SENTRONIC Mini-M Series User manual

MODEL: M2SN
Super-mini Signal Conditioners Mini-M Series
INPUT LOOP POWERED ISOLATOR
Functions & Features
• Loop-powered design eliminates output loop power supply
• Two isolators housed in one enclosure
• 350 Ω output drive with 4 – 20 mA
• CE marking
• UL approval
Typical Applications
• Isolation between control room and field instrumentation,
between telemetering system and input device
• Eliminates ground problems in existing systems
thanks to easiness of application without requiring
additional power wiring
Model
SPAN
ZERO
SPAN
ZERO
23 (.91)
76
(2.99)
124
(4.88)
mm (inch)
MODEL: M2SN-[1][2][3][4]
ORDERING INFORMATION
• Code number: M2SN-[1][2][3][4]
Specify a code from below for each [1] through [4].
(e.g. M2SN-2A6/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01)
[1] NO. OF CHANNELS
1: 1 channel
2: 2 channels
[2] INPUT
Current
A: 4 – 20 mA DC
H: 10 – 50 mA DC
[3] OUTPUT
Current
A: 4 – 20 mA DC
Voltage
6: 1 – 5 V DC
[4] OPTIONS (multiple selections)
STANDARDS & APPROVALS (must be specified)
/N: Without CE or UL
/CE: CE marking
/UL: UL approval (CE marking)
OTHER OPTIONS
blank: none
/Q: Option other than the above (specify the specification)
(UL not available)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M3 screw terminals (torque 0.8 N·m)
Housing material: Flame-resistant resin (black)
Isolation: Input to output, between channels
Zero adjustment (front)
Voltage output: -5 to +5 %
Current output: -0.5 to +0.5 %
Span adjustment (front)
Voltage output: 95 to 105 %
Current output: 98.5 to 101.5 %
INPUT & OUTPUT
• INPUT 4 – 20 mA DC / OUTPUT 1 – 5 V DC
Equivalent input impedance: Approx. 250 Ω with 20 mA
input
Operational range: 3 – 22 mA DC
(Accuracy is assured within 4 – 22 mA)
Load resistance: ≥ 50 kΩ
• INPUT 10 – 50 mA DC / OUTPUT 1 – 5 V DC
Equivalent input impedance: Approx. 100 Ω with 50 mA
input
Operational range: 7 – 55 mA DC
(Accuracy is assured within 8 – 55 mA)
Load resistance: ≥ 50 kΩ
• INPUT 4 – 20 mA DC / OUTPUT 4 – 20 mA DC
Equivalent input impedance: 230 Ω plus load resistance with
20 mA input
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: M2SN
Operational range: 3 – 22 mA DC
(Accuracy is assured within 4 – 22 mA)
Load resistance: 50 – 350 Ω (min. 50 Ω required for
adequate operation)
• INPUT 10 – 50 mA DC / OUTPUT 4 – 20 mA DC
Equivalent input impedance: 90 Ω + [load resistance×0.16]
with 50 mA input
Operational range: 7 – 55 mA DC
(Accuracy is assured within 8 – 55 mA)
Load resistance: 50 – 600 Ω (min. 50 Ω required for
adequate operation)
•INPUT 4 – 20 mA DC / OUTPUT 1 – 5 V DC
INPUT CURRENT [mA]
4 12 20
5.0
approx.
3.7
VOLTAGE [V] ACROSS
INPUT TERMINALS
3.0
approx. 5.0
4.0
•INPUT 10 – 50 mA DC / OUTPUT 1 – 5 V DC
INPUT CURRENT [mA]
10 30 50
5.0
approx.
3.7
VOLTAGE [V] ACROSS
INPUT TERMINALS
3.0
approx. 5.0
4.0
•INPUT 4 – 20mA DC / OUTPUT 4 – 20 mA DC
INPUT CURRENT [mA]
4 12 20
10.0
VOLTAGE [V] ACROSS
INPUT TERMINALS
3.0
approx. 5.6
(load 50Ω)
6.0
12.0
approx. 5.0
8.0
approx. 3.8
approx. 9.6
(load 250Ω)
approx. 4.6
approx. 11.6
(load 350Ω)
•INPUT 10 – 50 mA DC / OUTPUT 4 – 20 mA DC
INPUT CURRENT [mA]
10 30 50
10.0
VOLTAGE [V] ACROSS
INPUT TERMINALS
3.0
approx. 4.9
(load 50Ω)
6.0
approx. 4.7
8.0
approx. 3.8
approx. 6.5
(load 250Ω)
approx. 4.1
approx. 9.3
(load 600Ω)
INSTALLATION
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lbs)
PERFORMANCE in percentage of span
Accuracy: ±0.1 %
Temp. coefficient
Voltage output: ±0.015 %/°C (±0.008 %/°F)
Current output: ±0.02 %/°C (±0.01 %/°F)
Response time
Voltage output: ≤ 0.5 sec. (0 – 90 %)
Current output: Approx. 15 msec. (0 – 90 %)
Load effect (current output)
4 – 20 mA input: 0.015 %/Ω (50 – 150 Ω)
0.003 %/Ω (150 – 350 Ω)
10 – 50 mA input: 0.015 %/Ω (50 – 100 Ω)
0.003 %/Ω (100 – 600 Ω)
(The unit is calibrated with 250 Ω load at the factory.)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
500 V AC @1 minute (input to output)
2000 V AC @1 minute (between channels)
2000 V AC @1 minute (input or output to ground)
STANDARDS & APPROVALS
CE conformity:
EMC Directive (2004/108/EC)
EN 61000-6-4 (EMI)
EN 61000-6-2 (EMS)
Approval:
UL nonincendive Class I, Division 2,
Groups A, B, C, and D hazardous locations
(UL 1604)
UL general safety requirements
(UL 61010B-1)
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

MODEL: M2SN
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
5
9
21.5 (.85)
70.5 (2.78)
84 (3.31)10 (.39) 15 (.59)
6 (.23)
59 (2.32)
DIN RAIL
35mm wide
[4 (.16)]
8–M3
SCREW
72 (2.83)
23 (.91)
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
114 (4.49)
• When mounting, no extra space is needed between units.
4
8
12
14 13
1
4 (.16)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Base Socket
+
–
Ch 1 INPUT 1
5
8
+
–
9
12
13
14
+
–
4
+
–
Ch 2 INPUT
Chopper
Buffer
Amplifier
Z S
Ch 1 OUTPUT
Ch 2 OUTPUT
Inverter Rectifier
Chopper
Buffer
Amplifier
Z S
Inverter Rectifier
■ VOLTAGE OUTPUT
Base Socket
+
–
Ch 1 INPUT
1+
–
9
12
4
5
8
S
Ch 1 OUTPUT
13
14
+
–
Inverter
Isolation
Load Effect
Compensation
Z
■ CURRENT OUTPUT
+
–
Ch 2 INPUT
S
Ch 2 OUTPUT
Inverter
Isolation
Load Effect
Compensation
Z
Specifications are subject to change without notice.
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

M2SN
P. 1 / 2EM-5019 Rev.7
INPUT LOOP POWERED ISOLATOR MODEL M2SN
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket) ...................... (1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ NONINCENDIVE APPROVAL OPTION
• This equipment is suitable for use in Class I, Div. 2, Groups
A, B, C and D or Non-Hazardous Locations only.
• WARNING! Before You Remove the Unit from Its Base
Socket or Mount It, Turn Off the Power Supply and Input
Signal for Safety.
• WARNING! – Explosion Hazard –
Substitution of Components May Impair Suitability for
Class I, Div. 2.
• WARNING! – Explosion Hazard –
Do Not Disconnect Equipment Unless Power Has Been
Switched Off or The Area is Known To Be Non-Hazardous.
• The equipment was evaluated for use in the ambient tem-
perature and relative humidity as mentioned in ‘ENVI-
RONMENT’ section.
• The input and output wiring must be in accordance with
Class I, Div. 2 wiring methods and in accordance with the
authority having jurisdiction for use in these hazardous
locations.
■ GENERAL PRECAUTIONS
•Before you remove the unit from its base socket or mount
it, turn off the power supply and input signal for safety.
■ ENVIRONMENT
• Indoor use
•When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ven-
tilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with ca-
bles, etc.
■ WIRING
• Do not install cables (input and output) close to noise
sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as the input sig-
nal is supplied, however, a warm up for 10 minutes is re-
quired for satisfying complete performance described in
the data sheet.
COMPONENT IDENTIFICATION
INSTALLATION
Loosen the fixing screw at the front of the unit in order to
separate the body from the base socket.
■ DIN RAIL MOUNTING
Set the base socket so that
its DIN rail adaptor is at
the bottom. Position the
upper hook at the rear side
of base socket on the DIN
rail and push in the lower.
When removing the socket,
push down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
■ WALL MOUNTING
Refer to “EXTERNAL DI-
MENSIONS.”
Model
SPAN
ZERO
SPAN
ZERO
Zero Adj.
Span Adj.
Connection
Diagram
Specifications
Ch.1
Zero Adj.
Span Adj.
Ch.2
Body Base Socket
Fixing Screw
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG

M2SN
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the con-
nection diagram on the side of the unit.
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Input: Check current with an ammeter. Be sure that
the connected transmitter allows the load shown in the
following table.
3) Output: Check that output load is within the permis-
sible limit shown in the following table.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■ HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
EXTERNAL DIMENSIONS unit: mm (inch)
5
9
21.5(.85)
70.5 (2.78)
84 (3.31)10 (.39) 15(.59)
6(.23)
59 (2.32)
DIN RAIL
35mm wide
[4 (.16)]
8–M3
SCREW
72 (2.83)
23 (.91)
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
114 (4.49)
• When mounting, no extra space is needed between units.
4
8
12
14 13
1
4 (.16)
+
–
1Ch.1 OUTPUT
+
–Ch.2 OUTPUT
4
9
12
13
14
+
–
Ch.1 INPUT
5
8
+
–
Ch.2 INPUT
MODEL EQUIVALENT INPUT IMPEDANCE
M2SN-xA6 250Ω
M2SN-xH6 100Ω
M2SN-xAA 230Ω plus output load
M2SN-xHA 90Ω plus output load ×0.16
MODEL LOAD RESISTANCE
M2SN-xA6 50kΩ minimum
M2SN-xH6 50kΩ minimum
M2SN-xAA 50 – 350Ω
M2SN-xHA 50 – 600Ω
Rugghölzli 2
CH - 5453 Busslingen Tel.+41 (0)56 222 38 18
Fax +41 (0)56 222 10 12 mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SENTRONICAG
This manual suits for next models
5
Table of contents
Other SENTRONIC Air Conditioner manuals
Popular Air Conditioner manuals by other brands

Friedrich
Friedrich WallMaster PE07K Service manual

Giatsu
Giatsu JONICA GIA-FST3-O-48JON Owners and installation manual

Daikin
Daikin Super Multi NX FTXS20G2V1B Operation manual

LG
LG BG5200ER owner's manual

Mitsubishi Electric
Mitsubishi Electric MSZ-HR42VF installation manual

Whirlpool
Whirlpool ACP102PR2 Use & care guide