Sharp R-241CWAA User manual

R-241CWAA
R-241CWAC
R-241CWAP
In interests of user-safety the oven should be restored to its original
condition and only parts identical to those specified should be used.
MODELS R-241CWAA (Argentina)
R-241CWAC (Chile)
R-241CWAP (Peru)
S7908R241CPA/
MICROWAVE OVEN
TABLE OF CONTENTS
CAUTION, MICROWAVE RADIATION............................................................................................................... 1
WARNING............................................................................................................................................................1
PRODUCT SPECIFICATIONS ........................................................................................................................... 2
GENERAL INFORMATION..................................................................................................................................2
APPEARANCE VIEW ......................................................................................................................................... 3
OPERATION SEQUENCE.................................................................................................................................. 4
FUNCTION OF IMPORTANT COMPONENTS .................................................................................................. 5
SERVICING .........................................................................................................................................................6
TEST PROCEDURE........................................................................................................................................... 8
TOUCH CONTROL PANEL...............................................................................................................................14
COMPONENT REPLACEMENT AND ADJUSTMENT PROCEDURE............................................................. 18
MICROWAVE MEASUREMENT ...................................................................................................................... 24
WIRING DIAGRAM........................................................................................................................................... 25
PICTORIAL DIAGRAM ..................................................................................................................................... 26
CONTROL PANEL CIRCUIT .............................................................................................................................27
PRINTED WIRING BOARD ...............................................................................................................................28
PARTS LIST ..................................................................................................................................................... 29
SHARP CORPORATION
SERVICE MANUAL

R-241CWAA
R-241CWAC
R-241CWAP

R-241CWAA
R-241CWAC
R-241CWAP
1
SERVICE MANUAL
SHARP CORPORATION
OSAKA, JAPAN
MICROWAVE OVEN
R-241CWAA (Argentina)
R-241CWAC (Chile)
R-241CWAP (Peru)
GENERAL IMPORTANT INFORMATION
ThisManualhasbeenpreparedtoprovideSharpCorp.Service
engineers with Operation and Service Information.
It is recommended that service engineers carefully study the
entire text of this manual, so they will be qualified to render
satisfactory customer service.
CAUTION
MICROWAVE RADIATION
DO NOT BECOME EXPOSED TO RADIATION FROM
THE MICROWAVE GENERATOR OR OTHER PARTS
CONDUCTING MICROWAVE ENERGY.
Serviceengineersshouldnotbeexposedtothemicrowave
energy which may radiate from the magnetron or other
microwave generating devices if it is improperly used or
connected. All input and output microwave connections,
waveguides, flanges and gaskets must be secured.Never
operate the device without a microwave energy absorbing
load attached. Never look into an open waveguide or
antenna while the device is energized.
WARNING
Never operate the oven until the following points are ensured.
(A) The door is tightly closed.
(B) The door brackets and hinges are not defective.
(C) The door packing is not damaged.
(D) The door is not deformed or warped.
(E) There is not any other visible damage with the oven.
Servicing and repair work must be carried out only by trained
service engineers.
All the parts marked "*" on parts list are used at voltages more
than 250V.
Removal of the outer wrap gives access to potentials above
250V.
All the parts marked "∆" on parts list may cause undue
microwave exposure, by themselves, or when they are dam-
aged, loosened or removed.
TEST PROCEDURE
SERVICING AND
TROUBLESHOOTING CHART
FUNCTION OF IMPORTANT
COMPONENTS
OPERATING SEQUENCE
APPEARANCE VIEW
PRODUCT SPECIFICATIONS
WIRING DIAGRAM
PARTS LIST
MICROWAVE MEASUREMENT
TOUCH CONTROL PANEL
ASSEMBLY
COMPONENT REPLACEMENT
AND ADJUSTMENT PROCEDURE

R-241CWAA
R-241CWAC
R-241CWAP
2
GENERAL INFORMATION
WARNING
THIS APPLIANCE MUST BE EARTHED
IMPORTANT
THE WIRES IN THIS MAINS LEAD ARE COLOURED IN ACCORDANCE WITH THE FOLLOWING CODE:
GREEN-AND-YELLOW (for R-241CWAA & R-241CWAC): EARTH
BLUE : NEUTRAL
BROWN : LIVE
ITEM DESCRIPTION
Power Requirements 220 Volts / 50 Hertz
R-241CWAA, R-241CWAC : Single phase, 3 wire earthed
220 Volts / 60 Hertz
R-241CWAP (Peru) : Single phase, 2 wire
Power Consumption 1.2 kW
Power Output 800 watts nominal of RF microwave energy (IEC 705)
Operating frequency 2450 MHz
Case Dimensions Width 460 mm
Height 290 mm including foot
Depth 372 mm
Cooking Cavity Dimensions Width 314 mm
Height 199 mm
Depth 321 mm
Turntable diameter 295mm
Control Complement Touch Control System
Timer (0 - 99 minutes 99 seconds)
Microwave Power for Variable Cooking
Repetition Rate;
HIGH....................................... Full power throughout the cooking time
MEDIUM HIGH ........................................ approx. 70% of FULL Power
MEDIUM .................................................. approx. 50% of FULL Power
MEDIUM LOW......................................... approx. 30% of FULL Power
LOW......................................................... approx. 10% of FULL Power
EASY DEFROST pad
INSTANT ACTION pads
Number pads
POWER LEVEL pad
TIMER/CLOCK pad
STOP/CLEAR pad
INSTANT COOK/START pad
Set Weight (Approx.) 14 kg
PRODUCT SPECIFICATIONS

R-241CWAA
R-241CWAC
R-241CWAP
3
APPEARANCE VIEW
TOUCH CONTROL PANEL
OVEN
8. Control panel
9. Waveguide cover
10.Power supply cord
11.Turntable
12.Roller stay
13. Earth wire [R-241CWAP]
1. Ventilation openings
2. Oven lamp
3. Door hinges
4. Door safety latches
5. See through door
6. Door seals sealing surfaces
7. Coupling
1. DIGITAL READOUT
2. INDICATOR
3. EASY DEFROST PAD
Press to select the Easy Defrost menu.
4. INSTANT ACTION PADS
Press to cook or reheat 6 popular menus.
5. NUMBER PADS
Press to enter cooking time, clock time, weight of
food.
6. POWER LEVEL PAD
Press to select microwave power setting.
If not pressed, HIGH is automatically selected.
Press to alter the cooking result for automatic
operations.
7. TIMER/CLOCK PAD
Press to set clock, timer, child lock or demonstra-
tion mode.
8. STOP/CLEAR PAD
Press to clear during programming.
Press once to stop operation of oven during cook-
ing; press twice to cancel cooking programme.
9. INSTANT COOK/START PAD
Press once to cook for 1 minute at 100% or in-
crease by 1 minute multiples each time this pad is
pressed during cooking.
Press to start oven after setting programmes.
1
2
3
4
5
7
9
6
8
9
21
5
44
7
11
3
6
8
12
10
13

R-241CWAA
R-241CWAC
R-241CWAP
4
OPERATION SEQUENCE
OFF CONDITION
Closing the door activates all door interlock switches
(1st. latch switch, 2nd. interlock relay control switch).
IMPORTANT
When the oven door is closed, the monitor switch contacts
(COM-NC) must be open.
When the microwave oven is plugged in a wall outlet, rated
voltage is supplied to the control unit.
Figure O-1 on page 25
1. The display flashes "88:88".
2. To set any programmes or set the clock, you must first
touch the stop/ clear pad.
3. " : " appears in the display.
NOTE: When the oven door is opened, the oven lamp
comes on at this time.
MICROWAVE COOKING CONDITION
HIGH COOKING
Enter a desired cooking time with the touching the number
keys and start the oven with touching the start key.
Function sequence
Figure O-2 on page 25
CONNECTED COMPONENTS RELAY
Oven lamp, Fan motor, Turntable motor RY1
Power transformer RY2
1. Rated voltage is supplied to the primary winding of the
powertransformer.Thevoltageisconvertedtoabout3.3
voltsA.C.outputonthefilamentwindingandhighvoltage
of approximately 2000 volts A.C. on the secondary
winding.
2. The filament winding voltage (3.3 volts) heats the
magnetron filament and the high voltage (2000 volts) is
senttothe voltagedoublingcircuit,where itisdoubledto
negative voltage of approximately 4000 volts D.C..
3. The 2450 MHz microwave energy produced in the
magnetron generates a wave length of 12.24 cm. This
energy is channelled through the waveguide (transport
channel)intotheovencavity,wherethefoodisplacedto
be cooked.
4. When the cooking time is up, a signal tone is heard and
therelaysRY1+RY2goback totheirhome position.The
circuits to the oven lamp, power transformer, fan motor
and turntable motor are cut off.
5. When the door is opened during a cook cycle, the
switches come to the following condition.
CONDITION
DURING DOOR OPEN
SWITCH CONTACT COOKING
(NO COOKING)
1st. latch switches COM-NO Closed Open
2nd. interlock relay
control switch COM-NO Closed Open
Monitor switch COM-NC Open Closed
The circuits to the power transformer, fan motor and
turntablemotor arecutoff whenthe1st.latchswitch and
2nd. interlock relay control switch are made open.
The oven lamp remains on even if the oven door is
opened after the cooking cycle has been interrupted,
because the relay RY1 stays closed. Shown in the
display is the remaining time.
6. MONITOR SWITCH CIRCUIT
The monitor switch is mechanically controlled by oven
door, and monitors the operation of the 1st. latch switch
and the 2nd. interlock relay.
6-1 Whentheoven door isopenedduring or afterthe cycle
of a cooking program, the 1st. latch switch and 2nd.
interlock relay control switch must open their contacts
first. After that the contacts (COM-NC) of the monitor
switch can be closed.
6-2. When the oven door is closed, the contacts (COM-NC)
of the monitor switch must be opened. After that the
contactsofthe1st.latchswitch and2nd.interlockrelay
control switch are closed.
6-3. When the oven door is opened and the contacts of the
1st latch switch and 2nd. interlock relay remain closed.
The fuse M8A will blow, because the monitor switch is
closed and a short circuit is caused.
MEDIUM HIGH, MEDIUM, MEDIUM LOW, LOW
COOKING
When the microwave oven is preset for variable cooking
power, rated voltage is supplied to the power transformer
intermittentlywithina32-secondtimebasethroughtherelay
contact which is coupled with the current-limiting relay. The
following levels of microwave power are given.
SETTING;
NOTE: TheON/OFFtimeratiodoesnotexactlycorrespond
to the percentage of microwave power, because
approx. 2 seconds are needed for heating up the
magnetron filament.
32 sec. ON
24 sec. ON
18 sec. ON
12 sec. ON
6 sec. ON
8 sec. OFF
14 sec. OFF
20 sec. OFF
26 sec. OFF
HIGH
MEDIUM HIGH
MEDIUM
MEDIUM LOW
LOW
Approx. 70%
Approx. 50%
Approx. 30%
Approx. 10%

R-241CWAA
R-241CWAC
R-241CWAP
5
FUNCTION OF IMPORTANT COMPONENTS
DOOR OPEN MECHANISM
Thedoorisopenedbypullingthedoor,refertotheFigureD-
1.
Figure D-1. Door Open Mechanism
1ST. LATCH SWITCH AND 2ND. INTERLOCK RE-
LAY CONTROL SWITCH
1. When the oven door is closed, the contacts (COM-NO)
must be closed.
2. When the oven door is opened, the contacts (COM-NO)
must be opened.
MONITOR SWITCH
1. When the oven door is closed, the contacts (COM-NC)
must be opened.
2. When the oven door is opened, the contacts (COM-NC)
must be closed.
3. If the oven door is opened and the contacts (COM-NO)
ofthe1stlatchswitchand2nd.interlockrelayfailtoopen,
the fuse blows simultaneously with closing the contacts
(COM-NC) of the monitor switch.
CAUTION: BEFORE REPLACING A FUSE TEST THE
1ST LATCH SWITCH, 2ND. INTERLOCK
RELAY(RY2), 2ND. INTERLOCK RELAY
CONTROLSWITCH,MONITORSWITCHAND
MONITOR RESISTOR FOR PROPER OP-
ERATION. (REFER TO CHAPTER "TEST
PROCEDURE".)
MONITOR RESISTOR 0.8Ω20W
The monitor resistor prevents the fuse bursting when the
fuseblowsduetotheoperationofthemonitorswitch.
FUSE
1. The fuse blows when the contacts (COM-NO) of the 1st
latch switch and 2nd. interlock relay remain closed with
theovendooropenandwhenthemonitorswitch closes.
2. If the wire harness or electrical components are short-
circuited,thefuseM8Ablowstopreventanelectricshock
of fire hazard.
HIGH VOLTAGE FUSE
The high voltage fuse blows when the high voltage rectifier
or the magnetron is shorted.
THERMAL CUT-OUT 125˚C (OVEN)
The thermal cut-out located on the top of the oven cavity is
designed to prevent damage to the oven if the foods in the
oven catch fire due to over heating produced by improper
setting of cook time or failure of control unit. Under normal
operation, the thermal cut-out remains closed. However,
when abnormally high temperatures are reached within the
oven cavity, the thermal cut-out will open at 125˚C, causing
the oven to shut down. The defective thermal cut-out must
be replaced with a new one.
THERMAL CUT-OUT 95˚C (MAGNETRON )
The thermal cut-out located on the top of the oven cavity is
designed to prevent damage to the magnetron if an over
heated condition develops in the tube due to cooling fan
failure, obstructed air guide, dirty or blocked air intake, etc.
Undernormaloperation,thethermalcut-outremainsclosed.
However, when abnormally high temperatures are reached
tothethermalcut-out,itwillopenat 95˚C,causingtheoven
toshutdown. Whenthe magnetronhas cooled to75˚C,the
thermal cut-out closes and cook cycle will resume.
TURNTABLE MOTOR
The turntable motor drives the roller stay to rotate the
turntable.
FAN MOTOR
The fan motor drives a blade which draws external cool air.
This cool air is directed through the air vanes surrounding
the magnetron and cools the magnetron. This air is chan-
nelledthroughtheovencavitytoremovesteamandvapours
givenofffromtheheatingfoods.Itisthenexhaustedthrough
the exhausting air vents at the oven cavity.
Latch Heads
Latch Hook
Door Monitor
Switch
1st. Latch
Switch
2nd. Interlock
Relay Control
Switch

R-241CWAA
R-241CWAC
R-241CWAP
6
SERVICING
WARNING TO SERVICE PERSONNEL
Microwaveovenscontaincircuitrycapableofproducingveryhighvoltageandcurrent,contactwithanypartofthehigh
voltagecircuitwillresultinelectrocution.Highvoltagecapacitor,Powertransformer,Magnetron,Highvoltagerectifier
assembly, High voltage fuse, High voltage harness.
REMEMBER TO CHECK 3D
1) Disconnect the supply.
2) Door opened, and wedged open.
3) Discharge high voltage capacitor.
WARNING: AGAINST THE CHARGE OF THE
HIGH-VOLTAGE CAPACITOR
The high-voltage capacitor remains charged about
60 seconds after the oven has been switched off.
Wait for 60 seconds and then short-circuit the con-
nection of the high-voltage capacitor (that is, of the
connecting lead of the high-voltage rectifier) against
the chassis with the use of an insulated screwdriver.
Sharprecommend thatwhereverpossible fault-findingis
carriedoutwith thesupply disconnected.Itmay in,some
cases,benecessarytoconnectthesupplyaftertheouter
casehasbeenremoved,inthiseventcarryout3Dchecks
andthendisconnecttheleadstotheprimaryofthepower
transformer. Ensure that these leads remain isolated
from other components and the oven chassis. (Use
insulation tape if necessary.) When the testing is com-
pletedcarryout3Dchecksandreconnecttheleadstothe
primary of the power transformer.
REMEMBER TO CHECK 4R
1) Reconnect all leads removed from components dur-
ing testing.
2) Replace the outer case (cabinet).
3) Reconnect the supply.
4) Run the oven. Check all functions.
Microwave ovens should not be run empty. To test for
the presence of microwave energy within a cavity, place
a cup of cold water on the oven turntable, close the door
and set the power level to HIGH. And set the microwave
timer for two (2) minutes. When the two minutes has
elapsed (timer at zero) carefully check that the water is
now hot. If the water remains cold carry out 3D checks
andre-examinetheconnectionstothecomponentbeing
tested.
When all service work is completed and the oven is fully assembled, the microwave power output should be
checked and microwave leakage test should be carried out.
IMPORTANT: Iftheovenbecomesinoperativebecauseof
a blown fuse M8A in the 1st. latch switch -
2nd. interlock relay - monitor switch - moni-
torresistorcircuit,checkthe1st.latchswitch,
2nd.interlockrelay,2nd.interlockrelaycon-
trol switch, monitor switch and monitor
resistor before replacing the fuse M8A.
When troubleshooting the microwave oven, it is helpful to
followtheSequence ofOperation inperforming thechecks.
Many of the possible causes of trouble will require that a
specific test be performed. These tests are given a proce-
dureletterwhichwillbefoundinthe"TestProcedure"section.
TROUBLESHOOTING GUIDE

R-241CWAA
R-241CWAC
R-241CWAP
7
MAGNETRON
POWER TRANSFORMER
H.V. RECTIFIER ASSEMBLY
HIGH VOLTAGE WIRE
HIGH VOLTAGE CAPACITOR
1ST. LATCH SWITCH
2ND. INTERLOCK RELAY CONTROL SWITCH
MONITOR SWITCH
MONITOR RESISTOR
THERMAL CUT-OUT 125˚C (OVEN)
THERMAL CUT-OUT 95˚C (MG)
FAN MOTOR
TURNTABLE MOTOR
FUSE M8A
TOUCH CONTROL PANEL
RELAY (RY-1, RY-2)
FOIL PATERN ON P.W.B.
POWER SUPPLY CORD
SHORTED WIRE HARNESS
OPENED WIRE HARNESS
OVEN LAMP OR SOCKET
WALL OUTLET
MISADJUSTMENT SWITCH
HOME FUSE OR BREAKER
BLOCKED COOLING FAN
BLOCKED VENTILATION
KEY UNIT
H.V. FUSE
Homefuseblowswhenpower
supply cord is plugged into
wall outlet.
FUSEM8Ablowswhenpower
supply cord is plugged into
wall outlet.
"88:88"doesnotappearindis-
play but power supply cord is
plugged into wall outlet.
Display doesnotoperateprop-
erly when stop/clear pad is
touched.
Oven lamp does not light at
door opened. (Display ap-
pears.)
Oven does not start when the
start pad is touched. (Display
appears)
Ovenlampdoesnotlight(Dis-
play appears.)
Fan motor does not operate.
(Display appears.)
Turntable motor does not op-
erate. (Display appears.)
Oven or any electrical parts
does not stop when cooking
time is 0 or stop/clear pad is
touched.
Oven seems to be operating
butlittleornoheatisproduced
in oven load. (Microwave
power level is set at HIGH)
Oven does not seems to be
operating properly when ME-
DIUM HIGH, MEDIUM, ME-
DIUM LOW or LOW is set.
(Oven operates properly at
HIGH and then the stop/clear
pad is touched the oven
stops.)
Ovengoesintocook cycle but
shutsdownbeforeendofcook-
ing cycle.
OFF
CONDITION
PROBLEM
CONDITION
POSSIBLE CAUSE
AND
DEFECTIVE PARTS
TEST PROCEDURE
ON
CONDITION
CK = Check / RE = Replace
ABC
CK D
EEEFGGHHIKMN
RECK CK RE CK CK CK CK CK
LJ

R-241CWAA
R-241CWAC
R-241CWAP
8
CARRY OUT 3D CHECKS.
Isolate the magnetron from the high voltage circuit by removing all leads connected to the filament
terminal.
To test for an open circuit filament use an ohmmeter to make a continuity test between the magnetron
filament terminals, the meter should show a reading of less than 1 ohm.
To test for a short circuit filament to anode condition, connect ohmmeter between one of the filament
terminals and the case of the magnetron (ground). This test should be indicated an infinite resistance. If
a low or zero resistance reading is obtained then the magnetron should be replaced.
MICROWAVE OUTPUT POWER (1 litre water load)
Thefollowingtestprocedureshouldbecarriedoutwiththemicrowaveoveninafullyassembledcondition
(outercasefitted).MicrowaveoutputpowerfromthemagnetroncanbemeasuredbywayofIEC705,i.e.
it can be measured by using water load how much it can be absorbed by the water load. To measure the
microwave output power in the microwave oven, the relation of calorie and watt is used. When P(W)
heating works for t(second), approximately P x t/4.187 calorie is generated. On the other hand, if the
temperature of the water with V(ml) rises∆T (˚C) during this microwave heating period, the calorie of the
water is V x ∆T.
Measuring condition:
1. Container
The water container must be a cylindrical borosilicate glass vessel having a maximum material
thickness of 3 mm and an outside diameter of approximately 190 mm.
2. Temperature of the oven and vessel
The oven and the empty vessel are at ambient temperature prior to the start of the test.
3. Temperature of the water
The initial temperature of the water is (10±2)˚C.
4. Select the initial and final water temperature so that the maximum difference between the final water
temperature and the ambient temperature is 5˚C.
5. Select stirring devices and measuring instruments in order to minimize addition or removal of heat.
6.
The graduation of the thermometer must be scaled by 0.1˚C at minimum and an accurate thermometer.
7. The water load must be (1000±5) g.
8. “t” is measured while the microwave generator is operating at full power. Magnetron filament heat-up
time is not included.
NOTE: Theoperationtimeofthemicrowaveovenis“t+2”sec.2sec.ismagnetronfilamentheat-uptime.
Measuring method:
1. Measure the initial temperature of the water before the water is added to the vessel.
(Example: The initial temperature T1 = 11˚C)
2. Add the 1 litre water to the vessel.
3. Place the load on the centre of the shelf.
4. Operate the microwave oven at HIGH for the temperature of the water rises by a value ∆T of
(10 ±2)˚C.
5. Stir the water to equalize temperature throughout the vessel.
6. Measure the final water temperature. (Example: The final temperature T2 = 21°C)
7. Calculate the microwave power output P in watts from above formula.
A MAGNETRON TEST
NEVER TOUCH ANY PART IN THE CIRCUIT WITH YOUR HAND OR AN INSULATED TOOL
WHILETHEOVENISINOPERATION.
The formula is as follows;
P x t / 4.187 = V x ∆T P (W) = 4.187 x V x ∆T / t
Our condition for water load is as follows:
Room temperature..............around 20˚C Power supply Voltage.........Rated voltage
Water load.........1000 g Initial temperature...........10±2°C Heating time.........52 sec.
P = 80 x ∆T
TEST PROCEDURES
PROCEDURE
LETTER COMPONENT TEST

R-241CWAA
R-241CWAC
R-241CWAP
9
1000g
1000g
1000g
T1˚C T2˚C
Heat up for 54 sec.
B POWER TRANSFORMER TEST
CARRY OUT 3D CHECKS.
Disconnect the leads to the primary winding of the power transformer. Disconnect the filament and
secondarywindingconnectionsfromtherestoftheHVcircuitry.Usinganohmmeter,setonalowrange,
it is possible to check the continuity of all three windings. The following readings should be obtained:
WARNING: High voltages and large currents are present at the secondary winding and filament
windingofthe powertransformer.Itisvery dangerous toworknearthispart whenthe
oven is on. NEVER make any voltage measurements of the high-voltage circuits,
including the magnetron filament.
Ifthe readingobtainedare notstatedasabove,then thepowertransformerisprobably faultyandshould
be replaced.
CARRY OUT 4R CHECKS.
Initial temperature .................................................................................................. T1 = 11°C
Temperature after (52 + 2) = 54 sec. ..................................................................... T2 = 21°C
Temperature difference Cold-Warm.................................................................... ∆T1 = 10°C
Measured output power
The equation is “P = 80 x ∆T” ...................................................... P = 80 x 10°C = 800 Watts
JUDGMENT: The measured output power should be at least ±15 % of the rated output power.
CAUTION: 1°C CORRESPONDS TO 80 WATTS. REPEAT MEASUREMENT IF THE POWER IS
INSUFFICIENT.
CHIGH VOLTAGE RECTIFIER ASSEMBLY TEST
HIGH VOLTAGE RECTIFIER TEST
CARRY OUT 3D CHECKS.
Isolate the high voltage rectifier assembly from the HV circuit. The high voltage rectifier can be tested
using an ohmmeter set to its highest range. Connect the ohmmeter across the terminal B+C of the high
voltage rectifier and note the reading obtained. Reverse the meter leads and note this second reading.
The normal resistance is infinite in one direction and more than 100 kΩin the other direction.
CARRY OUT 4R CHECKS.
NOTE: FORMEASUREMENTOFTHERESISTANCEOFTHERECTIFIER,THEBATTERIESOFTHE
MEASURING INSTRUMENT MUST HAVE A VOLTAGE AT LEAST 6 VOLTS, BECAUSE
OTHERWISE AN INFINITE RESISTANCE MIGHT BE SHOWN IN BOTH DIRECTIONS.
TEST PROCEDURES
PROCEDURE
LETTER COMPONENT TEST
BC
HIGH VOLTAGE RECTIFIER
R-241CWAA/241CWAC R-241CWAP (Peru)
Primary winding 1.6 ohms approximately 1.35 ohms approximately
Secondary winding 128 ohms approximately 123 ohms approximately
Filament winding less than 1 ohm

R-241CWAA
R-241CWAC
R-241CWAP
10
TEST PROCEDURES
PROCEDURE
LETTER COMPONENT TEST
D HIGH VOLTAGE CAPACITOR TEST
CARRY OUT 3D CHECKS.
A. Isolate the high voltage capacitor from the circuit.
B. Continuitycheckmustbecarriedoutwithmeasuringinstrument whichisset tothehighest resistance
range.
C. Anormalcapacitor shows continuityfor a shorttime(kick) and thena resistance ofabout10MΩafter
it has been charged.
D. A short-circuited capacitor shows continuity all the time.
E. An open capacitor constantly shows a resistance about 10 MΩbecause of its internal 10MΩ
resistance.
F. When the internal wire is opened in the high voltage capacitor shows an infinite resistance.
G. Theresistanceacrossalltheterminalsandthechassismustbe infinitewhenthe capacitoris normal.
If incorrect reading are obtained, the high voltage capacitor must be replaced.
CARRY OUT 4R CHECKS.
E SWITCH TEST
Isolate the switch to be tested and using an ohmmeter check between the terminals as described in the
following table.
CARRY OUT 3D CHECKS.
Table: Terminal Connection of Switch
Plunger Operation COM to NO COM to NC
Released O.C. S.C.
Depressed S.C. O.C.
COM; Common terminal,
NO; Normally open terminal
NC; Normally close terminal
S.C.; Short circuit
O.C.; Open circuit
If incorrect readings are obtained, make the necessary switch adjustment or replace the switch.
CARRY OUT 4R CHECKS.
FMONITOR RESISTOR TEST
CARRY OUT 3D CHECKS.
Disconnecttheleadsfromthemonitorresist.Usinganohmmeterandsetonalowrange.Checkbetween
the terminals of the monitor resistor.
The resistance of monitor resistor is approx. 0.8 ohms.
If incorrect readings are obtained, replace the monitor resistor.
CARRY OUT 4R CHECKS.
GTHERMAL CUT-OUT TEST
CARRY OUT 3D CHECKS.
Disconnect the leads from the terminals of the thermal cut-out. Then using an ohmmeter, make a
continuity test across the two terminals as described in the below.
CARRY OUT 4R CHECKS. Table: Thermal Cut-out Test
Temperature of "ON" condition Temperature of "OFF" condition Indicationofohmmeter(Whenroom
Parts Name (closed circuit). (open circuit). temperature is approx. 20˚C.)
Thermal cut-out 125˚C
This is not resetable type. Above 125˚C Closed circuit
Thermal cut-out 95˚C Below 75˚C Above 95˚C Closed circuit.
If incorrect readings are obtained, replace the thermal cut-out.

R-241CWAA
R-241CWAC
R-241CWAP
11
TEST PROCEDURES
PROCEDURE
LETTER COMPONENT TEST
An open circuit thermal cut-out (MG) indicates that the magnetron has overheated, this may be due to
resistricted ventilation, cooling fan failure or a fault condition within the magnetron or HV circuit.
Anopen circuitthermal cut-out(OVEN) indicatesthat thefood inthe ovencavity maycatch fire,this may
be due to overheating produced by improper setting of the cooking time or failure of the control panel.
H MOTOR WINDING TEST
CARRY OUT 3D CHECKS.
Disconnect the leads from the motor. Using an ohmmeter, check the resistance between the two
terminals as described in the table below.
I FUSE M8A
CARRY OUT 3D CHECKS.
If the fuse M8A is blown when the door is opened, check the 1st latch switch, 2nd. interlock relay, 2nd.
interlock relay control switch, monitor switch and monitor resistor.
If the fuse M8A is blown by incorrect door switching, replace the defective switch(s) and the fuse M8A.
If the fuse M8A is blown, there is a shorts or grounds in electrical parts or wire harness.
Check them and replace the defective parts or repair the wire harness.
CARRY OUT 4R CHECKS.
CAUTION: Only replace fuse with the correct value replacement.
If incorrect readings are obtained, replace the motor.
CARRY OUT 4R CHECKS.
J HIGH VOLTAGE FUSE TEST
CARRY OUT 3D CHECKS.
If the high voltage fuse is blown, there could be a short in the high voltage rectifier or the magnetron.
Check them and replace the defective parts and the high voltage fuse.
CARRY OUT 4R CHECKS.
CAUTION: ONLY REPLACE HIGH VOLTAGE FUSE WITH THE CORRECT VALUE REPLACE-
MENT.
KTOUCH CONTROL PANEL ASSEMBLY TEST
The touch control panel consists of circuits including semiconductors such as LSI, ICs, etc. Therefore,
unlike conventional microwave ovens, proper maintenance cannot be performed with only a voltmeter
and ohmmeter.
In this service manual, the touch control panel assembly is divided into two units, Control Unit and Key
Unit, troubleshooting by unit replacement is described according to the symptoms indicated.
1. Key Unit.
The following symptoms indicate a defective key unit. Replace the key unit.
Table: Resistance of Motor
Resistance
Motors R-241CWAA/241CWAC R-241CWAP (Peru)
Fan motor Approximately 390 ohms Approximately 166 ohms
Turntable motor Approximately 12 kohms Approximately 12 kohms

R-241CWAA
R-241CWAC
R-241CWAP
12
M RELAY TEST
TEST PROCEDURES
PROCEDURE
LETTER COMPONENT TEST
a) When touching the pads, a certain pad produces no signal at all.
b) When touching a number pad, two figures or more are displayed.
c) When touching the pads, sometimes a pad produces no signal.
2. Control Unit.
The following symptoms indicate a defective control unit. Replace the control unit.
2-1 Programming problems.
a) When touching the pads, a certain group of pads do not produce a signal.
b) When touching the pads, no pads produce a signal.
2-2 Display problems.
a) For a certain digit, all or some segments do not light up.
b) For a certain digit, brightness is low.
c) Only one indicator does not light up.
d) The corresponding segments of all digits do not light up; or they continue to light up.
e) Wrong figure appears.
f) A certain group of indicators do not light up.
g) The figure of all digits flicker.
2-3 Other possible problems caused by defective control unit.
a) Buzzer does not sound or continues to sound.
b) Clock does not operate properly.
c) Cooking is not possible.
LKEY UNIT TEST
If the display fails to clear when the Detención/Cancelación pad is depressed, first verify the flat ribbon
cableismakinggoodcontact,verifythat2ndinterlockrelaycontrolswitch(doorsensingswitch) operates
properly; that is the contacts are closed when the door is closed and open when the door is open. If 2nd
interlockrelaycontrolswitch(doorsensingswitch)isgood,disconnecttheflatribboncablethatconnects
the key unit to the control unit and make sure the door sensing switch is closed (either close the door or
shortthedoorsensingswitchconnecter).UsetheKeyunitmatrixindicatedonthecontrolpanelschematic
and place a jumper wire between the pins that correspond to the Detención/Cancelación pad making
momentary contact. If the control unit responds by clearing with a beep, the key unit is faulty and must
bereplaced.Ifthecontrolunitdoesnotrespond,itis afaultyand mustbereplaced. Ifaspecific paddoes
not respond, the above method may be used (after clearing the control unit) to determine if the control
unit or key pad is at fault.
Remove the outer case and check voltage between Pin No 3 of the 2 pin connector (A) and common
terminal (lower terminal) of the relay (RY2) on the control unit with an A.C. voltmeter.
The meter should indicate 220 volts, if not check oven circuit.
RY1 and RY2 Relay Test
These relays are operated by D.C. voltage
Check voltage at the relay coil with a D.C. voltmeter during the microwave cooking operation.
1
2
345
6
7
89
0
Plato
Principal
Nivel de
Potencia
Verdura
Congelada
Papa
Asada
Bebida
Verdure
Fresca
Cronómetro
Reloj
Arroz/
Pasta
G 6 G 5 G 4 G 3 G 2 G 1
G 7
G 8
G 9
G10
Comienzo
Minuto Extra
Detención
Cancelación
DESCONGELACION
AUTOMATICA

R-241CWAA
R-241CWAC
R-241CWAP
13
TEST PROCEDURES
PROCEDURE
LETTER COMPONENT TEST
N PROCEDURES TO BE TAKEN WHEN THE FOIL PATTERN ON THE PRINTED WIRING BOARD
(PWB) IS OPEN
NOTE: At the time of making these repairs,
makeavisual inspectionof the varistor.
Checkforburneddamageandexamine
the transformer with tester for the pres-
ence of layer short-circuit (check pri-
mary coil resistance). If any abnormal
conditionisdetected,replacethedefec-
tive parts.
DC. voltage indicated.......... Defective relay.
DC. voltage not indicated .... Checkdiodewhichisconnectedtotherelaycoil.Ifdiodeisgood,control
unit is defective.
RELAY SYMBOL OPERATIONAL VOLTAGE CONNECTED COMPONENTS
RY1 Approx. 15.0V D.C. Oven lamp / Turntable motor / Cooling fan motor
RY2 Approx. 14.0V D.C. Power transformer
To protect the electronic circuits, this model is provided with a fine foil pattern added to the primary on
the PWB, this foil pattern acts as a fuse. If the foil pattern is open, follow the troubleshooting guide given
below for repair.
Problem: POWER ON, indicator does not light up.
STEPS OCCURANCE CAUSE OR CORRECTION
The rated voltage is not applied between Pin
1 No. 3 of the 2 pin connector (A) and the. Check supply voltage and oven power cord.
common terminal of the relay RY2.
2The rated voltage is applied to primary side Low voltage transformer or secondary circuit defective.
of low voltage transformer. Check and repair.
3 Only pattern at "a" is broken. *Insert jumper wire J1 and solder.
4 Pattern at "a" and "b" are broken. *Insert the coil RCILF2003YAZZ between "c" and "d".
12
a
b c
d
31
P
AC (N) FM TTM OL RY1
VRS1
T1 RY2
(J1)

R-241CWAA
R-241CWAC
R-241CWAP
14
The touch control section consists of the following units as
shown in the touch control panel circuit.
(1) Key Unit
(2) Control Unit
The principal functions of these units and their related
signals are explained below.
Key Unit
The key unit is composed of a matrix, signals generated in
theLSIaresenttothekeyunitthroughR81,R82,R83,R90,
R91 and R92.
When a key pad is touched, a signal is completed through
the key unit and passed back to the LSI through R60, R61,
R62, R63 to perform the function that was requested.
Control Unit
Control unit consists of LSI, ACL circuit, indicator circuit,
power source circuit, relay circuit, buzzer circuit and syn-
chronizing signal circuit.
1) ACL
ThiscircuitgeneratesasignalwhichresetstheLSItothe
initial state when power is supplied.
2) Indicator Circuit
This circuit consists of 4-digits, 12-segments and 3-
common electrodes using a Liquid Crystal Display.
TOUCH CONTROL PANEL ASSEMBLY
OUTLINE OF TOUCH CONTROL PANEL
3) Power Source Circuit
This circuit generates voltage necessary in the control
unitfromtheAClinevoltage.Inaddition,thesynchroniz-
ing signal is available in order to compose a basic
standard time in the clock circuit.
Symbol Voltage Application
VC -5V LSI(IC1)
4) Relay Circuit
To drive the magnetron, fan motor, turntable motor and
light the oven lamp.
5) Buzzer Circuit
The buzzer is responsive to signals from the LSI to emit
audiblesounds(keytouchsoundandcompletionsound).
6) Synchronizing Signal Circuit
The power source synchronizing signal is available in
order to compose a basic standard time in the clock
circuit. It accompanies a very small error because it
works on commercial frequency.
7) 2nd. Interlock Relay Control Switch (Door Sensing
Switch)
A switch to “tell” the LSI if the door is open or closed.

R-241CWAA
R-241CWAC
R-241CWAP
15
1-12 SEG0-SEG11 OUT Segment data signal.
Connected to LCD.
The relation between signals are as follows:
LSI signal (Pin No.) LCD (Pin No.) LSI signal (Pin No.) LCD (Pin No.)
SEG 0 (1) ..............................S12 SEG 6 (7)................................. S6
SEG 1 (2) ..............................S11 SEG 7 (8)................................. S5
SEG 2 (3) ..............................S10 SEG 8 (9)................................. S4
SEG 3 (4) ................................S9 SEG 9 (10)............................... S3
SEG 4 (5) ................................S8 SEG 10 (11)............................. S2
SEG 5 (6) ................................S7 SEG 11 (12)............................. S1
13 R60 IN Signal coming from touch key.
Wheneither G10lineon keymatrixistouched,a correspondingsignaloutofR81 -R83
and R90 - R92 will be input into R60. When no key is touched, the signal is held at “H”
level.
14 R61 IN Signal similar to R60.
WheneitherG9lineonkeymatrixistouched,acorrespondingsignalwillbeinputintoR60.
15 R62 IN
Signal similar to R60.
WheneitherG8lineonkeymatrixistouched,acorrespondingsignalwillbeinputintoR60.
16 R63 IN Signal similar to R60.
WheneitherG7 lineon keymatrix istouched,a correspondingsignal willbeinput intoR60.
17 AIN0 IN To input signal which communicates the door open/close information to LSI.
Door close “H” level signal (0V). Door open “L” level (-5V).
18-20 AIN1-AIN3 IN Terminal to change functions according to the Model.
By using the A/D converter contained in the LSI, DC voltage in accordance with the
Model in operation is applied to set up its function.
21 VSS IN Power source voltage: -5V.
VSS voltage of power source circuit input.
22 R70 OUT Magnetron high-voltage circuit driving signal.
Toturnonandoffthecookrelay(RY2). Thesignals
holds “L” level during microwave cooking and “H”
level while not cooking. In other cooking modes
(variable cooking) the signal turns to “H” level and
“L” level in repetition according to the power level.
23 PULSE OUT Signal to sound buzzer (2.0 kHz).
A: key touch sound.
B: Completion sound.
R-241CWAA/ R-241CWAC R-241CWAP (Peru)
24 R72 OUT Oven lamp, fan motor and turntable motor driving signal.
Toturnonandoffshutoffrelay(RY1).Thesquarewaveformvoltageisdeliveredtothe
RY1 driving circuit and RY2 control circuit.
R-241CWAA/ R-241CWAC R-241CWAP (Peru)
DESCRIPTION OF LSI
LSI(IZA906DR)
The I/O signal of the LSI(IZA906DR) are detailed in the following table.
Pin No. Signal I/O Description
H : GND
L : -5V
OFF
ON
ON
OFF OFF
H : GND
L : -5V
P-HI
P-70 24 sec. 8 sec.
A
B
0.12 sec.
2.4 sec.
H : GND
L : -5V
H : GND
L : -5V
During cooking L : -5V
H : GND
20.0 msec.
A
B
0.1 sec.
2.0 sec.
H : GND
L : -5V
H : GND
L : -5V
During cooking L : -5V
H : GND
16.7 msec.

R-241CWAA
R-241CWAC
R-241CWAP
16
25 R73 OUT Terminal not used.
26 INT2 IN Signal synchronized with commercial power source frequency.
This is the basic timing for time processing of LSI.
R-241CWAA/R-241CWAC R-241CWAP (Peru)
27 R81 OUT Key strobe signal.
Signal applied to touch-key section. A pulse signal is input to R60 - R63 terminal while
one of G6 line keys on key matrix is touched.
28 R82 OUT Key strobe signal.
Signal applied to touch-key section. A pulse signal is input to R60 - R63 terminal while
one of G5 line keys on key matrix is touched.
29 R83 OUT Key strobe signal.
Signal applied to touch-key section. A pulse signal is input to R60 - R63 terminal while
one of G4 line keys on key matrix is touched.
30 R90 OUT Key strobe signal.
Signal applied to touch-key section. A pulse signal is input to R60 - R63 terminal while
one of G3 line keys on key matrix is touched.
31 R91 OUT Key strobe signal.
Signal applied to touch-key section. A pulse signal is input to R60 - R63 terminal while
one of G2 line keys on key matrix is touched.
32 R92 OUT Key strobe signal.
Signal applied to touch-key section. A pulse signal is input to R60 - R63 terminal while
one of G1 line keys on key matrix is touched.
33 XIN IN Internal clock oscillation frequency setting input.
The internal clock frequency is set by inserting the capacitor-resistor oscillation circuit
with respect to XOUT terminal.
34 XOUT OUT Internal clock oscillation frequency control output.
Output to control oscillation input of XIN.
35 RESET IN Auto clear terminal.
Signal is input to reset the LSI to the initial state when power is supplied. Temporarily
setto“L”levelthemomentpowerissupplied,atthistimetheLSIisreset.Thereafterset
at “H” level.
36 HOLD IN/OUT Connected to GND.
37 VLC IN Signal synchronized with commercial power source frequency.
Signal similar to VSS.
38 COM1 OUT Common data signal: COM1.
Connected to LCD (Pin No. C1)
39 COM2 OUT Common data signal: COM2.
Connected to LCD (Pin No. C2)
40 COM3 OUT Common data signal: COM1.
Connected to LCD (Pin No. C3)
41 COM4 OUT Terminal not used.
42 VDD IN Power source voltage input terminal.
Connected to GND.
Pin No. Signal I/O Description
20.0 msec
H : GND
L : -5V 16.7 msec
H : GND
L : -5V

R-241CWAA
R-241CWAC
R-241CWAP
17
1. Precautions for Handling Electronic Components
This unit uses CMOS LSI in the integral part of the
circuits. When handling these parts, the following pre-
cautions should be strictly followed. CMOS LSI have
extremely high impedance at its input and output termi-
nals. For this reason, it is easily influenced by the
surrounding high voltage power source, static electricity
charge in clothes, etc., and sometimes it is not fully
protected by the built-in protection circuit.
In order to protect CMOS LSI.
1) Whenstoringandtransporting,thoroughlywrapthem
in aluminium foil. Also wrap PW boards containing
them in aluminium foil.
2) When soldering, ground the technician as shown in
the figure and use grounded soldering iron and work
table.
2. Shapes of Electronic Components
3. Servicing of Touch Control Panel
We describe the procedures to permit servicing of the
touch control panel of the microwave oven and the
precautions you must take when doing so.
To perform the servicing, power to the touch control
panel is available either from the power line of the oven
itself or from an external power source.
(1) Servicing the touch control panel with power
supply of the oven :
CAUTION:
THE HIGH VOLTAGE TRANSFORMER OF THE
MICROWAVEOVENISSTILLLIVEDURINGSERV-
ICING AND PRESENTS A HAZARD .
Therefore, when checking the performance of the
touchcontrolpanel, puttheoutercabinet ontheoven
to avoid touching the high voltage transformer, or
unplug the primary terminal (connector) of the high
voltage transformer to turn it off; the end of such
connector must be insulated with an insulating tape.
After servicing, be sure to replace the leads to their
original locations.
A. On some models, the power supply cord between
the touch control panel and the oven itself is so
short that the two can’t be separated.
Forthosemodels,checkandrepairallthecontrols
(sensor-related ones included) of the touch con-
trol panel while keeping it connected to the oven.
SERVICING
ECB
B. On some models, the power supply cord between
the touch control panel and the oven proper is so
long enough that they may be separated from
each other. For those models, therefore, it is
possible to check and repair the controls of the
touchcontrolpanelwhilekeepingitapartfromthe
ovenproper;inthiscaseyoumustshortbothends
of the door sensing switch (on PWB) of the touch
controlpanelwithajumper,whichbringsaboutan
operational state that is equivalent to the oven
door being closed. As for the sensor-related con-
trols of the touch control panel, checking them is
possible if the dummy resistor(s) with resistance
equal to that of the controls are used.
(2)Servicing the touch control panel with power
supply from an external power source:
Disconnect the touch control panel completely from
the oven proper, and short both ends of the door
sensing switch (on PWB) of the touch control panel,
whichbringsaboutanoperationalstatethatisequiva-
lent to the oven door being closed. Connect an
external power source to the power input terminal of
the touch control panel, then it is possible to check
andrepairthecontrolsof thetouch controlpanel; itis
also possible to check the sensor-related controls of
thetouchcontrolpanelbyusingthedummyresistor(s).
4. Servicing Tools
Toolsrequiredtoservicethetouchcontrolpanelassem-
bly.
1) Soldering iron: 30W
(It is recommended to use a soldering iron with a
grounding terminal.)
2) Oscilloscope: Single beam, frequency range: DC -
10MHz type or more advanced model.
3) Others: Hand tools
5. Other Precautions
1) Beforeturningonthepowersourceofthecontrolunit,
remove the aluminium foil applied for preventing
static electricity.
2) Connect the connector of the key unit to the control
unit being sure that the lead wires are not twisted.
3) Afteraluminiumfoilisremoved,becarefulthatabnor-
mal voltage due to static electricity etc. is not applied
to the input or output terminals.
4) Attach connectors, electrolytic capacitors, etc. to
PWB, making sure that all connections are tight.
5) Be sure to use specified components where high
precision is required.
approx. 1M ohm
Transistor
2SA933S
DTA143ES
KRA101M
KRC243M

R-241CWAA
R-241CWAC
R-241CWAP
18
COMPONENT REPLACEMENT AND ADJUSTMENT PROCEDURE
WARNING: Avoid possible exposure to microwave energy. Please follow the instructions below
before operating the oven.
1. Disconnect oven from power supply.
2. Visuallycheckthedoorandcavityfaceplatefor damage
(dents, cracks, signs of arcing etc.).
Carry out any remedial work that is necessary before oper-
ating the oven.
Do not operate the oven if any of the following conditions
exist;
1. Door does not close firmly.
2. Door hinge, support or latch hook is damaged.
3. The door gasket or seal or damaged.
4. The door is bent or warped.
5. There are defective parts in the door interlock system.
6. There are defective parts in the microwave generating
and transmission assembly.
7. There is visible damage to the oven.
Do not operate the oven:
1. Without the RF gasket (Magnetron).
2. If the wave guide or oven cavity are not intact.
3. If the door is not closed.
4. If the outer case (cabinet) is not fitted.
Please refer to ‘OVEN PARTS, CABINET PARTS, CONTROL PANEL PARTS, DOOR PARTS’, when carrying out any of
the following removal procedures:
WARNING FOR WIRING
To prevent an electric shock, take the following man-
ners.
1. Before wiring,
1) Disconnect the power supply.
2) Open the door and wedge the door open.
3) Dischargethehighvoltagecapacitorandwaitfor60
seconds.
2. Don't let the wire leads touch to the following parts;
1) High voltage parts:
Magnetron, High voltage transformer, High voltage
capacitor, High voltage fuse and High voltage recti-
fier assembly.
2) Hot parts:
Oven lamp, Magnetron, High voltage transformer
and Oven cavity.
3) Sharp edge:
Bottomplate,Ovencavity,Waveguideflange,Chas-
sis support and other metallic plate.
4) Movable parts (to prevent a fault)
Fan blade, Fan motor, Switch
3. Do not catch the wire leads in the outer case cabinet.
4. Insert the positive lock connector certainly until its pin
islocked.Andmakesurethatthewireleadsshouldnot
come off even if the wire leads is pulled.
5. To prevent an error function, connect the wire leads
correctly, referring to the Pictorial Diagram.
To remove the outer case proceed as follows.
1. Disconnect oven from power supply.
2. Open the oven door and wedge it open.
3. Removetheeight(8)screwsfromrearandalongtheside
edge of case.
4. Slide the entire case back about 3cm to free it from
retaining clips on the cavity face plate.
5. Lift the entire case from the oven.
6. Discharge the H.V. capacitor before carrying out any
further work.
7. Do not operate the oven with the outer case removed.
N.B.; Step 1, 2 and 6 form the basis of the 3D checks.
CAUTION: DISCHARGEHIGHVOLTAGECAPACITOR
BEFORETOUCHINGANYOVENCOMPO-
NENT OR WIRING.
OUTER CASE REMOVAL
1. CARRY OUT 3D CHECKS.
2. Disconnect the wire leads (main wire harness and H.V.
fuse) from power transformer.
3. Disconnect the filament lead of power transformer from
the magnetron.
4. Disconnect the filament lead of the power transformer
from high voltage capacitor.
5. Remove the two (2) screws holding the transformer to
bottom plate and (2) screws from bottom plate.
6. Remove the transformer.
POWER TRANSFORMER REMOVAL
This manual suits for next models
2
Table of contents
Other Sharp Microwave Oven manuals

Sharp
Sharp R-9320G-BS User manual

Sharp
Sharp R-330E User manual

Sharp
Sharp R-4P58 User manual

Sharp
Sharp R-200 User manual

Sharp
Sharp YC-PC284AU-S User manual

Sharp
Sharp R-899R User manual

Sharp
Sharp R-798-A Instruction Manual

Sharp
Sharp R-898M User manual

Sharp
Sharp R-969 Instruction Manual

Sharp
Sharp R-208 Instruction Manual

Sharp
Sharp R-360EG User manual

Sharp
Sharp R-390B User manual

Sharp
Sharp R-231(W)W Instruction Manual

Sharp
Sharp R642WW User manual

Sharp
Sharp R-750D Use and care manual

Sharp
Sharp R-508DK User manual

Sharp
Sharp R-852N Instruction Manual

Sharp
Sharp R-630DKA User manual

Sharp
Sharp SM-267FH(ST) User manual

Sharp
Sharp R-371 User manual