Simpex Electronic SRP-2309-100-RGBW-24V User manual

1
Änderungen vorbehalten. Angaben ohne Gewähr. / 26.09.2019 © Simpex Electronic
SRP-2309-100-RGBW-24V
100W DALI DT8 DIMMABLE LED DRIVER
Product Features
• DT8 Dimmable 4-Channel RGBW LED driver
• 100-240VAC wide input voltage
• 4-channels DC24V constant voltage output
• Built-in DALI interface, DALI DT8 device, each dvice is controlled via a single DALI address
• Color control according to DALI specicaons of device type 8
• Complies to DALI Standards IEC 62386-209-:2011
• Compable with universal DALI masters that supports DT8 commands
• Compable with AC-Push dimmer
• Compabel with DT6 DALI commands
• IP20 rang, suitable for indoor LED lighng applicaons

2
Änderungen vorbehalten. Angaben ohne Gewähr. / 26.09.2019 © Simpex Electronic
Technical data
INPUT
Voltage Range 100-240VAC
Frequency Range 50/60Hz
Power Factor (typ.) >0.9@230VAC
Total Harmonic Distoron THD ≤ 15% (@ full load /230VAC)
Eciency typ. 90% @ 230VAC full load
AC Current (typ) 1.2A @ 100VAC, 0.5A @ 230VAC
Inrush Current (typ) Cold start max. 50A@230VAC
Leakage Current < 0.5mA/230VAC
Stand by Power Consumpon 1W
OUTPUT
LED Channel 4
DC Voltage 24VDC
Voltage Tolerance +/- 1%
Max. Current max. 4.1A/CH, CH1+CH2+CH3+CH4 = 4.1A
Rated Power max. 98.4W
PROTECTION Short Circuit Yes, recovers automacally aer fault condion is removed
Over Temperature Yes, recovers automacally aer fault condion is removed
CONTROL
Dimming Interface DALI DT8
Dimming Range 0.1% - 100% for color sengs
1%-100% for brightness sengs (DT6, AC Push)
Dimming Methode PWM, 1.5kHz
Dimming Curve Logarithmic
ENVIRONMENT
Working Tempetrature -20°C - + 45°C
Max. Case Temperature 75°C
Working Humidity 10%-95% RH non-condensing
Storage Temperature -40°C - +80°C
Storage Humidity 10% - 95% RH
IP Rang IP20 (suitable for indoor LED lighng applicaons)
Safety & EMC
Safety Standards TUV EN61347-1, EN61347-2-13 approved
DALI Standards Comply with IEC 62386-209:2011
Withstand Voltage I/P-O/P: 3.75KVAC
Isolaon Resistance I/P-O/P: 100M Ohms / 500VDC / 25°C / 70% RH
EMC Emission EN55015, EN61000-3-2, EN61000-3-3
EMC Immunity
EN61547, EN61000-4-2,3,4,5,6,8,11, , surge immunity Line-
Line 1KV
Others
MTBF 193.6K hrs min. @ 230VAC full load and 25°C ambient tempe-
rature
Dimension 244 x 64 x 32mm
Warranty 5 years

3
Änderungen vorbehalten. Angaben ohne Gewähr. / 26.09.2019 © Simpex Electronic
Product dimension
Wiring diagram
Wiring diagram with DALI DT8
Wiring diagram with AC Push
Wiring diagram with DALI

4
Änderungen vorbehalten. Angaben ohne Gewähr. / 26.09.2019 © Simpex Electronic
Installaon
Operaon
SAFETY AND WARNINGS
• Do not install with power applied to the device
• Do not expose the device to moisture
• Do never connect two minuses (by example –R & -B) connect to the same potenal (same minus at the
module)
• Approved wire diameter: AWG16—AWG20 / 0.5mm2-1.5mm2
6-7mm isolated
Set DALI address manually via buons
1. Press and hold down any of the two buons unl numeric digital display ashes, then release the
buon.
2. 1.2. Click any of the two buons once to select a digit, click again to change the digit unl the desi-
red DALI address appears. Click rst buon to set “tens” posion and second buon to set “units”
posion. The address can be set from 00~63.
3. Then press and hold down any of the 2 buons unl the numeric digital display stops ashing to
conrm the seng.
Note: DALI address can be manually assigned from 00-63-FF, by factory defaults, no DALI address is assig-
ned for the dimmer, and the dispaly shows FF. Seng DALI address as FF will reset the dimmer to factory
defaultes
DALI address assigned by DALI masters
DALI address can also be assigned by DALI Master controller automacally, please refer to user manuals of
compable DALI Masters for specic operaons.
Note: The digital display will show AU. When the DALI master is assigning addresses.
Once an address is selected, all four channels' address will be the same. For example, if the dimmer is
addressed to 22 on the display then CH1, CH2, CH3 and CH4 will be the same address

5
Änderungen vorbehalten. Angaben ohne Gewähr. / 26.09.2019 © Simpex Electronic
Important Informaon
Drivers with PWM dimming might cause noises due to vibraon in the driver itself or resoncance frequencies of
other products.
Standard DALI preseng: 100% brightness for all 4 channels
CASE A Powersupply went to overload protecon mode
What happens ?
The strips start to blink. You are able to reduce the brightness with the soware and the strips will stop with blinking. You
can‘t controll the colors any more.
What can I do to go back to solve the problem?
A. 1. Reduce the load accoring to the specicaon.
2. Dissconnect the powersupply from AC for at least 10 min. Aer 10 min. it will go back to the factory sengs
3. You are now able to control the device again.
B 1. Dissconnect the load.
2. Dissconnect the powersupply from AC for at least 10 min. Aer 10 min. it will go back to the factory sengs
3. Connect the powersupply to AC
4. Connect the powersupply with your DALI soware.
5. Reduce Power On level and the max level. The level has to be under the max. load of the powersupply.
6. Switch the powersupply o and connect again the load.
7. You are now able to control all other parameter of the device.
Note: Simpex is just responsible for the product itself and not for consequential damages or costs. Extended
warranty requirements have to be agreed case by case. The general terms and conditions of the Simpex
Electronic AG apply (hps://www.simpex.ch/en/Imprint/) .
Table of contents
Popular Dimmer manuals by other brands

Leviton
Leviton ACI06-1L installation instructions

LEGRAND
LEGRAND MIRO MRP6 installation instructions

LightwaveRF
LightwaveRF JSJS LW250 Operation manual

Lutron Electronics
Lutron Electronics Caseta Pico PD-6WCL quick start guide

hager
hager TYA661 Series quick start guide

BEGA
BEGA 71148 Instructions for use