ISYGLT UD-700-X2 User manual

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
1
Technical Data / Instruction Manual
UD-700-X2
Article no. 80026503
Universal Dimmer

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
2
1. Notes on documentation
These instructions are intended for qualified personnel who are
familiar with the assembly, installation and operation of the ISYGLT
system. It is essential that you read these operating instructions
through before commissioning and keep them accessible for further
use.
SEEBACHER cannot accept any liability for damage or malfunctions
resulting from failure to observe these instructions.
1.1. Retention of documents
These instructions and all other applicable documents are part
of the product. They must be handed over to the device operator.
The operator will store the documents so that they can be made
available if necessary.
1.2. Symbols used
Observe the following safety and other instructions in the manual:
Handling instruction
The hand indicates that you should carry out an act.
Danger!
Immediate danger to life!
Attention!
General notes, useful information and special features
Directory of Content
1. Notes on documentation
1.1. Retention of documents
1.2. Symbols used
2. Safety instructions
2.1. Intended usage
2.2. Predictable mishandling
2.3. Safe handling
2.4. Qualification of staff
2.5. Changes to the product
2.6. Use of spare parts and additional equipment
2.7. Liability notes
3. Warranty
4. Declaration of Conformity
5. Service address
6. Maintenance / Care / Disposal
7. Storage
8. Assembly
9. Product description
10. Technical Data
10.1. Pin assignment
11. Wiring diagram

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
3
The module is designed for cabinet installation on a 35mm DIN
rail according to EN 60715 in corresponding standard housings.
Extreme environmental conditions impair the function of the pro-
duct.
• Protect module from shocks
• Use module indoors only
• Protect module from humidity
In addition to these safety instructions, you must also observe
the special safety instructions listed in the individual chapters for
the individual acts.
2.4. Qualification of staff
Assembly, commissioning, operation, maintenance, decommis-
sioning and disposal may only be carried out by qualified staff.
Work on electrical parts may only be carried out by a trained
electrician in accordance with the applicable regulations and
directives. Other activities in connection with the ISYGLT module,
such as assembly and installation of system components with
tested standard plug connections, as well as operation and con-
figuration of the ISYGLT module may only be carried out by trai-
ned staff.
2.5. Changes to the product
Unauthorized modifications to the ISYGLT module which are not
described in this or the other applicable instructions can lead to
malfunctions and are prohibited for safety reasons.
2.6. Use of spare parts and additional equipment
The module may be damaged if unsuitable spare parts and addi-
tional equipment are used. Only use original spare parts and
additional equipment from the manufacturer.
2.7. Liability notes
SEEBACHER accepts no liability or warranty whatsoever for
damage and consequential damage caused by non-compliance
with the technical regulations, instructions and recommendati-
ons. SEEBACHER shall not be liable for any costs or damage
incurred by the user or third parties as a result of the use of this
equipment, in particular improper use of the equipment, misuse
or malfunction of the connection, malfunction of the equipment
or connected devices.
SEEBACHER accepts no liability for printing errors.
2. Safety instructions
Observe the following general safety instructions when installing
and commissioning the device:
Assembly and installation of the ISYGLT module may only be carried
out by a qualified electrician. Other activities in connection with the
ISYGLT module, such as assembly and installation of system com-
ponents with tested standard plug connections, as well as operation
and configuration of the ISYGLT module may only be carried out by
trained staff.
Observe the electrical installation regulations of the country in which
the device is installed and operated as well as its national accident
prevention regulations. In addition, observe internal company regu-
lations (work, operating and safety regulations).
Before working on the ISYGLT module system, it must be
disconnected from the power supply and secured against
being switched on again. After completion of the assembly,
installation and maintenance work, an electrical check must
be carried out! Check all protective conductor connections
and the voltages at all connection plugs as well as at each
individual module slot.
2.1. Intended usage
The module is exclusively suitable for regulation (control) in con-
nection with ISYGLT system components. Any other use is not
intended. The limit values stated in the technical data must not be
exceeded under any circumstances. This applies in particular to
the permissible ambient temperature range and the permissible
IP protection type. For applications with a higher required IP pro-
tection type, the ISYGLT module must be installed in a housing
or a cabinet with a higher IP protection type.
2.2. Predictable mishandling
The module must not be used in the following cases in particular:
•explosive area
When operating in explosive areas, sparking can lead to defla-
gration, fire or explosions.
2.3. Safe handling
This module corresponds to the state of the art and the recog-
nised safety regulations. Each device is tested for function and
safety before delivery.
Only operate this module in perfect condition in accordance with
the operating instructions, the applicable regulations and directi-
ves of the country in which the device is installed and operated,
and the applicable safety and accident prevention regulations.

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
4
6. Maintenance / Care / Disposal
The product is maintenance-free. It is sufficient from time to time to
remove any dust deposits. This may only be done in a power-free
state.
Disposal (European Union)
Do not dispose of product in household waste! Products with this
symbol
7. Storage
The product must be stored in a dry place, protected from dirt and
mechanical stress. After damp or dirty storage, the product may only
be operated after a condition check by an authorised electrician.
8. Assembly
(Only by certified electrician!)
Mount the product only when it is in a power-free state!
Switch off the power supply, check that there is no voltage, secure
against being switched on again!
The device may only be operated at voltages according to the tech-
nical data and loaded with the currents defined therein. Only use
suitable equipment (system modules).
Check that there are no loose parts in the product. If this is the case
and the presence of such parts is not explicitly described, do not
install or commission the product.
Only use suitable cables and fixing screws.
Assembly site
• The product can be installed in any position in a casing to be deter-
mined by the electrician (distribution box, switch cabinet). Observe
maximum ambient temperature!
Assembly steps
(Read completely before assembly!)
• Mount the device in a suitable casing.
• Make the electrical connections according to the wiring diagram.
• Congure the DIP switches according to your requirements.
• Only after a complete connection and a visual test by a qualied
electrician, the system may be put under voltage.
Seebacher GmbH
Marktstrasse 57
83646 Bad Tölz
GERMANY
Phone: +49 (0) 80 41 / 77 77 6
Fax: +49 (0) 80 41 / 77 77 2
www.seebacher.de
info@seebacher.de
5. Service address
4. Declaration of Conformity
The valid declaration of conformity for the module can be requested
from us free of charge by stating type and article no. as follows:
By phone: +49(0)8041/77776
By fax: +49(0)8041/77772
By mail: info@seebacher.de
3. Warranty
We provide warranty within the framework of the statutory provisi-
ons. These are limited to the intended use of the module and refer
to the repair or replacement of the ISYGLT module. Please send the
device with an attached error description to our company address
given below.
must be disposed of according to the EU directive WEEE 2012/19/
EU on waste electrical and electronic equipment at the local collec-
tion points for waste electrical and electronic equipment!

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
5
9. Product description
The universal dimmer is suitable for the reliable operation of high-
voltage lamps, magnetic transformers, electronic transformers, ESL
and LED retrofit lamps. There are 2 separate dimmer outputs avai-
lable, each of which can be loaded with 700W. By configuration and
parallel connection of the outputs the dimmer can be loaded with
1x1400W. Each channel can be parameterized separately to the
corresponding load type (leading edge or trailing edge mode). The
dimmer automatically checks the connected load by carrying out a
short test after the operating voltage has been applied for the first
time to see whether the connected load can be operated with the
desired setting. The dimmer works with an internal dimming resolu-
tion of 16 bit and thus meets the highest demands. The properties
already predefined in the factory, such as dimming curves, minimum
and maximum limits, can still be changed and optimized by the user
himself. ISYGLT users can parameterize the functions as usual in
the ProgramDesigner. A free software tool is available for stand-
alone or DMX users. With this tool, the dimmer can be optimized
per parameter via USB or RS-485 data connection and internal data
such as temperatures, voltages, peak currents and power can be
displayed. In addition, an oscilloscope function is also integrated as
a new feature. This is the first time that the user has a tool for dis-
playing the current load - and this without dangerous measurements
on the mains voltage! A check of unknown illuminants - such as
new retrofit lamps - is thus possible without any additional measu-
ring equipment. All you need is the connected UD-700-X2 dimmer,
a USB cable (USB Type A to Micro B m/m) and our free software.
Inputs / Outputs
• 2 dimmer outputs 700W
• 2 control inputs 0-10V or 1-10V for „emergency operation“ or „stand-alone operation“
Design
• plastic housing black, can be snapped onto 35mm DIN rail, 6 HP
Function displays in ISYGLT operating mode
LED state Meaning
1 x LED (red) OFF No operating voltage
ON Operating voltage, no error
steady blinking Too high mains voltage (>400Vs)
3x blinking No valid ISYGLT parameters available
1 x LED (yellow)
Operating voltage /
BUS
OFF No BUS signal detected
ON BUS signal detected, own address is not detected
steady blinking BUS signal and own module address detected
2 x LED (green) OFF Output „OFF“, no error
ON Output „ON“, no error
steady blinking Overtemperature
1x blinking Overload
2x blinking Overvoltage
3x blinking Failure of communication with dimmer processor
Connections
• 1 voltage connection 230V, 45-65Hz
• 2 outputs 0-230V, max. 700W/VA each or 1x1400W/VA (both channels coupled)
• 2 control inputs 0-10V or 1-10V für „emergency operation“ or „stand-alone operation“
• 1 connection for the subnet (BUS A and B, RS-485)

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
6
Function displays in stand-alone and DMX operating mode
LED state Meaning
1 x LED (red) OFF No operating voltage
ON Operating voltage, no error
1Hz blinking Too high mains voltage (>400Vs)
1x blinking + break 1.5s Error in self-test
2x blinking + break 1.5s After the ISYGLT dialing (DIP switches) no valid ISYGLT version is recognized
3x blinking + break 1.5s No valid parameters available
1 x LED (yellow)
Operating voltage /
BUS
OFF No BUS signal detected
ON BUS is active, but communication processor is not receiving data
DMX: Data for the set address are not transmitted (telegram too short) or data format is
wrong
RS-485 test: set address or data format is wrong
1Hz blinking Communication processor receives data
2 x LED (green) OFF Output „OFF“, no error
ON Output „ON“, no error
1Hz blinking Warning/switch-off at too high temperatures:
Communication processor: 65°C / 75°C
MOSFET housing: 95°C / 105°C
1x blinking + break 1.5s Signal at overload:
1. if the max. permissible peak current (>15A) is exceeded
2. if the limit values for power loss (>8W/channel) or peak current (>10A) are reached
2x blinking + break 1.5s Signal after switch-off at voltage peaks >450V
3x blinking + break 1.5s Failure of communication with dimmer processor
DIP switches
ISYGLT BUS operating mode
1 2 3 4 5 6 7 8
O N
1 2 3 4 5 6 7 8
O N
Sample address 37
Address 0 to 127
OFF
All OFF
Mode
Address bit
0
1
2
3456
ISYGLT PC test (RS485/USB)

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
7
DIP switches
DMX-512 operating mode
DIP switches
stand-alone operating mode
12345678
O N
Sample
DMX start address 331
Address 0 to 511
Mode
Channel 1+2 coupled
Channel 1+2 seperated
C
Address bit
0
1
2
34567
8
1=1 2=0 DMX-512 8 bit
1=1 2=1 DMX-512 16 bit
1 2 3 4 5 6 7 8
O N
A
B
D
12345678
O N
Mode
U-inputs 1-10V
Channel 1+2 coupled
1-button-dimmer
Reserve
U-inputs 0-10V
Channel 1+2 separately
Analog 0(1)-10V
Reserve
1 2 3 4 5 6 7 8
O N
U-inputs 1-10V
U-inputs 0-10V
C
A
B
D
C
A
B
D
Dimming channel 1
or total
Dimming channel 2

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
8
10. Technical Data
Operating mode setting for DMX-512 and stand-alone operation with DIP switches A to D
DIP A DIP B Operating mode
OFF OFF Automatic operating mode switching, the start value is predefined with the PC program on the „General“ tab
ON OFF Trailing edge
OFF ON Leading edge
ON ON NonDim
DIP C DIP D Setting dimming characteristics such as min-max values, curves, etc. (see PC program for UD-700-X2)
OFF OFF Parameters of the 1st column („General“ in the PC program UD-700-X2)
ON OFF Parameters of the 2nd column („General“ in the PC program UD-700-X2)
OFF ON Parameters of the 3rd column („General“ in the PC program UD-700-X2)
ON ON Parameters of the 4th column (with preheating setting for ESL)
(„General“ in PC program UD-700-X2)
Type designation UD-700-X2
Article no. 80026503
Mains supply 230V / 45 to 65 Hz
Mains fuse 1 x 230V automatic or GL fuse 10A
Output 2 x 230V short-circuit proof, 10W-700W per channel
Power loss <0.5...6W (Stand-by...full load) per channel - total 12W at 2x700W load
Please ensure that the switch cabinet or housing is sufficiently ventilated!
1 (0)-10V Sink current at 1-10V = 0.54mA
Source current at hardware option 0-10V = 0.14mA at 71kOhm
Isolation voltage 3500V (ISYGLT BUS / mains)
Short-circuit protection electronic overload protection by current measurement
short-circuit cut-off within 10 milliseconds
Subnet (RS-485) max. 5.6V limitation by Z-diodes
Dimensions WxHxD 106x90x59mm REG (6 HP)
Weight 300g
Connection screw terminals 1.5mm² pluggable
Operating temperature -10°C to +45°C
-> at +50°C max. 60% connectable power
-> at +55°C max. 50% connectable power
-> +60°C max. 30% connectable power
Storage temperature -25°C to +70°C
Humidity 0-85% r.h. non-condensing
Protection type IP30
Protection class I
CE mark yes

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
9
Terminal Internal connections Meaning
GND Reference potential (Ground) for the voltage inputs (0-10V) and BUS RS-485
UE1 Control voltage input for the dimmer output LD1 (emergency function)
UE2 Control voltage input for dimmer output LD2 (emergency function)
+10V Power supply for external potentiometer(s)
Reserve
Reserve
GND Reference potential (Ground) for the voltage inputs (0-10V) and BUS RS-485
A ISYGLT subnet BUS RS-485
B ISYGLT subnet BUS RS-485
10.1. Pin assignment
Terminal Internal connections Meaning
LD1 Dimmer 1 load output 0...230V max. 700W/VA leading edge / trailing edge
LD2 Dimmer 2 load output 0...230V max. 700W/VA leading edge / trailing edge
L Mains voltage 230V (45Hz-65Hz)
N Neutral conductor
N Neutral conductor
PE Protective conductor
9-pole plug (left)
6-pole plug (right)
View

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
10
Sample views of PC program
Oscillogram of retrofit LEDs in trailing edge mode
Tab „General“ Tab „Special functions“
Custom dim curves

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
11
11. Wiring diagram
+24V
0V=
BUS-A
BUS-B
B6A
NPE
1
N
0V
0(1)-10V
0(1)-10V
N PEN PE
PE
D1
D2
Art.-Nr.:
RLC
max. 2x700VA
UD-700-X2
80026503
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
OFF
ON
ISYGLT
L
N
GND
BUS A
BUS B
LD1
LD2
N
UE1
UE2
GND
+10V
005
e.g. ISYGLT-Adr.5
low voltage magnetic transformer
low voltage electronic transformer /
dimmable ECG
high voltage halogen
Suited for
trailing or
leading edge
leading edge
trailing edge
trailing or
leading edge
trailing or
leading edge
Sample: controlled by ISYGLT 2x700W
external voltage control
e.g. emergency function
channel 1
channel 2
max. 700W max. 700W
optional:

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
12
+24V
0V=
BUS-A
BUS-B
B6A
NPE
1
N
0V
0(1)-10V
N PE
PE
D1
D2
Art.-Nr.:
RLC
max. 2x700VA
UD-700-X2
80026503
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
OFF
ON
ISYGLT
L
N
GND
BUS A
BUS B
LD1
LD2
N
UE1
UE2
GND
+10V
005
Sample: controlled by ISYGLT 1x1400W
trailing or
leading edge
Suited for
trailing or
leading edge
leading edge
trailing edge
low voltage magnetic transformer
low voltage electronic transformer /
dimmable ECG
high voltage halogen
e.g. ISYGLT-Adr.5
external voltage control
e.g. emergency function
max. 700W
optional:
channel 1

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
13
N PE
B6A
DMX+
DMX-
COM
1
5
2
4
3
DMX-IN
N PEN PE
N
261
PE
D1
D2
Art.-Nr.:
RLC
max. 2x700VA
UD-700-X2
80026503
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
OFF
ON
ISYGLT
L
N
GND
BUS A
BUS B
LD1
LD2
N
UE1
UE2
GND
+10V
trailing or
leading edge
trailing or
leading edge
low voltage magnetic transformer
low voltage electronic transformer /
dimmable ECG
high voltage halogen
Suited for
trailing or
leading edge
leading edge
trailing edge
external voltage control
e.g. emergency function
0V
0(1)-10V
0(1)-10V
Sample: controlled by DMX512 8-/16-Bit
e.g. 8 Bit DMX start adr.261
for more DIP switch options
please use the datasheet
channel 1
channel 2
max. 700W max. 700W
optional:

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
14
B6A
N PEN PE
1-10V Poti
N
1-10V Poti
NPE
1
PE
D1
D2
Art.-Nr.:
RLC
max. 2x700VA
UD-700-X2
80026503
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
OFF
ON
ISYGLT
L
N
GND
BUS A
BUS B
LD1
LD2
N
UE1
UE2
GND
+10V
DIP switches
please use the datasheet
trailing or
leading edge
trailing or
leading edge
high voltage halogen
Suited for
trailing or
leading edge
leading edge
trailing edge
low voltage magnetic
transformer
low voltage electronic
transformer /
dimmable ECG
Option 1-button dimmer
Sample: 1-10V and 1-button dimming
max. 700W max. 700W
option 1-10V potentiometer

Seebacher GmbH www.seebacher.de Phone: +49 (0) 80 41 / 77 77 6
Marktstrasse 57, 83646 Bad Tölz info@seebacher.de Fax: +49 (0) 80 41 / 77 77 2
15
B6A
N PEN PE
N
NPE
1
PE
D1
D2
Art.-Nr.:
RLC
max. 2x700VA
UD-700-X2
80026503
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
OFF
ON
ISYGLT
L
N
GND
BUS A
BUS B
LD1
LD2
N
UE1
UE2
GND
+10V
A
E
S
10kOhm
A
E
S
10kOhm
Sample: Potentiometer 10kOhm
trailing or
leading edge
trailing or
leading edge
high voltage halogen
Suited for
trailing or
leading edge
leading edge
trailing edge
low voltage magnetic
transformer
low voltage electronic
transformer /
dimmable ECG
DIP switches
please use the datasheet
max. 700W max. 700W
option potentiometer 10kOhm
Misprints and technical changes reserved.
This manual suits for next models