Siemens sitrans PROBE LU Instruction manual

Quick Start Manual 12/2013
SITRANS
Ultrasonic Transmitters
SITRANS Probe LU (HART)

IQ300IX.fm Page 5 Tuesday, October 2, 2001 1:43 PM

A5E32168031 SITRANS Probe LU (HART) – QUICK START MANUAL Page EN-1
mmmmm
English
SITRANS Probe LU Quick Start Manual
This manual outlines the essential features and functions of SITRANS Probe LU. We strongly
advise you to acquire the detailed version of the manual so you can use your instrument to its
fullest potential. The complete manual is available on our website at:
www.siemens.com/probelu. The printed manual is available from your local Siemens
representative.
Questions about the contents of this manual can be directed to:
Siemens Milltronics Process Instruments
1954 Technology Drive, P.O. Box 4225
Peterborough, Ontario, Canada, K9J 7B1
Email: techpubs.smpi@siemens.com
MILLTRONICS is a registered trademark of Siemens Milltronics Process Instruments
Safety Guidelines1
Warning notices must be observed to ensure personal safety as well as that of others, and to
protect the product and the connected equipment. These warning notices are accompanied by
a clarification of the level of caution to be observed.
Copyright Siemens Milltronics
Process Instruments 2013.
All Rights Reserved
Disclaimer of Liability
We encourage users to purchase
authorized bound manuals, or to view
electronic versions as designed and
authored by Siemens Milltronics Process
Instruments. Siemens Milltronics
Process Instruments will not be
responsible for the contents of partial or
whole reproductions of either bound or
electronic versions.
While we have verified the contents of this manual
for agreement with the instrumentation described,
variations remain possible. Thus we cannot
guarantee full agreement. The contents of this
manual are regularly reviewed and corrections are
included in subsequent editions. We welcome all
suggestions for improvement.
Technical data subject to change.
1. This warning symbol is used when there is no corresponding caution symbol on the product.
WARNING: relates to a caution symbol on the product, and means that failure to
observe the necessary precautions can result in death, serious injury, and/or
considerable material damage.
WARNING1: means that failure to observe the necessary precautions can result
in death, serious injury, and/or considerable material damage.
Note: means important information about the product or that part of the operating manual.

Page EN-2 SITRANS Probe LU (HART) – QUICK START MANUAL A5E32168031
mmmmm
English
SITRANS Probe LU
SITRANS Probe LU is a loop-powered continuous level monitor, using advanced ultrasonic
techniques. The unit consists of an electronic component coupled to the transducer and
process connection.
The transducer is available in ETFE (ethylene-tetrafluoroethylene) or PVDF (polyvinylidene
fluoride), allowing SITRANS Probe LU to be used in a wide variety of industries and
applications using corrosive chemicals.
The ultrasonic transducer contains a temperature sensing element to compensate for
temperature changes in the application.
Communication is via HART1, and signals are processed using Sonic Intelligence®.
Specifications
For a complete listing, see the SITRANS Probe LU Instruction Manual. For Approvals
information, please refer to the device nameplate.
Ambient/Operating Temperature
WARNING: Changes or modifications not expressly approved by Siemens
could void the user’s authority to operate the equipment.
Notes:
• SITRANS Probe LU is to be used only in the manner outlined in this manual,
otherwise protection provided by the equipment may be impaired.
• This product is intended for use in industrial areas. Operation of this equipment in a
residential area may cause interference to several frequency based
communications.
1. HART® is a registered trademark of the HART Communication Foundation.
Note: Process temperature and pressure capabilities are dependent upon information
on the product nameplate. The reference drawing listed on the nameplate can be
downloaded from the Siemens website. Go to the product page at:
www.siemens.com/probelu.
process temperature:
–40 to +85 °C (–40 to +185 °F)
ambient temperature
surrounding enclosure:
–40 to +80 °C (–40 to +176 °F)
hand programmer
product nameplate
flange adaptor
customer-
supplied flange

A5E32168031 SITRANS Probe LU (HART) – QUICK START MANUAL Page EN-3
mmmmm
English
Power
• Maximum 30 V DC
• 4 to 20 mA
Approvals
• General: CSAUS/C, FM, CE
• Hazardous: Intrinsically Safe (Europe) ATEX II 1 G Ex ia IIC T4 Ga
(US/Canada) FM/CSA: (barrier required)1
Class I, Div. 1, Groups A, B, C, D
Class II, Div. 1, Groups E, F, G
Class III T4
(International) IECEx SIR 13.0008X Ex ia IIC T4 Ga
(Brazil) INMETRO DNV 12.0070 X
Ex ia IIC T4 Ga
IP67/IP68
-40 ºC ≤Ta ≤+80 ºC
DNV #OCP 0017
ABNT NBR IEC 60079-0:2008
ABNT NBR IEC 60079-11:2009 e
ABNT NBR IEC 60079-26:2008
Non-incendive (US) FM: 2
Class I, Div. 2, Groups A, B, C, D T5
• Marine Lloyd’s Register of Shipping
ABS Type Approval
Nominal 24 V DC at max. 550 Ohm: for other configurations see the full manual.
1. See
FM Intrinsically safe connection drawing
on page 1
of Appendix A, for reference drawing
23650516, or
CSA Intrinsically Safe connection drawing
on page 2 of Appendix A, for reference
drawing 23650517.
2. See
FM Class 1, Div. 2 connection drawing
on page 3 of Appendix A, for reference drawing 23650583.
Note: Approved dust-tight and water-tight conduit seals are required for outdoor Type 4X /
NEMA 4X, Type 6 / NEMA 6, IP67, IP68 locations.

Page EN-4 SITRANS Probe LU (HART) – QUICK START MANUAL A5E32168031
mmmmm
English
Installation
Mounting Location
Recommendations:
• Ambient temperature within –40 to +80 °C (–40 to +176 °F).
• Easy access for viewing the display and programming via the hand programmer.
• An environment suitable to the housing rating and materials of construction.
• Keep the sound path perpendicular to the material surface.
Precautions:
• Avoid proximity to high voltage or current wiring, high voltage or current contacts, and to
variable frequency motor speed controllers.
• Avoid interference to the sound path from obstructions or from the fill path.
WARNINGS:
• Materials of construction are chosen based on their chemical compatibility (or
inertness) for general purposes. For exposure to specific environments, check with
chemical compatibility charts before installing.
• This product can only function properly and safely if it is correctly transported,
stored, installed, set up, operated, and maintained.
• The user is responsible for the selection of bolting and gasket materials which will
fall within the limits of the flange and its intended use, and which are suitable for
the service conditions.
Note: Installation shall only be performed by qualified personnel and in accordance with
local governing regulations.
10°
seams
rungs
pipe
Fill
The sound path should be:
• perpendicular to the
monitored surface
• clear of rough walls,
seams, rungs, or
other obstructions
• clear of the fill path

A5E32168031 SITRANS Probe LU (HART) – QUICK START MANUAL Page EN-5
mmmmm
English
Mounting Instructions
SITRANS Probe LU is available in three thread types: 2" NPT, 2" BSP, or PF2/G.
1. Before inserting SITRANS Probe LU into its mounting connection, ensure that the threads
are of the same type to avoid damaging them.
2. Simply screw SITRANS Probe LU into the process connection, and hand tighten.
Wiring
Power1
Connecting SITRANS Probe LU
Note: Ideally, mount SITRANS Probe LU so that the face of the transducer is at least
300 mm (1 ft) above the highest anticipated level.
WARNINGS:
DC terminals shall be supplied from an SELV 1source in accordance with IEC-
1010-1 Annex H.
All field wiring must have insulation suitable for rated voltages.
1. Safety Extra Low Voltage
Notes:
• For detailed information on Intrinsically
Safe set-ups, please see the full manual.
• Use shielded, twisted pair cable (wire
gauge AWG 22 to AWG 14 /0.34 mm2to
2.08 mm2).
• Separate cables and conduits may be
required to conform to standard
instrumentation wiring practices, or
electrical codes.
• The non-metallic enclosure does not
provide a continuous ground path
between conduit connections: use
grounding-type bushings and jumpers.
water-
tight gland
hinged lid
cover screws
threaded
connection

Page EN-6 SITRANS Probe LU (HART) – QUICK START MANUAL A5E32168031
mmmmm
English
.
1
Wiring setups for hazardous area installations
Always check the device nameplate and process device tag to verify the approval rating.
1. Intrinsically Safe wiring
• For power demands see
Loop Voltage versus Loop Resistance
on page 4.
• For wiring requirements: follow local regulations.
• Approved dust-tight and water-tight conduit seals are required for outdoor Type 4X /
NEMA 4X, Type 6 / NEMA 6, IP67, IP68 locations.
• Refer to
Instructions specific to hazardous area installations (Reference European
ATEXDirective 94/9/EC, Annex II, 1/0/6)
on page 7.
1. If cable is routed through conduit, use only approved suitable-size hubs for waterproof application.
mA
cable
terminals for
loop current
1. Strip the cable jacket for approximately 70 mm
(2.75") from the end of the cable, and thread the
wires through the gland1.
2. Connect the wires to the terminals as shown
above: the polarity is identified on the terminal
block.
3. Tighten the gland to form a good seal.
4. Close the cover and tighten screws: please do
not overtighten screws. Recommended torque is
1.1 to 1.7 N-m (10 to 15 in-lb).
Serial No: GYZ / B1034567
Power Rating: 24V Max., 4-20 mA
Nom., 30V
Ui=30V
Ii=120mA
Pi=0.8W
Ci=3.6nF
Li=0 mH
Assembled in Canada with domestic and imported parts
Siemens Milltronics Process Instruments, Peterborough
SITRANS Probe LU
7MLxxxx-xxxxx-xxxx Encl.: NEMA/TYPE 4X, 6, IP67, IP68
Amb.Temp.: – 40°C to 80°C
HART
Ex ia IIC T4 Ga
DNV 12.0070 X
0518
1G
Ex ia IIC T4 Ga
II
SIRA 06ATEX2355X
IECEx SIR 13.0008X
ATENÇÃO - RISCO POTENCIAL DE CARGA ELETROSTÁTICA - VEJA INSTRUÇÕES
KCC-REM-S49
PROBELU
The ATEX certificate can be downloaded from the product
page of our website at: www.siemens.com/probelu. Go to Support > Approvals /
Certificates.
The IECEx certificate listed on the nameplate can be viewed on the IECEx website. Go to:
http://iecex.iec.ch and click on Ex Equipment Certificates of Conformity then enter the
certificate number IECEx SIR 13.0008X.
Device nameplate (ATEX/IECEX/INMETRO/C-TICK)
Serial No: GYZ / S1034567 Encl.: NEMA/TYPE 4X, 6, IP67, IP68
Amb.Temp.: – 40°C to 80°C
Power Rating: 24V Max., 4-20 mA
Nom., 30V
WARNING: Possible static hazard, do not rub or clean on site.
Class I, Div 1, Group A, B, C, D
Class II, Div 1, Group E, F, G
Class III
Temp. Code: T4
CSA per drawing: 23650517
FM per drawing: 23650516
HART
Assembled in Canada with domestic and imported parts
Siemens Milltronics Process Instruments, Peterborough
SITRANS Probe LU
7ML1234-78910-ABC-D
159134
Vmax=30V
Imax = 120 mA
Pmax = 0.8 W
Ci=3.6nF
Li=0.5mH
FM Intrinsically Safe connection drawing number 23650516, and CSA Intrinsically Safe
connection drawing number 23650517 can be downloaded from the product page of our
website at: www.siemens.com/probelu. Go to Support > Installation Drawings > Level
Measurement > Continuous - Ultrasonic.
Device nameplate (FM/CSA)

A5E32168031 SITRANS Probe LU (HART) – QUICK START MANUAL Page EN-7
mmmmm
English
2. Non-incendive wiring (FM US only)
• For power demands, see
Loop Voltage versus Loop Resistance
on page 4 of Appendix A.
Instructions specific to hazardous area installations
(Reference European ATEXDirective 94/9/EC, Annex II, 1/0/6)
The following instructions apply to the SITRANS Probe LU covered by certificate number SIRA
06ATEX2355X:
1. For use and assembly, refer to the main instructions.
2. The equipment is certified for use as Category 1G equipment.
3. The equipment may be used with flammable gases and vapors with apparatus groups IIA,
IIB, and IIC, and temperature classes T1, T2, T3, and T4.
4. The equipment is certified for use in an ambient temperature range of –40 C to +80 C.
5. The equipment has not been assessed as a safety related device (as referred to by
Directive 94/9/EC Annex II, clause 1.5).
6. Installation and inspection of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice (EN 60079-14 and EN 60079-
17 in Europe).
7. Repair of this equipment shall be carried outby suitably trained personnel in accordance
with the applicable code of practice (e.g. EN 60079-19 within Europe).
8. Components to be incorporated into or used as replacements in the equipment shall be
fitted by suitably trained personnel in accordance with the manufacturer’s
documentation.
(continued on next page)
9. It is the responsibility of the user to ensure that manual override is possible in order to
shut down the equipment and protective systems incorporated within automatic
processes which deviate from the intended operating conditions, provided that this does
not compromise safety.
10. The ‘X’ suffix to the certificate number relates to the following special conditions for safe
use:
Parts of the enclosure may be non-conducting and may generate an ignition-
capable level of electrostatic charge under certain extreme conditions. The
user should ensure that the equipment is not installed in a location where it
may be subjected to external conditions (such as high-pressure steam) which
might cause a build-up of electrostatic charge on non-conducting surfaces.
Class I,Div.2,
Group A,B,C, D
Temp.Code:T5
HART
Serial No: GYZ / S1034567
Encl.: NEMA/TYPE 4X, 6, IP67, IP68
Amb.Temp.: – 40°C to 80°C
Power Rating: 24V Max., 4-20 mA
Nom., 30V
Assembled in Canada with domestic and imported parts
Siemens Milltronics Process Instruments, Peterborough
SITRANS Probe LU
7ML1234-78910-ABC-D
FM Class 1, Div 2 connection drawing
number 23650583 can be downloaded from the product page of our website at:
www.siemens.com/probelu. Go to Support > Installation Drawings > Level Measurement >
Continuous - Ultrasonic.

Page EN-8 SITRANS Probe LU (HART) – QUICK START MANUAL A5E32168031
mmmmm
English
11. If the equipment is likely to come into contact with aggressive substances, then it is the
responsibility of the user to take suitable precautions that prevent it from being adversely
affected, thus ensuring that the type of protection is not compromised.
Aggressive substances:e.g. acidic liquids or gases that may attack metals, or
solvents that may affect polymeric materials.
Suitable precautions: e.g. regular checks as part of routine inspections or
establishing from the material’s data sheet that it is
resistant to specific chemicals.
12. Equipment Marking:
The equipment marking contains at least the information on the product nameplate, shown on
the inside front cover of this manual.
Operation
RUN Mode and PROGRAM Mode
SITRANS Probe LU has two modes of operation: RUN and PROGRAM.
SITRANS Probe LU automatically starts in RUN mode when power is applied, and detects the
material level. The primary reading displays the material level (in meters) referenced from
Empty (process empty level). This is the default start-up display mode.
System status is displayed on the LCD, or on a remote communications terminal.
RUN Mode Display
Use the hand programmer to control the display.12
1 – Primary Reading (displays level, distance, or volume1, in either units or percent).
2 – Secondary Reading (displays Parameter number for Auxiliary Reading2)
3 – Echo status indicator: Reliable Echo or Unreliable Echo
4 – Units or Percent
5 – Active bar graph represents material level
6 – Auxiliary Reading (depending on the parameter selected, it displays milliAmp value,
distance, or echo confidence, with units where applicable.)
1. For details on displaying flow instead of volume, please see P050 in the full manual.
2. Press to display the auxiliary reading field when in RUN mode.
m
m
Normal operation Failsafe operation
1
3
4
5
1
3
4
5
2
6
6

A5E32168031 SITRANS Probe LU (HART) – QUICK START MANUAL Page EN-9
mmmmm
English
If the echo confidence drops below the echo confidence threshold, the failsafe timer starts
running. When the timer expires, the letters LOE (Loss of Echo) alternate with the reading
every two seconds, and the Reliable Echo indicator is replaced by the Unreliable indicator.
When a valid reading is received, the level reading display returns to normal operation.
PROGRAM Mode Display
Programming
• Set parameters to suit your specific application.
•ActivatePROGRAM mode at any time, to change parameter values and set operating
conditions.
• For local programming, use the Siemens hand programmer.
• For programming from a distance, use either a PC running SIMATIC PDM, or a HART
handheld communicator.
Hand programmer
1
23
4
1– Primary Reading (displays parameter value)
2– Secondary Reading (displays parameter number)
3– Programming indicator
4– Auxiliary Reading (displays parameter names for P001 to
P010, if a language is selected. It displays the index value
for indexed parameters, such as P054).
display
hand programmer
max. 600 mm
(2 ft)
Key Programming Mode
Decimal point1
1. Press plus three-digit parameter number, to set
parameter to show in the auxiliary display.
Negative value
CLEAR value
TOGGLE between Units and % on parameter
value
End PROGRAM session and enable RUN mode
Update echo quality parameters
Parameter scroll-up
Parameter scroll-down
DISPLAY opens parameter fields
ENTER the displayed value
For direct access to SITRANS Probe LU,
point the programmer at the SITRANS
Probe LU display and press the keys.
(For detailed instructions, see the next
page.)

Page EN-10 SITRANS Probe LU (HART) – QUICK START MANUAL A5E32168031
mmmmm
English
Low temperature effects on RUN/PROGRAM modes
If the internal temperature falls to –30 oC (–22 oF) or below, it will affect both RUN and
PROGRAM modes.
RUN mode will operate normally, with the following exceptions:
• hand programmer operation is disabled
• the LCD displays only limited information: the bar graph and the reliable/unreliable echo
indicator
PROGRAM mode:
• hand programmer operation is disabled
Security: (P000: Lock)
* Factory setting for P069 is 1954: after a new value is entered and accepted, it becomes the
default setting.
Activating SITRANS Probe LU
Power up the instrument. SITRANS Probe LU starts in RUN mode.
Value Description
Value stored in P069 *Lock off: programming permitted
other Lock activated: no changes permitted
Notes:
• Keep infrared devices such as laptops, cell phones, and PDA’s, away from SITRANS
Probe LU to prevent inadvertent operation.
• The following instructions apply when using the Hand Programmer.
• Do not use the Hand Programmer at the same time as SIMATIC PDM, or erratic operation
may result.
•PressPROGRAM then DISPLAY to access PROGRAM mode, and press
PROGRAM to return to RUNmode.
• You do not need to key in initial zeros when entering a parameter number: for example,
for P005, key in 5.

A5E32168031 SITRANS Probe LU (HART) – QUICK START MANUAL Page EN-11
mmmmm
English
Accessing a parameter
1. Press PROGRAM then DISPLAY , to activate
PROGRAM mode.
2. Either use the ARROW keys to scroll to a
different parameter, or:
3. Press DISPLAY to open the Parameter Number
field.
4. Key in the desired parameter number followed by
ENTER .
5. For example: press then .
6. The LCD displays the new parameter number and
value.
Changing a Parameter Value
1. Key in the new value.
2. Press ENTER to set the value.
Parameter Reset to Factory Default
1. Scroll to the parameter or enter its address.
2. Press CLEAR then ENTER . The value returns to the default setting.
Master Reset (P999)
Returns all parameters except P000 and P069 to default settings. (The learned TVT curve is not
lost.)
1. Press PROGRAM ,then DISPLAY to activate PROGRAM mode.
2. Press DISPLAY to open parameter fields.
3. Key in 999.
4. Press CLEAR then ENTER , to Clear All and initiate
reset. The LCD displays C.ALL.
5. Reset complete. (Reset takes several seconds to complete.)
Notes:
• Security must be disabled to enable programming: set P000 to the Unlocked Value stored
in P069. (A remote master can still change configuration, if P799 is set to allow this.)
• Invalid entries will be rejected or limited.
•CLEAR can be used to clear the field.
Parameter Value
Parameter Number
PROGRAM Icon
current value

Page EN-12 SITRANS Probe LU (HART) – QUICK START MANUAL A5E32168031
mmmmm
English
Quick Setup: steps 1 to 10
1. Select language (P010: Language)
2. Set P001: Operation (measurement mode)
3. Set Measurement Response (P003)
Set P003 to a measurement response speed just faster than the maximum filling or emptying
rate (whichever is greater).
Note: Default values (factory settings) are marked by an asterisk (*) in the tables.
Notes:
• Setting P001 resets Span (P007), unless Span has previously been set to a different value.
• Changing P001 may reset Output Function (P201): this applies to HART only.
Values 1*Level returns distance to material level referenced from Empty (process empty level). The
reading is returned in volumetric units if parameters 050 to 055 are set to enable this.
2Space returns distance to material level referenced from Span (process full level).
3Distance returns distance to material level from reference point (transducer face).
Values
1 * slow 0.1m/minute
2medium 1m/minute
3fast 10m/minute
ENGLISH DEUTSCH FRANÇAIS ESPAÑOL
P000 LOCK VERRIEGELG VERROUIL BLOQUEO
P001 OPERATION BETRIEB FONCTIONMT FUNCIONAM.
P003 MEAS RESP REAKTIONSZ TEMPS REP. TIEMPO R.
P004 ANTENNA ANTENNE ANTENNE ANTENA
P005 UNITS EINHEIT UNITES UNIDADES
P006 EMPTY MESSBER. VIDE VACIO
P007 SPAN MESSSPANNE PLAGE RANGO
P010 LANGUAGE SPRACHE LANGUE IDIOMA
Values
0*
Numeric/None
1English
2German
3French
4Spanish
Level
(P001 = 1)Space
(P001 = 2)Distance
(P001 = 3)
Distance
Space
Level
P007
P006
100%
(20 mA)
(20 mA)
100%
0%
(4 mA)
0%
(4 mA)
100%
(20 mA)
(4 mA)
0%
Empty
Span Span
Empty
Span
Empty
transducer
face
mA Output with Level, Space, and Distance operation

A5E32168031 SITRANS Probe LU (HART) – QUICK START MANUAL Page EN-13
mmmmm
English
4. Select measurement units (P005)
5. Set process empty level (P006: Empty)
Empty can be set to any distance: not necessarily
the bottom of the tank.
6. Set measurement range (P007: Span)1
.
7. Minimize false reflections: Set P838 (Auto False Echo Suppression Distance)
Values
1*meters
2centimeters
3millimeters
4feet
5inches
Note:
• P006 and P007 are interlinked: see
notes attached to P007.
Values Range 0.0000 to 6.000 m (20 ft) or
0.0000 to 12.000 m (40 ft)
Default Maximum range
Values
Range 0.0000 to 6.000 m (20 ft) or
0.0000 to 12.000 m (40 ft) Span can be set at any distance above
Empty level
Default 5.725 m (18.78 ft) or
11.725 m (38.47 ft)
1. Default setting for Blanking is 0.25 m (10").
Notes:
• Setting P006 resets Span, if it has not previously been set to a different value.
• The default setting for Span is based on Operation (P001) and Empty (P006). Span is set to
Empty minus 110% of Blanking distance1, unless Operation is set to distance (P001=3). In
this case, Span is set to Empty distance.
• Always prevent the monitored surface from approaching within 0.3 m (1 ft) of the
transducer face. This provides a 0.05 m (2") safety margin, as 0.25 m (10") is the minimum
distance detectable.
Use P838 and P837
together: follow the
instructions for P837. Value
Range
(depends on model)
Maximum range:
0.000 to 6.000 m (20 ft) or
0.000 to 12 m (40 ft)
Default 1.000 m (3.28 ft)
P007
P006
100%
0%
Level Setup
Level
Empty
Span
transducer
face

Page EN-14 SITRANS Probe LU (HART) – QUICK START MANUAL A5E32168031
mmmmm
English
8. Enable False Echo Suppression: set P837 (Auto False Echo Suppression)
Using P837 and P838 (perform this function at low tank levels)
The TVT (Time Varying Threshold) curve sets a threshold which screens out false echoes1. If
SITRANS Probe LU displays an incorrect full level, or if the reading fluctuates between a false
high level and a correct level, use P838 and P837 together to elevate the TVT (Time Varying
Threshold) in this region and de-sensitize the receiver from any ‘base noise’ caused by internal
transducer reflections, nozzle echoes, or other vessel false echoes2.
.Using P837 and P838 (continued)
a. Determine the actual distance from the transducer face to the material level.
b. Select P838 and key in [distance to material level – 0.5 m].
c. Select P837, then press 2(Learn) and ENTER . P837 will automatically revert to 1(use
Learned TVT) after a few seconds.
9. Return to RUN
Press PROGRAM to return to RUN mode: setup is complete.
SITRANS Probe LU Communications: HART
• You will need the full manual to acquire the list of applicable parameters.
• Please contact your local representative concerning the availability of the HART DD for
SITRANS Probe LU.
• We recommend that you use SIMATIC Process Device Manager (PDM) to program your
instrument.
Maintenance
SITRANS Probe LU requires no maintenance or cleaning.
Unit Repair and Excluded Liability
For detailed information, please see the inside back cover.
Value
0Off
1 * Use "learned" TVT
2"Learn"
1. False echoes can be caused by obstructions in the beam path.
2. For more details on Auto False Echo Suppression, please see the full manual.
Notes:
• Use this function only if there is a minimum distance of 2 meters from SITRANS Probe LU
to the material. This function works best if the vessel is empty or nearly empty.
• Set P837 and P838 during start up, if possible.
• If the vessel contains an agitator, the agitator should be running.
Note: See
mA Output with Level, Space, and Distance operation
on page 12 for an
illustration of the mA output with different modes of operation.

A5E32168031 SITRANS Probe LU (HART) – KVIKSTART MANUAL Side DA-1
mmmmm
Dansk
SITRANS Probe LU Kvikstart Manual
Denne manual opridser de væsentligste karakteristika og funktioner af SITRANS Probe LU.
Vi anbefaler dig kraftigt at anskaffe den detaljerede version af denne manual, så du kan anvende
apparatet fuldt ud. Den komplette manual kan fås på vort website:
www.siemens.com/probelu. Den trykte manual kan fås hos din lokale Siemens repræsentant.
Spørgsmål vedrørende indholdet af denne manual kan rettes til:
Siemens Milltronics Process Instruments
1954 Technology Drive, P.O. Box 4225
Peterborough, Ontario, Canada, K9J 7B1
E-mail: techpubs.s[email protected]
MILLTRONICS er et registreret varemærke, der tilhører Siemens Milltronics Process Instruments
Sikkerhedsvejledning1
De anførte advarsler skal overholdes for at sikre egen og andres sikkerhed samt for at
beskytte produktet og det tilhørende udstyr. Disse advarsler ledsages af en tydeliggørelse af
graden af forsigtighed, der bør overholdes.
Copyright Siemens Milltronics
Process Instruments 2013.
Alle rettigheder forbeholdes
Ansvarsfragåelse
Vi opfordrer brugerne til at anskaffe de
autoriserede, indbundne manualer eller
at læse de elektroniske versioner, der er
udarbejdet og skrevet af Siemens
Milltronics Process Instruments.
Siemens Milltronics Process Instruments
påtager sig intet ansvar for indholdet af
delvise eller fuldstændige gengivelser af
indbundne eller elektroniske versioner.
Skønt vi har kontrolleret, at indholdet af denne
manual stemmer overens med de beskrevne
instrumenter, kan der stadig forekomme
variationer. Vi kan derfor ikke garantere en
fuldstændig overensstemmelse. Indholdet af
denne manual revideres jævnligt, og eventuelle
rettelser inkluderes i de efterfølgende udgaver. Vi
modtager gerne forslag til forbedringer.
Retten til ændringer af de tekniske data
forbeholdes.
1Dette advarselssymbol anvendes, når der ikke er noget tilsvarende advarselssymbol på produktet.
ADVARSEL: vedrører et advarselssymbol på produktet og betyder, at en
manglende overholdelse af de nødvendige forholdsregler kan føre til død,
alvorlig personskade og/eller omfattende materielle skader.
ADVARSEL1: betyder, at en manglende overholdelse af de nødvendige
forholdsregler kan føre til død, alvorlig personskade og/eller omfattende
materielle skader.
Bemærk: betyder vigtige oplysninger om produktet eller denne del af brugsvejledningen.

Side DA-2 SITRANS Probe LU (HART) – KVIKSTART MANUAL A5E32168031
mmmmm
Dansk
SITRANS Probe LU
SITRANS Probe LU er en sløjfeforsynet kontinuert niveaumåler, der anvender avanceret
ultralydsteknologi. Dette instrument består af en elektronisk komponent, der er forbundet til
transduceren og procestilslutningen.
Transduceren fås i ETFE (ethylen-tetrafluoroethylen) eller PVDF (polyvinylidenfluorid), hvilket
gør det muligt at anvende SITRANS Probe LU inden for et stort udvalg af industrier og
applikationer, hvor der bruges korrosive kemikalier.
Ultralydstransduceren indeholder en temperaturføler for at kompensere for
temperaturændringer i applikationen.
Kommunikationen foregår via HART1, og signalerne behandles ved hjælp af Sonic
Intelligence®.
Tekniske data
For en fuldstændig liste, jf. SITRANS Probe LU Instruktionsbogen. For oplysninger om
godkendelser henvises der til apparatets navneskilt.
Omgivende temperatur/Driftstemperatur
ADVARSEL: Ændringer eller modifikationer, der ikke er udtrykkeligt godkendt
af Siemens, kan ophæve brugerens ret til at benytte udstyret.
Bemærkninger:
• SITRANS Probe LU bør kun anvendes som beskrevet i denne manual, da den
beskyttelse, udstyret yder, ellers kan forringes.
• Dette produkt er beregnet til anvendelse i industriområder. Brugen af dette udstyr i
et beboelsesområde kan forårsage interferens med forskellige frekvensbaserede
kommunikationer.
1HART® er et registreret varemærke, der tilhører HART Communication Foundation.
Bemærk: De tilladelige procestemperaturer og -tryk afhænger af oplysningerne på
apparatets navneskilt. Referencetegningen, der er angivet på dette skilt, kan
downloades fra Siemens' website:
www.siemens.com/probelu.
procestemperatur:
–40 til +85 °C (–40 til +185 °F)
omgivende temperatur
omkring huset:
–40 til +80 °C (–40 til +176 °F)
håndholdt
programmeringsenhed produktets navneskilt
flangeadapter
brugerleveret
flange

A5E32168031 SITRANS Probe LU (HART) – KVIKSTART MANUAL Side DA-3
mmmmm
Dansk
Strømforsyning
• Max. 30 V dc
• 4 til 20 mA
Godkendelser
• Alment: CSAUS/C, FM, CE
• Risikoområder Egensikker (Europa) ATEX II 1 G Ex ia IIC T4 Ga
(US/Canada) FM/CSA1: (barriere påkrævet)
Klasse I, Div. 1, Gruppe A, B, C, D
Klasse II, Div. 1, Gruppe E, F, G
Klasse III T4
(Internationalt) IECEx SIR 13.0008X Ex ia IIC T4 Ga
(Brasilien) INMETRO DNV 12.0070 X
Ex ia IIC T4 Ga
IP67/IP68
-40 ºC ≤Ta ≤+80 ºC
DNV #OCP 0017
ABNT NBR IEC 60079-0:2008
ABNT NBR IEC 60079-11:2009 e
ABNT NBR IEC 60079-26:2008
Ikke-antændingsfarlig
(US) FM2:
Klasse I, Div. 2, Gruppe A, B, C, D T5
• Maritimt Lloyd's Skibsregister
ABS typegodkendelse
Nominel 24 V dc ved max. 550 Ohm: for andre konfigurationer henvises der til den
komplette manual.
1Se referencetegning nr. 23650516
FM Intrinsically safe connection drawing
på side 1
i Appendiks A eller
referencetegning nr. 23650517
CSA Intrinsically Safe connection drawing
på side 2 i Appendiks A.
2Se referencetegning nr. 23650583
FM Class 1, Div. 2 connection drawing
på side 3 i Appendiks A.
Bemærk: Godkendte støv- og vandtætte kabelrørstætninger er påkrævet for udendørs
Type 4X / NEMA 4X, Type 6 / NEMA 6, IP67, IP68 placeringer.

Side DA-4 SITRANS Probe LU (HART) – KVIKSTART MANUAL A5E32168031
mmmmm
Dansk
Installation
Montagested
Anbefalinger:
• Omgivende temperatur på mellem -40 til +80 °C (-40 til +176 °C).
• Lettilgængeligt for aflæsning af displayet og programmering ved hjælp af den håndholdte
programmeringsenhed.
• Omgivelser, der svarer til instrumenthusets klassificering og konstruktionsmaterialer.
• Sørg for, at lydens vej er vinkelret på materialets overflade.
Forholdsregler:
• Undgå nærhed til højspændings- eller stærkstrømsledninger, højspændings- eller
stærkstrømskontakter samt motorhastighedsregulatorer med variabel frekvens.
• Undgå, at materialpåfyldningen eller andre forhindringer interfererer med lydens vej.
ADVARSLER:
• Konstruktionsmaterialerne er valgt på basis af deres kemiske kompatibilitet (eller
inerti) ved almindelig brug. Hvis de skal udsættes for særlige omgivelser, bør
foreneligheden kontrolleres i tabeller over kemiske kompatibiliteter inden
installationen.
• Dette produkt kan kun fungere korrekt og sikkert, såfremt det transporteres,
opbevares, installeres, indstilles, bruges og vedligeholdes rigtigt.
• Brugeren er ansvarlig for at vælge sammenboltnings- og pakningsmaterialer, der
ligger inden for flangens begrænsninger og dens påtænkte anvendelse, og som
passer til anvendelsesforholdene.
Bemærk: Installationen må kun foretages af kvalificeret personale og under overholdelse
af de lokalt gældende regler.
10°
svejsesøm
stigetrin
rør
Påfyldning
Lydens vej bør være:
•vinkelretpåden
målte overflade
• fri for ru vægge,
svejsesøm, stigetrin
eller andre
forhindringer
• udenfor
påfyldningsområdet
Other manuals for sitrans PROBE LU
7
Table of contents
Languages:
Other Siemens Plumbing Product manuals
Popular Plumbing Product manuals by other brands

Delta
Delta T31338-WL quick start guide

Alfalaval
Alfalaval Unique SSV Aseptic instruction manual

Willoughby Industries, Inc.
Willoughby Industries, Inc. WWF-4203 Series Installation & operation manual

Delta
Delta T2788 quick start guide

Delta
Delta 597LF MPU Series manual

Delta
Delta Innovations Jetted Shower T18430 Series parts manual

Delta
Delta Jetted Shower installation instructions

Silvercrest
Silvercrest SGS 100 A1 operating instructions

ICON
ICON COBALT Pro 101819 quick start guide

Range Master
Range Master Aquaquad Monobloc TAQ1 Quick installation guide

Concept2
Concept2 BDC6529 manual

Delta
Delta 19940T-SD-DST Series quick start guide