SERO DS-045 Installation manual

OPERATION MANUAL
DEHUMIDIFIER
Please read this operation manual before using the dehumidifier
DRY
For Evaluation Only.
Copyright (c) by Foxit Software Company, 2004 - 2007
Edited by Foxit PDF Editor

CONTENTS
Attention during Usage
3
4-5
6
6
7
8
9-10
11
12
13
14
15
15
16
16
17-19
20
Descriptions of Parts
Remote Controller
Operation Guide
AUTO Operation Mode
Air Direction Adjustment
Timer Operations
Defrost system
Water drainage system
Error codes
Wiring diagram
Maintenance
Trouble Shooting
2
Safety Instruction
Principle of dehumiditifier
Specification
Panel Controll

Installation
Please read the following Safety Instructions carefully prior to use.
The instructions are classified into two levels, WARNING and CAUTION according to
the seriousness of possible risks and damages as follows. Compliance to the
instructions are strictly required for safety use.
lnstallation in a inadequate place may cause accidents. Do not install in the following place.
WARNING
Please call Sales/Service Shop for the Installation.
Do not attempt to install the air conditioner by yourself because improper works
may cause electric shock, fire, water leakage.
Safety Instruction
Connect the earth
cable.
earthing
Do not install in the
place where there is
any possibility of
inflammable gas
leakage around the
unit.
Do not get the unit
exposed to vapor
or oil steam.
PROHIBITION PROHIBITION
CAUTION
WARNING
When abnormality such as burnt-small found,
immediately stop the operation button and
contact sales shop.
OFF
Use an exclusive power source with a
circuit breaker
ENFORCEMENT
STRICT
3

WARNING
Ensure the power plug is secure
Do not use the same socke t
Do not expose yourself to a In case of abnormal condition Do not attempt to carry out a
repair.
(burning smell etc.),pull out the
power plug to stop the dehu-
midifier from running, or dis-
connect the power supply by
means of a electric current
protector.
single directional airflow for a
long period
Do not operate when the hands Do not insert a rod or other ob-
je cts i nto t he in let o r out let
vents.
are wet.
with other electric appliances or
use an extension cord.
Never pull out the power plug Never use damaged electric
wires or unspecified electric
wires.
during operation.
If the plug is not secure, it may
otherwise, it may cause a elec-
tric shock or a fire due to over - otherwise it may cause a elec-
tric shock or a fire.
heating.
cause a electric shock, over-heat-
otherwise it may cause a elec-
to avoid harming to
If the abnormal condition persists,
Improper repairs may cause a
electric shock or a fire. You should
contact the dealer of service cen-
tre to arrange for a repair.
it may cause a electric shock or a
fire due to over-heating. Please
consult the dealer of service cen-
tre as soon as possible to
arrange for a repair.
your health.
due to danger of a electric shock.
otherwise, it may cause a elec-
tric shock or a fire.
tric shock or a fire due to over-
heating.
ing or a fire.
OFF
Attention during Usage
4

Do not hold the electric wire to If the air-conditioner is not in Switch off the power supply
w h i l e c l e a n i n g t h e d e -
humidifier.
use for a long time, it is neces-
sary to pull out the power plug.
pull out the power plug.
Do not use the dehumidifier Do not pour water onto the
dehumidifier for cleaning.
Do not place a heater in front of
the dehumidifier.
for other purposes.
Do not use it for keeping precision
instruments, food, plants and ar-
Due to danger of electric shocks.
tistic items. This may affect the
quality of the food.
If internal combustion of the heater
is not complete, it may give out
poisonous carbon monoxide.
Pulling of the electric wire may
cause over-heating of the electric
wire of a fire.
Excessive dust on the power plug Please take care not to damage
the internal fan which is rotating
at a high speed.
may also cause over-heating or
a fire.
OFF
Attention during Usage
PROHIBITIONPROHIBITION
PROHIBITION
PROHIBITION
5

Principle of dehumidifier
The dehumidifier use the refrigeration circuit to change the damp air warm dry air.
When the damp air passes the condenser, the air water will be condensed and the air
will become dry.
WARM
DRY
AIR
OUTLET
CONDENSER
COMPRESSOR
FAN
CAPILLARY
WATER
DRAIN
OUT
WATER PUMP
CONDENSE WATER
WATER TANK
AMBIENT
AIR
INLET
EVAPORATOR
COLD
DRY
AIR
COLD
DRY
AIR
The Specification Of Dehumidifier (R410a)
Model DS-045 DS-060 DS-080 DS-011 DS-014
Capacity(L/hr)4.5 6 8 11 14
Heating capacity(W)2400 3200 4200 5700 7400
Power consumption(W)1200 1700 2200 2800 3400
Air flow(m3/hr)540 720 920 1300 1500
Refrigerant(g)960 1250 1600 2150 2540
Power supply 230V/50Hz/1Ph 230V/50Hz/1Ph 230V/50Hz/1Ph 400V/50Hz/3Ph 400V/50Hz/3Ph
Current(A)6.2 7.6 9.8 4 5.2
Aux electric heater(W)(option)700 700 700 1500 1500
Compressor type Rotary Rotary Rotary Rotary or Scroll Scroll
Compressor(brand name)Daikin or sanyo Daikin or sanyo Daikin or sanyo Daikin or sanyo Daikin or sanyo
Water pump Yes Yes Yes Yes Yes
Applicable area(㎡)100-150 150-200 200-250 250-300 300-400
Noise(dB(A)) 47 48 53 56 60
Drain pipe(mm)500 500 500 500 500
Packing dimension(mm)(WxHxD)562x1820x480 562x1820x480 562x1820x480 680x2004x540 680x2004x540
Unit dimension(mm)(WxHxD)482x1724x400 482x1724x400 482x1724x400 600x1900x460 600x1900x460
Weight(net/gross)(kg)70/80 78/88 85/95 120/134 135/147
Test condition: Dry ball temperature 30℃. Relative humidity of 80RH%.
6

Descriptions of Parts
1
2
3
4
TIMER HEATER S WING SWIN G
+
_
FAN
SPEED MODE ON /OFF
A
C
%
7896
5
5
4
3
2
1
6
7
Control Panel
Air Inlet
Air filter(inside)
Air Outlet
8
9
Humidity sensor
Indoor temperature sensor
Water drainage system
Four way valve
Compressor
7

ON / OFF
A
C
%
1
2683
4
7
9
5
Panel Control
Auto operation mode
A
1
Heating operation mode
3
Dehumidifying operation mode
4
Displays when turns to TEMPERATURE status
C
72 Fan operation mode
Swing
5
Displays when turns to CLOCK status
6
CLOCK or TEMPERATURE or displayHUMIDITY
9
8%Displays when turns to statusHUMIDITY
TIMER HEATER SWING SWING
+
_
FAN
SPEED MODE ON/OFF
A
C
%
Signal Receiver
Button
FAN SPEED
SWING
HEATER
MODE
SWING
TIMER
+ /
_
Display
Button
Display
Press the button to start operation,
press the button again to stop operation.
Select the fan speed. Each time press the
button; fan speed is selected in a sequence:
LOW , MID , HIGH.
Mode is selected in a sequence:
Automatic ; Dehumidifying ; Fan ;
Heating.
One press of the “ + “ button to raise
o
the temperature by 1 C; One press of
the “ - ” button to lower the temperature
o
by 1 C.
Set the swing or stop of Left-Right Airflow
vane.
Set the swing or stop of Up-Down Airflow
vane.
Press once to switch on assistant heater;
Press again to switch off assistant heater. Set the TIMER ON / OFF.
8

OC
DRY
TEMP
AUTO FAN
SW I NG ON / OFF
MODE OFF ON
CANCEL CONFIRM
SW IN G
FA N TIM E R
Signal Emitter :
Sending out remote control signal
to the air-conditioner Temperature Adjustment Button :
Adjust temperature settings
Press once to set temperature 1
degree higher.
Press once to set temperature 1
degree lower.
On/Off Button :
Press once to start Air-conditioner
running; Press again to stop
running.
Timer Off Button :
Set Timer-off hour.
Timer On Button : Set Timer-on
hour.
Timer Confirm Button :
Send Timer-on or Timer-off data to
the air-conditioner
Remote Controller Display Panel :
Display settings
Mode Button :
Select Automatic, Heating,
De-humidifying, Fan modes
FAN Button :
Air flow setting
Timer Cancel Button :
Cancel Timer-On and Timer-Off
settings
Air Direction Button :
Set air louver swinging or stationary
Remote Controller
SL EE P HE ATE R
Manual Heater Button :Assistant
Press once to switch on assistant
heater; Press again to switch off
assistant heater.
(There is no this function in this unit)
9

Emission Indicator :
Air Direction Display :
FAN Displa y :
When
It displays the current amount of air
flow.
FAN Display on
Remote Controller
AUTO FAN
FAN
FAN
FAN
Automatic
Low
Mid
High
"Swing" is in display, the up-
down louver of the air-conditioner is
s w in g in g . W h e n t h e d is p la y
disappears, the up-down louver
stops swinging.
NOTE:
All Displays on the diagram are listed out for demonstration. During operation, only the
relevant Display will appear on the Remote Controller.
Timer Display :
It displays the time setting for Timer-
On or Timer-Off in the range of 1~12
hours.
Mode Display :
Press "Mode" button to display the
current working mode. Automatic,
Heating, Dehumidifying, Fan modes
Temperature Display :
It displays the current set tempera-
ture which may be adjusted by Tem-
perature Adjustment Button or
o
within the range of 18 ~30 C. In Au-
tomatic Mode, temperature is not dis-
played but " Standard " (standard)
o
temperature + 2 C) or " Standard "
(standard temperature o
-2 C) is
displayed.
This symbol flashes once when the
Remote Controller emits signals to
the Dehumidifier.
OC
AUTO
FAN
FAN
HEAT
DRY
HR AFT
ON
AUTO
SWING
Remote Controller
10

Operation Guide
Press "Mode" button to select the required working mode, which is
changed in the following sequence when pressed once:
Heating mode is available only on cooling-heating type air conditioner.
Automatic operation will be explained in detail on next page.
When Automatic FAN is selected, the air-conditioner will automatically select the suit-
able amount of air flow according to room temperature.
When Dehumidifying is selected, the amount of air flow is set by the machine and fan
setting is not functional.
o o
Range of adjustable temperature settings : 16 C ~ 31 C.
If it is desired to run the machine at the same settings for mode, air flow and temperature
as the last operation, skip Steps 1~3 and start the machine directly.
If the interval is shorter than 3 minutes from last shut down to the present switch-on, the
compressor only re-starts after 3 minutes to protect the system.
After switching on and if the mode is changed, the system may delay for 3 minutes before
starting operation.
When heating mode is selected, the internal fan will delay operation for a while when the
machine is switched on to prevent cool air circulation at the beginning.
After switching on, air flow amount and temperature may be separately adjusted as desired.
Press "FAN" button to select the required amount of air flow,
which is changed in the following sequence when pressed once :
Press "Temperature Adjustment Button " to set temperature 1
degree higher.
Press "Temperature Adjustment Button " to set temperature 1
degree lower.
Hold down the Button to increase of decrease the temperature
settings progressively.
Press "On/Off" button, and when the unit receives the signal, it gives
out two "beep" tones, the operation light is on and the dehumidi-
fier starts operation.
Automatic Heating
Automatic Low Mid High
Dehumidifying Fan
Proper settings of Heating, Dehumidifying and Fan modes
Mode Selection
NOTE:
NOTE:
NOTE:
NOTE:
Air Flow Selection ( 2 )
Temperature Setting Selection ( 3 )
Starting Operation ( 4 )
( 1 )
OC
COOL
TEMP
AUTO FAN
S W I N G ON / OFF
MODE OFF ON
CANCEL CONFIRM
SW I NG SL E EP
FA N TI M ER
H E AT E R
1
2
3
4
11

AUTO Operation Mode
Press "Mode" button to select Automatic Operation mode.
When Automatic FAN is selected, the unit will automatically select the suitable amount of
air flow according to room temperature.
In automatic mode, the dehumidifier automatically selects "Dehumidifying” , "Heating" modes
depending on room temperature and the humidity, with details as the follow-ing table:
Press "FAN" button to select the required amount of air flow,
which is changed in the following sequence when pressed once :
Press " On/Off " button, and when the unit receives the signal, it
gives out two " beep " tones, the operation light is on and the de-
humidifier starts operation is automatic mode.
Automatic Low Mid High
Automatic operation Mode
Mode Selection (1)
Adjustment in Automatic Mode
Fan Selection (2)
Starting Operation (3)
NOTE:
NOTE:
Temperature
Feeling Button Operation
o o
23 C ~ 28 C
o
23 C o
28 C
<>
Model
Press once to change the air flow pro-
gressively until the suitable air flow is
selected.
FAN
Unsuitable fan speed
Working
Heating
AUTO
TEMP
AUTO FAN
S W I N G ON / OFF
MODE OFF ON
CANCEL CONFIRM
SW I NG SL E EP
FA N TI M ER
HE AT ER
1
2
3
Dehumidify
or
humidity: > 80%
o
23 C o
28 C
<>
or
humidity: < 80%
Working
Working
Not Working Not Working
Not Working
12

To stop the up-down air louver in a desired position, set the louver to automatic swinging and
To get the best effect, the up-down air flow is usually set in the following manner :
Dehumidifying - Horizontal air direction or upward air direction. Heating -
Downward air direction.
when it reaches the desired position, stop the louver from swinging. It is necessary to adjust
the louver angle by means of the remote controller, Setting of the louver with the hand may
affect its normal operation, in which event, switch off the unit temporarily and re-start operation.
Air Direction Adjustment
Up-Down Air Direction Adjustment
Changing Left-Right Air Direction
NOTE:
OC
COOL
TEMP
AUTO FAN
S W I N G ON / OFF
MODE OFF ON
CANCEL CONFIRM
SWI N G SLE E P
FAN TIM E R
F R E S H
TIMER HEATER SWING SWING
+
_
FAN
SPEED MODE ON/OFF
A
C
%
TIMER HEATER SWING SWING
+
_
FAN
SPEED MODE ON/OFF
A
C
%
Airflow horizontally Airflow downwardAirflow upward
Don’t move the Left-Right vane directly.
NOTE:
OR
13

Before
Timer-Off can only be set when the Dehumidifier is running.
Timer-On and Timer-Off cannot be set at the same time.
Timer display on the remote controller : While time passes, the display shows the remaining
time.
If the "On-Off" button is pressed while the unit is under timer-off setting, then the unit will
shut down immediately, the timer setting is cancelled and the timer light will be off.
timer operation, please set the operation mode, temperature, air flow etc. on the
remote controller, With timer being set to switch-on mode. the Dehumidifier will operate
according to the last setting.
Usually, timer-on setting is made while the dehumidifier is not in operation. If timer-on is
set while the dehumidifier is running, then the unit will shut down immediately and re-start
at the pre-set time.
If the "On-Off" button is pressed while the unit is under timer-on setting, then the unit will start
immediately, the timer setting is cancelled and the timer light will be off.
Timer Operations
Timer Switch On
Timer Switch Off
Timer Cancellation
1. Press "Timer On" button to set time for timer-on switching. Press
1. Press "Timer Off" button to set time for timer-off switching. Press
Point the remote controller towards the receiver on the unit, press
"Timer
"Timer Press
Press "Timer-Cancel" button to cancel the timer-on or timer-off
settings.
2.
2.
Confirm"
Confirm"
button
button
to
to
send
send
the
the
timer
timer
setting
setting
to
to
the
the
de-
De-
humidifier. Then the timer light on the unit lights up, indicating
humidifier. Then the timer light on the unit lights up, indicating
that the unit is in the timer mode. When it reaches the switch-on
that the unit is in the timer mode. When it reaches the switch-off
time, the dehumidifier will operate in the pre-set modes.
time, the air-conditioner will automatically shut down.
the
the
button
button
once
once
to
to
change
change
the
the
time
time
interval
interval
of
of
1
1
hour
hour
in
in
a
a
cyclic
cyclic
manner
manner
of
of
6,
6,
7,
7,
8
8
...12
...12
..1,
..1,
2..5,
2..5,
6
6
(The
(The
display
display
is
is
showing
showing
the
the
previous
previous
time
time
as
as
the
the
starting
starting
time
time
of
of
the
the
present
present
setting)
setting)
If the button is held down, the time interval will increase progres-
If the button is held down, the time interval will increase progres-
sively by 1 hour unit.
sively by 1 hour unit.
NOTE:
NOTE:
OC
COOL
TEMP
AUTO FAN
HR AFT
ON
S W I N G ON / OFF
MODE OFF ON
CANCEL CONFIRM
SW I NG SL E EP
FA N TI M ER
H E AT E R
1
2
14

Defrost system
Sequences of the defrosting:
1- Start
The defrosting is engaged if the following conditions are at the same time fulfiled:
- the compressor and the fan motor run without stopping;
- the defrosting sensor temperature lower than 3 , and the duration of time more
oC
than 45 minutes;
- the defrosting sensor temperature goes down to -7 .
oC
2- After 15 seconds, the 4 way valve shifts.
3- Five seconds after its stop, the compressor starts alone ; And the accumulated freeze
on the gills becomes melting, what is generally with a steam cloud .
4- Stop:
The defrosting stops if one of the following conditions is fulfiled:
- the defrosting operates 20 seconds and the detected temperature by the defrost
sensor goes up to 12 ;
oC
- the compressor had run totally 8 minutes.
5- The compressor runs.
6- After 15 seconds the 4 way valve shifts
7- Five seconds after its stop the compressor and the fan start for restarting in
heating mode.
8- The running light is blinking during defrosting.
Water drainage system
During the dehumidify mode, the condenser water will be drained into the internal water tank .When the
water reaches the certain level, the water drain pump will work. If the water can be drained out in 8 mins,
the dehumidifier will keep working. If not, the compressor and the motor will stop working. Mean while an
error message “ E4 “ will appear in the control panel to inform you to empty the water.
In this instance, you should cut the power off, and then restart the dehumidifier ,and the operation
will continue .
15

Error Codes
E1 : Room temperature sensor error;
E2 : Defrost temperature sensor error;
E3 : Humidity sensor error;
E4 : Drain error;
PCB
COM
AC-N
ROOM
TEMPERATURE SENSOR
CONNECT TO OUTDOOR UNIT
NO
WHITE
TRANSFORMER
O
CNA CNB
DISPLAY
RECEIVE
BOARD
BLACK
G
Y/G
N
L
WIRING DIAGRAM
TERMINAL
CN-DISP
11
R
DEFROST
TEMPERATURE SENSOR
CNS
WATER
MS
5
LEFT
STEP
MOTOR
FM
FAN
MOTOR
MS
5
RY6
Y/G G
BLACK
COMPRESSOR
R
S
C
AC-N2
CM
4WV
RY1 RY2
PUMP
C1
RED
WHITE
HF MF LF
3
Synchronization
MOTOR
HUMIDITY
TEMPERATURE SENSOR
WATER LEVEL SWITCH
BLUE
BLUE
BROWN
Wiring diagram
TIMER HEATER SWING SWING
+
_
FAN
SPEED MODE ON/OFF
16

Proper
temperature
OFF
For smart use of the Dehumidifier:
Maintenance
Setting of proper room
temperature
Do not block the air inlet
or outlet
Close doors and windows
during operation
If the unit is not to be used
for a long time, turn off the
power supply main switch.
Use the timer effectively
Use the louvers effectively
TIMER HEATER SW ING SWING
+
_
FAN
SPEED MODE ON /OF F
A
C
%
17

Once every
two weeks
For smart use of the Dehumidifier:
Press the clasp on the top of the grill and pull the grill out,
and then the filter will be taken out along a gradient way.
WARNING
Air Filter cleaning
Remote Controller
Do not use the following for cleaning
Gasoline,benzine, thinner or cleanser may
damage the coating of the unit.Hot water over 40
o o
C (104 C ) may cause
discoloring or deformation.
Body
Before maintenance,be sure to turn off the system and the circuit breaker.
Clean the filter.
Use a vacuum cleaner to remove dust, or wash the filter with
water.After washing, dry the filter completely in the shade.
Then, reinstall it onto the unit.
Maintenance
Do not use water, wipe the controller with a
dry cloth.Do not use glass cleaner or chemical
cloth.
Wipe the air conditioner by using a soft and
dry cloth.For serious stains,use a neutral
detergent diluted with water.Wring the water
out of the cloth before wiping.then wipe off
the detergent completely.
18

1. Operate in FAN mode for about half a day.
2. Turn off the power supply main switch.
4. Take out the batteries from the
wireless remote controller.
3. Cleaning the body.
On a fine day, unit shall be started and operate in
FAN mode for about half a day until the inside of
the unit becomes thoroughly dry.
To keep your Dehumidifier in good condition after season:
Maintenance
OFF
19

Trouble shooting
Before asking for service, check the following first.
Is the air filter dirty? Normally it should be
cleaned every 15 days.
Are there any obstacles before inlet and outlet?
Is temperature set correctly?
Are there some doors or windows left open?
Cause or check points
Phenomenon
The system does not restart
immediately.
Noise is heard:
Smells are generated.
Does not work at all.
Multiple
check
Normal
Performance
inspection
When unit is stopped, it won't restart
immediately until 3 minutes have elapsed
to protect the system.
When the electric plug is pulled out and
reinserted, the protection circuit will work
for 3 minutes to protect the dehumidifier.
During unit operation or at stop, a swishing
or gurgling noise may be heard. At first 2-3
minutes after unit start, this noise is more
noticeable. (This noise is generated by
refrigerant flowing in the system.)
During unit operation, a cracking noise may
be heard. This noise is generated by the
casing expanding or shrinking because of
temperature changes.
Should there be a big noise from air flow in
unit operation, air filter may be too dirty.
This is because the system circulates smells
from the interior air such as the smell of
furniture, cigarettes.
Is power plug inserted?
Is there a power failure?
Is fuse blown out?
Inefficient
20
Table of contents
Popular Other manuals by other brands

THERMA
THERMA Big Dipper W-250-IS Technical data

Blue Ox
Blue Ox BX1508 installation instructions

Electrovert
Electrovert Aquastrom 200 instruction manual

ABB
ABB REU 610 Technical reference manual

HydraMaster
HydraMaster TITAN 425 Owner’s Guide and Maintenance Schedule

Parker
Parker Sporlan SMART Pro/R quick start guide