In order to satisfy the electromagnetic compliance requirements: - Use shielded cables for signals.
- Connect the shield to a preferential ground for devices.
- Separate the shielded cables from other cables used for power installations.
(transformers, inverters, motors, induction ovens, etc...).
The module allows to read temperature inputs as TC thermocouples, RTD thermistors with 2, 3 or 4 wire
connection and retransmits the input reading value on the 4 - 20 mA output loop.
In addition T121 can be used to read voltages (mV) and resistors (Ω).
2 wire connection
This connection can be used for short distances ( < 10 m) between module and probe, you should remember that this connection
introduces an error in the measurement (which can be removed by software programming) equivalent to the resistance
contributed by the connection cables to the measurement. The module must be programmed by PC for 2-wire connection.
3 wire connection
This connection can be used for medium-long distances ( > 10 m ) between module and probe. The instrument performs
compensation for the resistance of the connection cables. For the compensation to be correct, the resistance values of each
conductor must be the same. The module must be programmed by PC for 3-wire connection.
4 wire connection
This connection can be used for medium-long distances ( > 10 m ) between module and probe. It offers maximum precision
because the instrument measures the resistance of the sensor independently from the resistance of the cables.
The module must be programmed by PC for 4-wire connection.
Potentiometer connection
A potentiometer with resistance between 500 and 1,7 kΩ may be connected directly to the module. If the potentiometer has
a resistance greater than 1,7 kΩ up to 100 kΩ maximum, it will be necessary to use a resistor in parallel with potentiometer:
R = 1.5 kΩ.
Current loop connection 4 – 20 mA (regulated current).
Note: in order to reduce the instrument's
dissipation, we recommend
a Load > 250 Ω is connected
–