
Step 4 - Install the interior assembly between the two parts. Place the
adjustable anged band assembly toward the downstream section.
Step 5-Assemble the outlet end sliding innerwall to the outlet end section
as a regular section (See JOINT ASSEMBLY section). See Figure 16.
Step 6 - Before assembling the double anged sleeve to the inlet end
section, add a thin coat of sealant about 1”wide and a thin coat of
sealant at the unanged end of the LV joint whee the joint slides into
the mating duct section. Press sealant into any gap between the LV
and the mating joint section.
Step 7 -Assemble the inlet end ange assembly with the inlet end section
ange as a regular length installation (See JOINT ASSEMBLY section).
Step 8 - Apply thin layer of sealant inside the retaining collar, and also a
continuous bead of sealant at the collar overlap seam. See Figure 17.
Figure 16 -Step 4-5- Install the inner LV and secure the outlet end ange
Figure 17- Step 7-9- Secure the Double Flanged Sleeve
and seal the Retaining Flange Collar
Step 9 -Slide down the retaining band on the double anged sleeve to
mate their anges and tighten the retaining collar.
Step 10 -Then install the otherV-band (BSI) over these anges (like
regular joint assembly). See Figure 18.
Figure 18 - Step 10-11 - Secure the Retaining Flanged Band
Step 11 - Install the split outer casing that covers from the outer wall
of the inlet end section to the outerwall of the outlet end section. See
Figure 19.
Figure 19 - Step 12- Install the Split Outer Casing
Split Outer Casing

15
CAPS
TEE CAP (TC)
TheTee Cap provides access for cleaning and inspection. Usually on
horizontal runs, the Tee Cap is used to close the unused port of any Tee and
for clean out or access purposes only. When using clean-outs, always seal
the connection to prevent leaks.
The part list includes;
lx Cap with one Handle
lx smaller V-Band (BSI)
1x Outer Casing
1x LargerV-Band (BSI)
INSTALLATION PROCEDURES
STEP 1- (only for horizontal installation): AddViton® Caulking over the
Viton O-ring Gasket. See Figure 20.
Step 2 -Use the innerV-Band (BSI) to secure the inner Cap Kit to the ange
of the 90° Tee (T90, not included) as specied in the JOINT ASSEMBLY
section.
NOTE: Be sure the handle of the Cap faces outward as shown.
See Figure 20 or 21.
Figure 21: Step 2 for installation of the TC
DRAIN TEE CAP (DTC)
The DrainTee Cap (DTC) is used as a drain for the base of vertical
installations and must be connected to a suitable disposable point. It can
also be used as an access for clean outs or access purposes. (See Figure 23)
Same installation as a Tee Cap (TC).
ELBOWS
ELBOWS (E2, El5, E30, E43, E45, E88, E90)
Elbows are used for changes in direction in horizontal or vertical
portions of a system. All elbows feature the standard joint assembly as
described in JOINT ASSEMBLY section. Elbows are used in combination to
make dierent angles ranging from 2° to 90° in horizontal and vertical
segments of the system.
Elbows are not designed to take bending loads and must be structurally
supported. Structural parts such as posts or beams may also be needed to
hold chimney supports in position. See ELBOW SUPPORT section.
Figure 24: 3, 15, 30, 45 and 90° Elbow
Figure 20: Step 1 (only for Horizontal installation) Installation of the TC
Figure 23: DrainTee Cap (DTC)
Step 3 - Mate the ange of the outer casing with the ange of the out
wall of theTee section.
Step 4 - Secure with the bigger V-Band (BSI) by tightening the retaining
screw. See Figure 22.
Figure 22: Step 3-4 for installation of the TC

16
OFFSETS
1. The length of the oset is determined by strength considerations.The
maximum dimension between supports is given in Table 4, and is
applicable to all horizontal and sloped orientations. See Figure 26.
2. The minimum oset is accomplished with two elbows directly connected
to each other (see Figure 25 and Table 7).
3. With frequent re-support, there is no structural or operating limit to the
length of horizontal or sloped portions, providing the system meets
the capacity, pressure drop of available equipment.
4. The carrying capacity of supports and their structural attachments
must take into account the weight of the oset plus whatever vertical
section is carried by that support.
5. Height limits for supports are tabulated inTable 3.
6. The vertical sections above the oset must also be supported or
anchored and guided where necessary.
7. Anchor PlateWall Support (WSHD) andWall Guide (WGHD) may be used
in a variety of ways for oset support to achieve the structural stability
of the system.
8. Re-supports must be securely anchored to walls, posts, or locally
fabricated rigid framework. This framework must be designed to
assure stability of supports, such as Ventilated anchor Plate (APV)
supports and Heavy Duty Wall Supports (WSHD).
9. Supports suspended by threaded rods or from small size angles or straps
are usually not satisfactory to resist bending moments due to osets.
Figure 26: Maximum Spacing
between supports for Oset
ADAPTERS
TAPERED INCREASER (TIN)
TheTapered Increaser Adapter is used for a diameter change in duct
system. Uses when there is a sucient length for duct run available for the
size change.The TIN is used uses 2”of length per 1“increment diameter
change.The TIN is considered to have the same load strength as a straight
duct. See Figure 27.
Figure 27:Tapered Increaser Adapter (TIN)
ECCENTRIC TAPERED INCREASER (ETIN)
The EccentricTapered Increaser Adapter is similar as the Tapered Increaser
Adapter except the smaller diameter is oset from the larger diameter.
When installed horizontally, the ETIN keep a at slope unlike the TIN.
See Figure 28.
Figure 28: EccentricTapered Increaser (ETIN)
Figure 25: Minimum Oset for each Elbows
MINIMUM ELBOW OFFSET FORTWO (2) ELBOWS CAX1-(BC)
Flue Diameter
Ø (in.) 2° 3° 15° 30° 45° 88° 90°
5 1/2 1/2 2 1/2 5 1/4 8 1/4 18 1/4 18 1/2
6 1/2 1/2 2 1/2 5 3/8 8 1/2 19 1/4 19 1/2
7 1/2 1/2 2 5/8 5 1/2 8 3/4 20 1/8 20 1/2
8 1/2 1/2 2 5/8 5 3/4 9 1/8 21 1/8 21 1/2
9 1/2 1/2 2 5/8 5 7/8 9 3/8 22 1/8 22 1/2
10 1/2 1/2 2 5/8 6 9 5/8 23 23 1/2
11 1/2 1/2 2 3/4 6 1/8 10 24 24 1/2
12 1/2 1/2 2 3/4 6 1/4 10 1/4 25 25 1/2
13 1/2 1/2 2 3/4 6 3/8 10 1/2 26 26 1/2
14 1/2 1/2 2 3/4 6 1/2 10 7/8 26 7/8 27 1/2
16 1/2 1/2 2 7/8 6 3/4 11 3/8 28 7/8 29 1/2
18 1/2 1/2 3 7 12 30 3/4 31 1/2
20 1/2 1/2 3 7 1/4 12 5/8 32 3/4 33 1/2
22 1/2 1/2 3 1/8 7 5/8 13 1/8 34 5/8 35 1/2
24 1/2 1/2 3 1/8 7 7/8 13 3/4 36 5/8 37 1/2
26 1/2 1/2 3 1/4 8 1/8 14 3/8 38 1/2 39 1/2
28 1/2 1/2 3 1/4 8 3/8 14 7/8 40 1/4 41 1/2
30 1/2 1/2 3 3/8 8 5/8 15 1/2 42 3/8 43 1/2
32 1/2 1/2 3 3/8 8 7/8 16 1/8 44 1/4 45 1/2
34 1/2 1/2 3 1/2 9 1/8 16 3/4 46 1/4 47 1/2
36 1/2 1/2 3 1/2 9 1/2 17 1/4 48 1/8 49 1/2
TABLE 7- Minimum Oset for Each Elbow for CAX1-(BC)
Dimensions are in inches
Table 4

17
SUPPORTS
PLATE AND WALL SUPPORT
Ventilated Anchor Plate (APV)
Anchor Supports are designed to provide support to vertical sections
and provide xed-point support for horizontal sections. See Figure 29.
NOTE: Rings installed at 90° to plates.
Figure 29: -Ventilated Anchor Plate for Combustible material
The Plate Support must be attached to the building structure or supported
with rigid structural members. See Table 3 for maximum supported height.
For maximum support, the entire perimeter of the Plate Support must be
attached to structural framing. Structural members are supplied by the
installer. See Figure 30 and 31.
Figure 30: -Ventilated Anchor Plate on a Framework
Figure 31: Detail of theVentilated Anchor Plate on a Framework.
Supported duct sections in a vertical position must be braced with
diagonal members or gussets to prevent deection of the supported joint
as shown in Figure 31. ”X”is a minimum of 30°.
Plate Supports are usually located adjacent to ttings, such as tees or
elbows, to protect tting from expansion stresses. Table 8 shows Plate
Support, bracing and framework requirements for duct size ranges.
NOTE: If bracing is used, minimum“X”angle is 30°. If there is no
bracing, the framework must be attached to structural members
to provide equivalent rigidity.
Figure 32: - Anchor Plate Horizontal Bracing

18
VENTILATED ANCHOR PLATE WITH LENGTH (APVL)
The APLV has a free anchor plate integrated on a length. It cannot be
used has a xed support for vertical or horizontal installation. Refer to the
Ventilated Anchor Plate (APV ) for all the warnings / details, except for the
installation. See Figure 33 for an APLV
It is assembled exactly like ange-to-ange assembly with the V-Band
(BSI) (See JOINT ASSEMBLY Section).
The part doesn’t have any outer wall, but Outer Band (BSE) is provided to
secure the insulation on the part. See Figure 34, 35 & 36 for the three steps
to install the CAX1-(BC).
Figure 33:Ventilated Anchor Plate with Length (APVL)
Figure 34: Step 1 of installation of APVL
Figure 35: Step 2 of installation of APVL
For vertical installation, small brackets must be on the bottom side when
the bottom Outer Band will be installed, these Brackets will hold the
Casing Band (BSE) right to the support plates. See Figure 36.
MINIMUM ACCEPTABLE SIZE FOR FRAMEWORK AND BRACING
Duct Diameter Ø
(in)
Plate thickness
(in)
Bracing
(in)
Framework
(in)
5 to 24 3/16 2 x 2 x 3/16
Channel or Equivalent
2 x 2 x 1/4
Channel or Equivalent
26 to 36 1/4 3 x 3 x 1/4
Channel or Equivalent
3 x 3 x 1/4
Channel or Equivalent
TABLE 8 - Minimum Acceptable Size for Framework and Bracing for Model CAX1-(BC)

19
Figure 36: Step 3 of installation of APVL
HEAVY DUTY WALL SUPPORT (WSHD)
When attached to a non-combustible wall with brackets and struts, a
Heavy DutyWall Support makes up a xed-point (See Figure 37).The
clamp rings are installed with the splits 90° apart so that they support
each other.The notches in the clamp rings are aligned with the draw
screws of the ange band. The Heavy Duty Wall Support Assembly is
bolted together with provided hardware. It is made with adjustable struts,
which allows a variable clearance from the non-combustible wall to the
chimney outer casing.
The minimum clearance varies with the size of the wall support, but is
between 2 and 2 1/2”(based on the angle shape of the Full Angle Ring
(FAR). See Figure 38.
The maximum clearance for all sizes is around 10”. See Figure 39
Figure 37:Wall Support (WSHD)
Figure 39:WSHD Maximum Adjustment
Figure 38:WSHD Minimum Adjustment

20
Figure 40: -Wall Guide Heavy Duty (WGHD)
HEAVY DUTY WALL GUIDE (WGHD)
The Heavy DutyWall Guide is designed to complement the Heavy Duty
Wall Support (See Figure 40). It is used as a lateral guide to prevent the
duct from exing due to lateral loading . The proper location for a WGHD is
immediately below the outer closure band near the duct joint.The Heavy
Duty Wall Guide is bolted together with hardware provided to form a rigid
assembly.
NOTE: - Seal joint with S-375 sealant above and below support if
exposed to weather.
- Can be attached to combustible wall
FULL ANGLE RING (FAR)
A Full Angle Ring is used as a guide to prevent the duct from exing due
to lateral loading.The angle ring is split for ease of installation. It is 1/8”
larger inside diameter than the outside diameter of the duct to allow
movement of the duct inside the ring.
Figure 41: - Full Angle Ring (FAR)
HALF ANGLE RING (HAR)
A Half Angle Ring is used as a saddle in horizontal or sloped runs.
Figure 42: - Half Angle Ring (HAR)
This manual suits for next models
1
Table of contents
Other Security Chimneys Fan manuals
Popular Fan manuals by other brands

ProKlima
ProKlima FN-114501.2 instruction manual

Hunter
Hunter Omnia installation manual

Greenheck
Greenheck CUBE-098 Installation, operating and maintenance manual

aldes
aldes InspirAIR H95-TRG Installation, operation & maintenance manual

ORIGO
ORIGO Crudus TF342 instruction manual

Prominence Home
Prominence Home Montauk owner's manual