SELPRO VTS300 User manual

rev.3.1 dated 30/06/14
VTS3003-PHASE SLAVE REGULATOR
SELPRO – Via P.G. Piamarta 5/11 – 25021 Bagnolo Mella (BS) – www.selpro.it – [email protected] - Tel. +39 030 6821611 – Fax +39 030 622274
1. PREPARATIONS
1.1.Important
Read these instructions carefully before installation.
Before use, follow all the installation and electrical connection
instructions.
Keep these instructions with the regulator for future use.
Observe current technical and safety regulations.
The device must be professionally installed and commissioned by a
qualified technician. INCORRECT installation may cause damages.
Before turning on device power, always check that it is correctly
grounded.
DO NOT tamper with or REMOVE internal regulator components;
this NULL AND VOIDS THE WARRANTY and can cause damages.
The user must be protected against electrical shock and the motor
must be equipped with overload protection, as per current pertinent
regulations.
According to safety regulations, protection against any contact with
live parts must be ensured by correct device installation; all parts
that ensure protection must be secured so as irremovable without
the help of a tool.
DO NOT turn on the regulator without the protection lid.
NEVER touch electrical circuit parts when the power is on.
Install the regulator away from direct sunlight so as not to overheat
the case.
Make sure working conditions (working temperature, humidity, etc.)
are within the indicated limits (see point 7).
Do not install the device near heat sources (resistances, hot air
ducts, etc.) where room temperature can exceed 50 °C, devices
that generate strong magnetic fields, sites subject to rain, humidity,
dust, excessive mechanical vibrations or shocks.
2. VTS300 REGULATOR UNIT DESCRIPTION
2.1.Overview
The VTS series three-phase regulators are built on a Vetronite(R)
support in an IP55 grade GW PLAST box. The control zone is at the
top of the board while the power zone is at the bottom.
In addition to the M3 and M4 terminal boards, regulation, connection
and signal devices are found in the control zone.
The fan speed command varies according to the command signal
received from the input. Output increases as input increases.
2.2.Key
VTS300 key
1 - Wire clamps - connection wires
2 M1 Three-phase output terminal board (U-V-W) + load
GND
3 M2 Three-phase power supply terminal board (L1-L2-
L3) + PE
4 - TPN lock screws with max 2.5 N m torque
5 - Wall mount perforated fin
6 - GW PLAST case
7 P1 Minimum voltage settings (MIN / CUT-OFF)
8 P2 Maximum voltage settings (MAX)
9 M3 Command input terminal board
10 M4 Alarm relay terminal board
11 DL.. Signal led
12 DSw Programming dip switch (0-10Vdc std setting)
13 SB1 Reset button
2.3.Mechanical dimensions
Model Plate data Mechanical dimensions Weight(*)
A kV A IP A B C E F Kg
VTS308 8 5.5 55 225 235 114 213 200 2.3
VTS312 12 8 55 225 230 128 213 200 2.5
VTS320 20 14 55 225 230 158 213 200 3.8
* Packaging included
3. INSTALLATION
3.1.INSTALLATION
Vertically install the device with the wire inlet facing down. To permit
correct heat dissipation, guarantee ≥150 mm clearance over and under
the regulator.
Reassemble and make sure the external protection lid is fully closed.
3.2.Electrical connections
Flexible wire section.
Signal: rated section 1.5 mm² (15 AWG)
Power: VTS 308 ≥1.5 mm² (15 AWG)
VTS 312 ≥2.5 mm² (13 AWG)
VTS 320 ≥4.0 mm² (11 AWG)
N.B. Protection devices: see point 8.
3.2.1.Power (M1) and load (M2*) connection:
(*)The regulator can be set to directly connect no. 4 fans (Three-phase +
Ground) upon request
3.2.2.Command signal connections (M3)
M3 Terminal Label Description
6 GND Reference grounding
5 S0 ON-OFF input (see point 3.3.3)
4 VR
Reference voltage output
+5.0 Vdc/+10.0 Vdc (±1.0%)
(automatic switching)
3 V+
Power supply voltage output
+20 Vdc (±20%)
2 GND Reference grounding
1 IN Command signal input
3.2.3.Alarm relay connection (M4)
Termi
nal Label Description
3 NO
Normally open contact
2 NC
Normally closed
contact
1 COM
Shared terminal
3.3.Dip-Switch function settings (DSw1 – DSw6)
DSw Description
1,2,3 Command signal selection (see point 3.3.2)
4 OFF = P1 (MIN) minimum voltage settings
ON = P1 cut-off voltage settings
5,6 ON-OFF input function (see point 3.3.3)
3.3.1.Default settings
3.3.2.Command input function programming
WARNING Press button SB1 after changing DSw settings to apply
changes..
DSw1 DSw2 DSw3 Description
OFF OFF OFF 0-20 mA signal
ON OFF OFF 4-20 mA signal
OFF ON OFF 0-10 Vdc signal
ON ON OFF 0-5 Vdc signal
OFF OFF ON PWM signal
ON ON ON Cos Phi calibration (reserved)
3.3.3.Functional programming for the ON-OFF input (S0)
DSw5 DSw6 Description
OFF OFF Start/Stop function (open = start)
ON OFF Thermal contact function (closed = start)
ON ON Output function at 100% (closed = 100%)
OFF ON Output function at MAX (closed = MAX (P2))
4. FUNCTIONAL CHARACTERISTIC

rev.3.1 dated 30/06/14
VTS3003-PHASE SLAVE REGULATOR
SELPRO – Via P.G. Piamarta 5/11 – 25021 Bagnolo Mella (BS) – www.selpro.it – [email protected] - Tel. +39 030 6821611 – Fax +39 030 622274
5. Trimmer Regulation limits
5.1.Regulation limits
Trimmer Label Description
P1 MIN/
CUT-OFF
Use as minimum voltage (MIN)
DSw4 = OFF (range from 0-100%).
Turn P1 clockwise to the required
minimum voltage.
Use as CUT-OFF
(shutdown point)
DSw4 = ON (range from 0-100%).
Once the minimum voltage is set, turn
DSw4 ON and press SB1 (reset). Cut-Off
will be set to minimum voltage.
P2 MAX
Maximum speed limit settings (range 0-
100%).
Settings procedure if maximum regulator
speed input signal is not available:
Remove signal connections from M3.
Set the regulator in
0-10 Vdc mode (see point 3.3.2)
Short circuit IN with VR (M3 terminals 1
and 4). The regulator runs at maximum
speed.
Turn P2 counter-clockwise to set the
required maximum voltage.
6. SIGNALS
6.1.Led
LED COLOR LABEL DESCRIPTION
GREEN PWR Power on
(light on)
GREEN CPU RUN Microprocessor running
(blinking light)
RED FAIL
Fault alarm
(blinking light)
(see point 6.2)
GREEN - RL1 relay excited
(light on)
6.2.Alarm blink code (DL3) in order of priority
NR. BLINKS DESCRIPTION
1 Board temperature over limit (> 85 °C)
2 Phase loss
3 T.K. contact open (DSw5 = ON and DSw6 =
OFF)
4 Input signal over range
5 Input signal under range
6 Incorrect dip switch settings
7. TECHNICAL SPECIFICATIONS
Power supply:
Voltage: 400 Vac (±10%) three-phase (230 Vac upon request).
Frequency: 50/60 Hz automatic frequency recognition
Surge: for installation category II (4 kV)
(> 500 Vac surge filters ON).
Mains: monitoring on all 3 phases.
Ground connection:
VTS300 controllers are compatible with the different Ground
connections: IT – TT - TN.
Current:
Rated RMS current @ 50 °C room temperature:
VTS308: 8 A < 50 °C; > 50 °C -0.6 A/°C
VTS312: 12 A < 50 °C; > 50 °C -0.6 A/°C
VTS320: 20 A < 50 °C; > 50 °C -0.6 A/°C
Overload: 150% of rated current (=10” every 3’)
Power:
Command: 5 V A
Dissipated in. 4 W/A: VTS308 32 W @ 8 A
VTS312 48 W @ 12 A
VTS320 72 W @ 20 A
Functional characteristic: SLAVE regulator
Direct function; output increases as input increases
Input signals and contacts:
Analog: 0-10 Vdc, 0-5 Vdc (Ri = 10 kΩ)
0-20 mA, 4-20 mA (Ri = 100 Ω)
Logic: PWM signal from 3 to 20 Vdc with positive polarity
“ON/OFF” clean contact: S0 programmable contact
(see point 3.3.3).
Output signals and contacts:
Auxiliary power:
20 Vdc (±20%), ≤20 mA not stabilized and protected against short circuit
5.0 Vdc/10,0 Vdc (±1.0%), ≤20 mA protected against short circuit
RL1 relay: COM, NC, NO contacts for alarm
3 A @ 250 Vac – 3 A @ 30 Vdc
Alarms:
In command: 0-5 Vdc: Vin ≤5.5 Vdc; 0-10 Vdc: Vin ≤11 Vdc
0-20 mA: Iin ≤24 mA; 4-20 mA: 2 mA ≤Iin ≤24 mA
Mains monitoring: phase loss
Regulator: working temperature control with internal probe
(< 85 °C).
Protections:
Surge: As per EN 61000-4-5: surge category II (4 kV)
Auxiliary power: with PTC sensor for short circuit protection
Internal temperature: internal thermal protection
Case:
Material: GW-PLAST 75 (temperature < 85 °C) and aluminum
Pollution: for high pollution using the wire clamp kit
Fire resistance: category D
Insulation:
Case: class I (use of grounded PE protection)
Command: 4000 Vac between command input and mains voltage parts
Working conditions:
Working temperature: from -20 °C to 50 °C ; use
Start/Stop contact if T ≤-10 °C
Storage temperature: from -20 °C to 70 °C
Humidity: from 0% to 85% non-condensing relative humidity
Vibrations: ≤1 g (9.8 m/s²)
Assembly:
Assembly: wall mount in vertical position only.
8. CIRCUIT BREAKER AND SHORT CIRCUIT PROTECTION
A short circuit and/or overload device must be installed upstream from the
VTS308, VTS312 or VTS320 regulator; this protection must be supplied
by the installer and can be made up of:
Three-phase circuit breaker with ‘AC’ cut-off curve
Triple ultra-fast fuses, to protect semi-conductors
Model Circuit breaker Protection fuses - SRC
Type Vac Amp P/N
VTS308 16 A 10x38
690
16 FR10GB69V16
VTS312 24 A 10x38 16 FR10GB69V16
VTS320 40 A 14x51 25 FR10GB69V25
The use of these protections safeguard regulation device electrical
integrity.
SURGE ARRESTER :
Electrical protection inserted between the regulator power supply and
grounding, that protects the device from transitory power surges up to 480
Vac.
WARNING:
Disconnect the faston contact from the PE ground reference, in the
electrical rigidity test.
WARNING:
For DIFFERENTIAL protection systems, use components with grounded
current dispersion ≥60 mA.
The VTS300’s dispersion current to Ground, it’s about 4 mA
The following table shows the measured values:
Supplied
phases
Current
(mA)
Regulation
output
L1 – L2 – L3 < 4 0%
L1 – L2 – L3 < 4 100%
L1 – L2 – L3 < 13 15%
L1 – L2 < 8 0%
L2 – L3 < 8 0%
L1 – L3 < 8 0%
L1 < 12 0%
L2 < 12 0%
L3 < 12 0%
9. MANUFACTURER'S DECLARATION
This instrument was designed and constructed for use in Industrial
environments and meets the following community directives:
Machinery Directive 2006/42/CE as amended
Low Voltage Directive 2006/95/CE and 93/68/CE
EMC 2004/108/CE directive as amended
10. COMMUNITY DIRECTIVES AND TECHNICAL STANDARDS
The essential directive requirements are met by compliance with
“generic standards” for the industrial environment.
Directive Code Standard Description
2006/42/CE EN 60204-1 Machine safety and electrical system
2006/95/CE
EN 60204-1 Machine safety and electrical system
EN50178 Power installation electronic equipment
2004/108/CE EN61800-3
Variable speed electric drives.
Part 3 : Product standard for
Electromagnetic compatibility and
specific test methods
With reference to EMC compatibility, according to markings:
11. CODE
ZN VTS a bb cc d e f g h i
POSITION a bb cc d e f g h i
EXAMPLE ZNVTS 3 12 40 1 0 0 S 0 0
Position Description
a power type 3 three-phase
bb
Rated current
08 8 A
12 12 A
20 20 A
cc power supply
voltage 40 400 Vac (±10%) - 50/60 Hz
d motor outputs
1 1 motor outputs
4 4 motor outputs
e not used 0 -
f not used 0 -
g case protection
grade
S IP55
G IP20
h customizations 0 Selpro standard version
i revision index 0 Global product update
index
The instrument must be disposed of according
to local electric and electronic device disposal
regulations.
This manual suits for next models
3
Other SELPRO Controllers manuals
Popular Controllers manuals by other brands

HESCH
HESCH HE 5422 MR operating manual

DX Engineering
DX Engineering DXE-NCC-2 quick start guide

Monosem
Monosem CS30 Series manual

PIETRO FIORENTINI
PIETRO FIORENTINI APERVAL Use and maintenance manual

Trox Technik
Trox Technik EN 320x160 Installation operation & maintenance

gefran
gefran 1600 Installation and operation manual