Siemens Building Technologies, Inc. P84391-003B
8 Fernwood Road Sheet 1 of 4
Florham Park, New Jersey 07932
INSTALLATION INSTRUCTIONS
MULTI-CANDELA FOUR WIRE HORN STROBE APPLIANCES
(WALL MOUNT VERSION)
IMPORTANT – All audible and visual signaling appliances must be
installed in accordance with all applicable national and local fire alarm
codes and any other required regulatory agencies.
Series HS-MC Multi-Candela Horn Strobe provides four selectable
candela settings (15, 30, 75, 110). The HS-MC allows for independent
operation of the strobe circuit and the horn circuit. It is the ideal choice
for retrofit applications as well as new installations. The HS-MC
appliance is UL Listed under Standard 1971 for Signaling Appliances
for the Hearing Impaired and UL Standard 464 for Audible Signal
Appliances. The HS-MC is also ULC Listed under Standard CAN/ULC-
S526-02 for Visual Signaling Appliances and Standard CAN/ULC-
S525-99 for Audible Signaling Appliances for Fire Alarm Systems. It is
listed for indoor use only and can be mounted to double-gang, 4”
backbox, 100mm European backbox or MT-SUR-BOX surface
backbox (See wiring and mounting information). This appliance is
listed for wall mounting only. The HS-MC appliance uses a xenon
flashtube with solid state circuitry enclosed in a polycarbonate lens to
provide maximum visibility and reliability for effective visible signaling.
Siemens Series HS appliances provide a selectable continuous or
Code 3 horn tone and non-synchronized strobe when connected
directly to a Fire Alarm Control Panel (FACP). They can also provide a
synchronized Code 3 (or March Time) horn tone and synchronized
strobe when connected to a notification appliance circuit running the
Siemens sync protocol. HS appliances can be field set for High (HI),
medium (MED) dBA or low (LO) dBA sound output. .
NOTE: The Code 3 temporal pattern (1/2 second on, 1/2 second off,
1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) is
specified by ANSI and NFPA 72 for standard emergency evacuation
signaling. The Code 3 Horn should be used only for fire
evacuation signaling and not for any other purpose.
The HS-MC is designed for use with either filtered DC or unfiltered full-
wave-rectified (FWR) input voltage. All inputs are polarized for
compatibility with standard reverse polarity supervision of circuit wiring
by an FACP.
NOTE: All Canadian Installations should be in accordance with the
Canadian Standard for the Installation of Fire Alarm Systems –
CAN/ULC-S524-01 and Canadian Electrical Code, Part 1. Final
acceptance is subject to authorities having jurisdiction (AHJ).
NFPA 72/ANSI 117.1 conform to ADAAG Equivalent Facilitation
Guidelines in using fewer, higher intensity strobes within the same
protected area.
NOTE: Refer to P/N 315-096363 for the maximum number of
appliances on a single notification appliance circuit.
SPECIFICATIONS:
Table 1: UL/ULC Listed Models and Ratings
Model* Operating Voltage (Special Application)
Per UL 1971
(VDC/VRMS)
Voltage Range Per
CAN/ULC-S526-02
(VDC/VRMS)
Strobe
Candela
(cd)
HS-MC 16.0-33.0 20.0-31.0 15/30/75/110
*Available in red and white.
Table 2: dBA Sound Output for 24VDC Models
Reverberant Per UL 464 Anechoic dBA @ 10 Ft. Per CAN/ULC-S525-99
Description
Volume 16.0VDC 24VDC 33.0VDC 20.0VDC 24VDC 31.0VDC
Low 80 83 86 88 90 91
Continuous Horn Medium 85 88 91 93 95 97
High 88 91 93 97 99 100
Low 75 79 82 88 90 91
Code 3 Horn or Medium 80 84 86 93 95 97
March Time** High 84 87 89 97 99 100
**Available in sync mode only.
Siemens Building Technologies, Inc. P84391-003B
8 Fernwood Road Sheet 2 of 4
Florham Park, New Jersey 07932
Figure 1: ULC Directional Characteristics
81dB83dB
-6dB
-3dB
95dB
-3dB
-6dB
8
5
dB
-3dB
-3dB
-6dB
95dB
-6dB
20° 30°
80°
30° 27°
60° 48°
NOTES:
1. The strobe will produce 1 flash per second over the Input Voltage
range.
2. This horn/strobe model meets the required light distribution
patterns defined in UL 1971 and ULC-S526-02.
3. This model is UL/ULC Listed for indoor use with a temperature
range of +32°F to +120°F (0°C to +49°C) and maximum humidity
of 93% ±2% RH. The effect of shipping and storage
temperatures shall not adversely affect the performance of the
appliance when it is stored in the original cartons and not
subjected to misuse or abuse.
When calculating the total current: Use Tables 3 & 3A to determine the highest value of “RMS Current” for an individual HS-MC then multiply the value
by the total number of HS-MC Appliances. Be sure to add the currents for any other appliances powered by the same source and to include any
required safety factors.
Note: These notification appliances are UL Listed as “Special Application”. They are intended to be used only with Siemens notification appliance
circuits.
CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT.
Table 3: Current Ratings (Horn Only)
Maximum RMS Current (Amps)
Input Voltage Lo Med Hi
DC 16-33VDC 0.027 0.068 0.110
FWR 16-33VRMS 0.041 0.050 0.094
Table 3A: Current Ratings (Strobe Only)
Maximum RMS Current (Amps)
Input Voltage 15cd 30cd 75cd 110cd
DC 16-33VDC 0.064 0.098 0.175 0.233
FWR 16-33VRMS 0.108 0.164 0.268 0.368
THESE APPLIANCES WERE TESTED TO THE VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING FILTERED DC OR UNFILTERED
FULL-WAVE-RECTIFIED VOLTAGE. DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.
Note: Refer to the installation instructions for the appropriate NAC to find the maximum allowed voltage drop. Use this value along with the current draw
for the appliance to determine the allowable wire resistance. The maximum wire resistance between strobes shall not exceed 35 ohms.
CAUTION: The strobe is not designed to be used on coded systems in which the applied voltage is cycled on and off.
NOTE: The horn circuit is compatible with coded systems only if the unit is wired for independent horn and strobe operation per figure 4.
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S
PRIMARY AND SECONDARY POWER SOURCES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS
OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE
RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN
PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
Siemens Building Technologies, Inc. P84391-003B
Sheet 3 of 4
SOUND OUTPUT (SPL) AND CANDELA SETTINGS:
Figure 2: Showing Location of Candela Selector and Jumper Plugs
R
+ STR -
J3
+ AUD -
TB1
3
J2 C
O
E
D
J1
H
L
M
B
P83511 ( )
AH C1 R5
TOP
75 30
15 110
CANDELASELECTOR
CANDELA
POINTER
3
J2 C
O
E
D
J1
H
L
M
Factory setting is on 15 candela, Medium dB and Code 3.
WARNING: THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION.
WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT “CLICKS” IN PLACE. AFTER CHANGING THE
CANDELA SETTING, THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION.
Figure 3: Jumper Plug Settings for High, Medium, Low dB,
Code 3 Horn (or March Time) and Continuous Horn Setting.
J1
HIGH LOW
HC
O
D
E
3 3
E
D
O
C
SETTING
HORN
SETTING
HORN
J1
J2 J2 J2
M
L
H
M
L
H
M
L
MEDIUM
SETTING
HORN CODE 3
SETTING
HORN CONTINUOUS
SETTING
* HORN
• Use needle nose pliers to pull and properly insert the jumper
plug.
• No jumper plug is needed for continuous horn setting.
However, it is recommended that the jumper plug be retained
in the unit for future use (if needed) as shown in Figure 3.
• The HS-MC must be set for Code 3 (or March Time) horn
when used with the sync module. If the HS-MC audible is
connected to a coded system, the continuous horn setting
must be used.
WIRING AND MOUNTING INFORMATION:
Figure 4: Audible signal and strobe operate independently. Figure 4A: Audible and strobe operate in unison. Shunt wires are
supplied.
+ STR - + AUD -
TB1
+
FROMFACPOR
PRECEDINGAPPLIANCE
TONEXTAPPLIANCE
OR EOLR.
FROMFIREALARM
CONTROLPANEL(FACP) OR
PRECEDINGAPPLIANCE
TONEXTAPPLIANCE
OR END OF LINE
RESISTOR(EOLR).
-
-
+
+
-
-
+
Figure 5:
+ STR - + AUD -
TB1
+
TONEXTAPPLIANCE
OR EOLR
FROM FACP OR
PRECEDINGAPPLIANCE
-
RED SHUNT WIRE BLACK SHUNTWIRE
-
+
• HS-MC Appliances have in-out wiring terminals that accepts two #12 to #18 American Wire Gauge (AWG) wires at each
screw terminal. Strip leads 3/8” inches for connection to screw terminals.
• Break all in-out wire runs on supervised circuit supervision as shown in Figure 5. The polarity shown in the wiring
diagrams is for the operation of the appliances. The polarity is reversed by the FACP during supervision.
The following figures (A-D) show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option. If these
limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the
product. Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed
multiconductor cable or 3/4" conduit fittings are used.
Siemens Building Technologies, Inc. P84391-003B
Sheet 4 of 4
FigureA
FLUSH (4" BOX)
#8-32 SCREWS
4" SQ. X 2-1/8"
DEEPBACKBOX
SCREW COVERS
8 488
AWG #18 AWG #16 AWG #14 AWG#12
MAXIMUM NUMBER OF CONDUCTORS
Figure B
8 888
AWG #18 AWG #16 AWG#14 AWG #12
MAXIMUM NUMBER OF CONDUCTORS
#6-32SCREWS
SCREWCOVERS
FLUSH (2-GANG BOX)
2-GANGx 3-1/2"
DEEPBACKBOX
FigureC
8 888
AWG #18 AWG#16 AWG #14 AWG #12
MAXIMUM NUMBER OF CONDUCTORS
WOODSCREWS
#8-18 SCREWS
SCREW COVERS
SURFACE MOUNTING
BACKBOX
(MT-SUR-BOX)
Figure D
8 888
AWG #18 AWG #16 AWG #14 AWG #12
MAXIMUM NUMBER OF CONDUCTORS
#8-18SCREWS
SCREWCOVERS
CONCEALED CONDUITMOUNTING
BACKBOX
(MT-SUR-BOX)
EXISTING
BOXINWALL
MOUNTING PROCEDURES:
1. This HS-MC model can be flush mounted to a 100mm
backbox (Figure A) or double-gang backbox (Figure B).
It can also be surface mounted to a indoor/outdoor
backbox (Figures C & D). Mounting hardware for each
mounting option is supplied.
2. Conduit entrances to the backbox should be selected to
provide sufficient wiring clearance for the installed
product. Do not pass additional wires (used for other
than the signaling appliance) through the backbox. Such
additional wires could result in insufficient wiring space
for the signaling appliance.
3. When terminating field wires, do not use more lead
length than required. Excess lead length could result in
insufficient wiring space for the appliance.
4. Use care and proper techniques to position the field wires
in the backbox so that they use minimum space and
produce minimum stress on the product. This is
especially important for stiff, heavy gauge wires and
wires with thick insulation or sheathing.
5. Connect field wires to the HS-MC terminal block (polarity
must be observed). Bend the field wires up 90°at the
connection to the terminal block.
6. Carefully push the field wires into the backbox by hand.
Press the HS-MC to the backbox, verifying that it is
seated and aligned correctly.
7. Fasten the HS-MC to the backbox using the supplied
screws.
The HS-MC 110cd setting is Listed for use in sleeping or non-sleeping areas when installed in accordance with appropriate NFPA Standards and the
AHJ.
WARNING: A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW, UNDER
CERTAIN CIRCUMSTANCES, MIGHT INDUCE A PHOTO-SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY. STROBE REFLECTIONS IN A
GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE. TO MINIMIZE THIS POSSIBLE HAZARD, SIEMENS STRONGLY
RECOMMENDS THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW WHICH
EXCEEDS FIVE Hz AT THE OPERATING VOLTAGE OF THE STROBES. SIEMENS ALSO STRONGLY RECOMMENDS THAT THE INTENSITY AND
COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS, STANDARDS,
REGULATIONS, CODES AND GUIDELINES.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital appliance, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses and can
radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures: 1) Reorient or relocate the receiving antenna, 2) Increase the separation between the
equipment and receiver, 3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected, and 4) Consult the
dealer or an experienced radio/TV technician for help.

Popular Horn manuals by other brands

CyberData 011472 Installation quick reference

CyberData

CyberData 011472 Installation quick reference

Vixen Horns VXO8315/4114B manual

Vixen Horns

Vixen Horns VXO8315/4114B manual

Vixen Horns VXO8705/1101 installation guide

Vixen Horns

Vixen Horns VXO8705/1101 installation guide

Vixen Horns VXO8530/3311C installation guide

Vixen Horns

Vixen Horns VXO8530/3311C installation guide

Bosch LBC 3428 installation manual

Bosch

Bosch LBC 3428 installation manual

Wheelock NS-121575W installation instructions

Wheelock

Wheelock NS-121575W installation instructions

Vixen Horns VXO8115/3114 installation guide

Vixen Horns

Vixen Horns VXO8115/3114 installation guide

Altec Lansing 311-60 HF HORN manual

Altec Lansing

Altec Lansing 311-60 HF HORN manual

Vixen Horns VXO8350/1164 installation guide

Vixen Horns

Vixen Horns VXO8350/1164 installation guide

Toa SC-615BS instruction manual

Toa

Toa SC-615BS instruction manual

Hadley 900CA installation instructions

Hadley

Hadley 900CA installation instructions

ITC T-720B owner's manual

ITC

ITC T-720B owner's manual

Gentex GC Series manual

Gentex

Gentex GC Series manual

Toa LE-420 Specifications

Toa

Toa LE-420 Specifications

Vixen Horns VXO8805/4114 installation guide

Vixen Horns

Vixen Horns VXO8805/4114 installation guide

Federal Signal Corporation 31X Series Installation and service instructions

Federal Signal Corporation

Federal Signal Corporation 31X Series Installation and service instructions

BERG Sound box user manual

BERG

BERG Sound box user manual

Electro-Voice Constant-Directivity Horn HP420 specification

Electro-Voice

Electro-Voice Constant-Directivity Horn HP420 specification

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.