Skyworth SMVH09B-2A2A3NG User manual

MODEL
SMVH09B-2A2A3NG
SMVH12B-3A2A3NG
SMVH18B-4A2A3NG
SMVH24B-5A2A3NG
(Refrigerant R32)

CONTENT
1. Summary and Features .............................................................................. 1
2. Safety Precautions...................................................................................... 3
3. Specifications.............................................................................................. 5
3.1 Unit Specifications..................................................................................................... 5
3.2 Operation Characteristic Curve ............................................................................... 9
3.3 Capacity Variation Ratio According to Temperature ............................................. 9
3.4 Cooling and Heating Data Sheet in Rated Frequency ......................................... 10
3.5 Noise Curve ............................................................................................................. 10
4. Function and Control................................................................................ 11
4.1 Remote Controller Operations................................................................................ 11
4.2 Smart APP User Guide............................................................................................. 16
4.3 Description of Each Control Operation.................................................................. 22
5. Installation Manual.................................................................................... 24
5.1 Safety operation of ammable refrigerant............................................................. 24
5.2 Notices for Installation ........................................................................................... 25
5.3 Installation Dimension Diagram ............................................................................ 27
5.4 Installation Indoor Unit ........................................................................................... 28
5.5 Installation Outdoor Unit ........................................................................................ 31
5.6 Check after installation........................................................................................... 34
5.7 Test operation.......................................................................................................... 34
5.8 Configuration of connection pipe.......................................................................... 35
5.9 Pipe expanding method.......................................................................................... 36
6. Construction Views................................................................................... 37
6.1 Indoor Unit ................................................................................................................ 37
6.2 Outdoor Unit ............................................................................................................. 39
7. Exploded Views and Parts List ................................................................ 41
7.1 Indoor Unit ................................................................................................................ 41
7.2 Outdoor Unit ............................................................................................................. 49
8. Schematic Diagram................................................................................... 55
8.1 Electrical Wiring ....................................................................................................... 55
8.2 PCB Printed Diagram............................................................................................... 57

9. Troubleshooting ........................................................................................ 62
9.1 Error Code List ......................................................................................................... 62
9.2 Procedure of Troubleshooting................................................................................ 65
10. Removal Procedure ................................................................................ 82
10.1 Removal Procedure of Indoor Unit....................................................................... 82
10.2 Removal Procedure of Outdoor Unit.................................................................... 86

1
Summary and Features
1. Summary and Features
Indoor Unit
Model Product Code Indoor unit Outdoor unit Power Supply Power Supply Intake
SMVH09B-2A2A3NG KEB001Z1530 SMVH09B-2A2A3NG(I) SMVH09B-2A2A3NG(O)
220-240V~,
50Hz,1Ph Outdoor Unit
SMVH12B-3A2A3NG KEB001Z1540 SMVH12B-3A2A3NG(I) SMVH12B-3A2A3NG(O)
SMVH18B-4A2A3NG KEB001Z1550 SMVH18B-4A2A3NG(I) SMVH18B-4A2A3NG(O)
SMVH24B-5A2A3NG KEB001Z1560 SMVH24B-5A2A3NG(I) SMVH24B-5A2A3NG(O)
SMVH09B-2A2A3NG(I)
SMVH12B-3A2A3NG(I)
SMVH18B-4A2A3NG(I)
SMVH24B-5A2A3NG(I)
Remote Controller
RA1A1
Outdoor Unit
SMVH09B-2A2A3NG(O)
SMVH12B-3A2A3NG(O)

2
Summary and Features
Outdoor Unit
SMVH18B-4A2A3NG(O)
SMVH24B-5A2A3NG(O)

3
Safety Precautions
2. Safety Precautions
Installing, starting up, and servicing air conditioner can be hazardous due to system pressure, electrical components, and
equipment location, etc.Only trained, qualied installers and service personnel are allowed to install, start-up, and service this
equipment.Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be
performed by trained service personnel.When handling the equipment, observe precautions in the manual and on tags, stickers,
and labels attached to the equipment. Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth
and re extinguisher nearby when brazing.Read the instructions thoroughly and follow all warnings or cautions in literature and
attached to the unit. Consult local building codes and current editions of national as well as local electrical codes.
Recognize the following safety information:
◆ Make sure the outdoor unit is installed on a stable, level surface with no accumulation of snow, leaves, or trash beside.
◆ Make sure the ceiling/wall is strong enough to bear the weight of the unit.
◆ Make sure the noise of the outdoor unit does not disturb neighbors.
◆ Follow all the installation instructions to minimize the risk of damage from earth quakes, typhoons or strong winds.
◆ Avoid contact between refrigerant and re as it generate spoisonous gas.
◆ Apply specied refrigerant only. Never have it mixed with any other refrigerant. Never have air remain in the refrigerant line as
it may lead to rupture and other hazards.
◆ Make sure no refrigerant gas is leaking out when installation is completed.
◆ Should there be refrigerant leakage, the density of refrigerant in the air shall in no way exceed its limited value, or it may lead
to explosion.
◆ Keep your ngers and clothing away from any moving parts.
◆ Clear the site after installation. Make sure no foreign objects are left in the unit.
◆ Always ensure effective grounding for the unit.
Incorrect handling could result inpersonal injury or death. Incorrect handling may result inminor injury,or damage to product
or property.
Warning Caution
Warning Caution
All electric work must be performed by a licensed technician
according to local regulations and the instructions given in
this manual.
Before installing, modifying, or servicing system,
mainelectrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
Never supply power to the unit unless all wiring and tubing
are completed, reconnected and checked.
This system adopts highly dangerous electrical voltage.
Incorrect connection or inadequate grounding can cause
personal injury or death. Stick to the wiring diagram and all
the instructions when wiring.
Have the unit adequately grounded in accordance with local
electrical codes.
Have all wiring connected tightly. Loose connection may lead
to overheating and a possible re hazard.
All installation or repair work shall be performed by your
dealer or a specialized subcontractor as there is the risk of
re, electric shock, explosion or injury.
Never install the unit in a place where a combustible gas
might leak, or it may lead to re or explosion.
Make a proper provision against noise when the unit is
installed at a telecommunication center or hospital.
Provide an electric leak breaker when it is installed in a
watery place.
Never wash the unit with water.
Handle unit transportation with care. The unit should not be
carried by only one person if it is more than 20kg.
Never touch the heat exchanger ns with bare hands.
Never touch the compressor or refrigerant piping without
wearing glove.
Do not have the unit operate without air lter.
Should any emergency occur, stop the unit and disconnect
the power immediately.
Properly insulate any tubing running inside the room to
prevent the water from damaging the wall.

4
Safety Precautions
Please read this operating manual carefully before operating the unit.
Appliance lled with ammable gas R32.
Before use the appliance, read the owner's manual rst.
Befoer install the appliance,read the installation manual rst.
Befoer repair the appliance ,read the service manual rst.
The gures in this manual may be different with the material objects ,please refer to the material objects for reference.
To realize the function of the air conditioner unit, a special refrigerant circulates in the system.The used refrigerant is the fluoride
R32,which is specially cleaned.The refrigerant is flammable and inodorous. Furthermore,it can leads to explosion under certain
condition.But the ammability of the refrigerant is very low. It can be ignited only by re.
Compared to common refrigerants, R32 is a nonpolluting refrigerant with no harm to the ozonosphere.The influence upon the
greenhouse effect is also lower. R32 has got very good thermodynamic features which lead to a really high energy efciency. The units
therefore need a less lling.
The Refrigerant
WARNING:
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacture.Should repair
be necessary, contact your nearest authorized Service Center.
Any repairs carried out by unqualied personnel may be dangerous.
The appliance shall be stored in a room without continuously operating ignition sources.
(For example: open ames, an operating gas appliance or an operating electric heater.)
Do not pierce or burn.
Appliance shall be installed, operated and stored in a room with a oor area larger than
"X"m2(see table 1).(only applies to appliances that are not xed appliances)
Appliance lled with ammable gas R32. For repairs,strictly follow manufacturer's
instructions only.
Be aware that refrigerants not contain odour.
Read specialist’s manual.

5
Specifications
3. Specifications
3.1 Unit Specifications
Parameter Unit Value
Model -- SMVH09B-2A2A3NG SMVH12B-3A2A3NG
Product Code -- KEB001Z1530 KEB001Z1540
Power
Supply
Rated Voltage V~ 220-240 220-240
Rated Frequency Hz 50 50
Phases -- 1 1
Power Supply Mode -- outdoor outdoor
Cross-sectional Area of Power Cable Conductor mm21.0 1.0
Recommended Power Cable(Core) N 3 3
Min/Max. Voltage V 198/264 198/264
Cooling Capacity W 2600 3500
Min. Cooling Capacity W 400 550
Max. Cooling Capacity W 3300 4000
Pdesignc kW 2.6 3.5
Heating Capacity W 2800 3650
Min. Heating Capacity W 400 600
Max. Heating Capacity W 4100 5130
Pdesignh(Average) kW 2.6 3.2
Cooling Power Input W 750 1010
Min. Cooling Power Input W 150 180
Max. Cooling Power Input W 1430 1560
Heating Power Input W 745 970
Min. Heating Power Input W 180 220
Max. Heating Power Input W 1550 1800
Cooling Current A 3.6 4.8
Heating Current A 3.4 4.4
Rated Input W 1550 1800
Rated Current A 6.88 7.99
EER W/W 3.47 3.47
COP W/W 3.76 3.76
SEER -- 6.7 6.5
SCOP(Average) -- 4.0 4.0
Energy Class -- A++<Cooling>/A+<Average> A++<Cooling>/A+<Average>
Air Flow Volume (cooling SH/H/L/SL) m3/h 520/440/230/150 580/500/300/230
Dehumidifying Volume L/h 0.80 1.40
Application Area m212-18 16-24
Indoor
Unit
Indoor Unit Model -- SMVH09B-2A2A3NG(I) SMVH12B-3A2A3NG(I)
Fan Type -- Cross-ow Cross-ow
Fan Diameter Length(D×L) mm Ф97.5×579 Ф97.5×633.5
Cooling Speed (SH/H/L/SL) r/min 1300/1150/750/600 1350/1200/800/650
Heating Speed (SH/H/L/SL) r/min 1300/1150/850/800 1350/1200/900/850
Fan Motor Power Output W 18 20
Fan Motor RLA A 0.2 0.24
Fan Motor Capacitor μF 1 1.5
Evaporator Form -- Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Evaporator Pipe Diameter mm Ф5 Ф5
Evaporator Pipe Diameter inch 0.197 0.197
Evaporator Row-n Gap mm 2-1.4 2-1.4
Evaporator Coil Length (L×D×W) mm 584.4×22.8×266.7 635×22.8×306.3
Swing Motor Model -- 24BJ-A2 24BJ-A2
Swing Motor Power Output W 1.5 1.5
Fuse Current A 3.15 3.15
Set Temperature Range ℃16~31 16~31
Sound Pressure Level (cooling) dB (A) 38/34/21/19 40/35/22/20
Sound Power Level dB (A) 51/47/34/32 53/48/35/33
Dimension (W×H×D) mm 792x279x195 850x291x203
Dimension of Carton Box(W×H×D) mm 868x280x349 927x287x365
Dimension of Package(W×H×D) mm 871x290x352 930x297x368
Stacked Layers -- 7 7
Net Weight kg 9 10
Gross Weight kg 11 12

6
Specifications
The above data is subject to change without notice. Please refer to the nameplate of the unit.
Outdoor
Unit
Outdoor Unit Model -- SMVH09B-2A2A3NG(O) SMVH12B-3A2A3NG(O)
Compressor Trademark panasonic panasonic
Compressor Manufacturer --
panasonic Wanbao Appliances
Compressor(guangzhou)
CO.,LTD./panasonic
panasonic Wanbao Appliances
Compressor(guangzhou)
CO.,LTD./panasonic
Compressor Model -- 9RS092ZAB21 9RS102ZAA21
Compressor Oil -- FV50S FV50S
Compressor Type -- Rotary Rotary
Compressor LRA. A 20.2 16.5
Compressor RLA A 6.22 6.48
Compressor Power Input W 855 970
Compressor Overload Protector -- -- --
Fan Type -- Axial-ow Axial-ow
Fan Diameter mm 405 405
Fan Motor Speed rpm 880 880
Fan Motor Power Output W 30 30
Fan Motor RLA A 0.4 0.4
Fan Motor Capacitor μF / /
Outdoor Unit Air Flow Volume m3/h 1800 1800
Condenser Form -- Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Condenser Pipe Diameter mm Ф7 Ф7
Condenser Rows-n Gap mm 1-1.4 2-1.4
Condenser Coil Length (L×D×W) mm 742×19.05×506 719×38.1×506
Permissible Excessive Operating
Pressure for the Discharge Side MPa 4.3 4.3
Permissible Excessive Operating
Pressure for the Suction Side MPa 2.5 2.5
Maximum Allowable Pressure MPa 4.3 4.3
Cooling Operation Ambient
Temperature Range ℃18~52 18~52
Heating Operation Ambient
Temperature Range ℃-15~24 -15~24
Throttling Method -- Capillary Capillary
Defrosting Method -- Automatic Defrosting Automatic Defrosting
Climate Type -- T1 T1
Climate Zone -- Temperate Zone Temperate Zone
Isolation -- I I
Moisture Protection -- IP24 IP24
Sound Pressure Level dB (A) 52 53
Sound Power Level dB (A) 61 62
Dimension (W×H×D) mm 830X540X325 830X540X325
Dimension of Carton Box (W×H×D) mm 876x585x363 876x585x363
Dimension of Package(W×H×D) mm 879x605x366 879x605x366
Stacked Layers -- 5 5
Net Weight kg 29 30
Gross Weight kg 31.5 32.5
Refrigerant -- R32 R32
Refrigerant Charge kg 0.52 0.78
Connection
Pipe
Length m 5 5
Gas Additional Charge g/m 20 20
Outer Diameter of Liquid Pipe inch 1/4" 1/4"
Outer Diameter of Gas Pipe inch 3/8" 3/8"
Max Distance Height m 10 10
Max Distance Length m 20 20

7
Specifications
Parameter Unit Value
Model -- SMVH18B-4A2A3NG SMVH24B-5A2A3NG
Product Code -- KEB001Z1550 KEB001Z1560
Power
Supply
Rated Voltage V~ 220-240 220-240
Rated Frequency Hz 50 50
Phases -- 1 1
Power Supply Mode -- outdoor outdoor
Cross-sectional Area of Power Cable Conductor mm21.5 2.5
Recommended Power Cable(Core) N 3 3
Min/Max. Voltage V 198/264 198/264
Cooling Capacity W 5270 6450
Min. Cooling Capacity W 1000 1400
Max. Cooling Capacity W 6700 7000
Pdesignc kW 5.2 6.4
Heating Capacity W 5500 6600
Min. Heating Capacity W 1100 1500
Max. Heating Capacity W 6800 7900
Pdesignh(Average) kW 5 6.2
Cooling Power Input W 1540 1840
Min. Cooling Power Input W 320 380
Max. Cooling Power Input W 2460 2800
Heating Power Input W 1480 1750
Min. Heating Power Input W 350 400
Max. Heating Power Input W 2300 2500
Cooling Current A 7.0 8.9
Heating Current A 6.3 8.4
Rated Input W 2300 2500
Rated Current A 10.20 11.09
EER W/W 3.42 3.51
COP W/W 3.72 3.77
SEER -- 6.3 6.4
SCOP(Average) -- 4.0 4.0
Energy Class -- A++<Cooling>/A+<Average> A++<Cooling>/A+<Average>
Air Flow Volume (cooling SH/H/L/SL) m3/h 850/760/570/480 1090/930/670/560
Dehumidifying Volume L/h 1.80 2.40
Application Area m225-36 37-54
Indoor
Unit
Indoor Unit Model -- SMVH18B-4A2A3NG(I) SMVH24B-5A2A3NG(I)
Fan Type -- Cross-ow Cross-ow
Fan Diameter Length(D×L) mm Ф106×706 Ф108×830
Cooling Speed (SH/H/L/SL) r/min 1230/1130/900/800 1250/1100/850/750
Heating Speed (SH/H/L/SL) r/min 1350/1200/900/850 1250/1100/900/800
Fan Motor Power Output W 40 55
Fan Motor RLA A 0.36 0.47
Fan Motor Capacitor μF 2.5 2.5
Evaporator Form -- Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Evaporator Pipe Diameter mm Ф7 Ф7
Evaporator Row-n Gap mm 2-1.4 2-1.4
Evaporator Coil Length (L×D×W) mm 715×25.4×304.8 850×25.4×342.9
Swing Motor Model -- 35BJ-A1 35BJ-A1
Swing Motor Power Output W 2.5 2.5
Fuse Current A 3.15 3.15
Set Temperature Range ℃16~31 16~31
Sound Pressure Level (cooling) dB (A) 47/44/31/29 48/44/35/33
Sound Power Level dB (A) 58/55/42/40 61/57/48/46
Dimension (W×H×D) mm 972x302x224 1081x327x248
Dimension of Carton Box(W×H×D) mm 1044x304x374 1155x342x410
Dimension of Package(W×H×D) mm 1047x314x377 1158x352x413
Stacked Layers -- 7 7
Net Weight kg 13 16
Gross Weight kg 15.5 19

8
Specifications
The above data is subject to change without notice. Please refer to the nameplate of the unit.
Outdoor
Unit
Outdoor Unit Model -- SMVH18B-4A2A3NG(O) SMVH24B-5A2A3NG(O)
Compressor Trademark panasonic panasonic
Compressor Manufacturer --
panasonic Wanbao Appliances
Compressor(guangzhou)
CO.,LTD./panasonic
panasonic Wanbao Appliances
Compressor(guangzhou)
CO.,LTD./panasonic
Compressor Model -- 9RD132ZEA21 9RD160ZAA21
Compressor Oil -- FV50S FV50S
Compressor Type -- Rotary Rotary
Compressor LRA. A 23 25
Compressor RLA A 6.7 6.9
Compressor Power Input W 1260 1645
Compressor Overload Protector -- -- --
Fan Type -- Axial-ow Axial-ow
Fan Diameter mm 455 522
Fan Motor Speed rpm 850 800
Fan Motor Power Output W 55 60
Fan Motor RLA A 0.67 0.79
Fan Motor Capacitor μF / /
Outdoor Unit Air Flow Volume m3/h 2800 3300
Condenser Form -- Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Condenser Pipe Diameter mm Ф7 Ф7
Condenser Rows-n Gap mm 2-1.4 2-1.4
Condenser Coil Length (L×D×W) mm 869×38.1×572 878×38.1×660
Permissible Excessive Operating
Pressure for the Discharge Side MPa 4.3 4.3
Permissible Excessive Operating
Pressure for the Suction Side MPa 2.5 2.5
Maximum Allowable Pressure MPa 4.3 4.3
Cooling Operation Ambient Temperature
Range ℃18~52 18~52
Throttling Method -- Capillary Capillary
Defrosting Method -- Automatic Defrosting Automatic Defrosting
Climate Type -- T1 T1
Climate Zone -- Temperate Zone Temperate Zone
Isolation -- I I
Moisture Protection -- IP24 IP24
Sound Pressure Level dB (A) 55 59
Sound Power Level dB (A) 63 68
Dimension (W×H×D) mm 890x598x372 960×700×396
Dimension of Carton Box (W×H×D) mm 938x647x409 1008x742x452
Dimension of Package(W×H×D) mm 941x663x412 1011x763x455
Stacked Layers -- 4 4
Net Weight kg 40 43.5
Gross Weight kg 43 47
Refrigerant -- R32 R32
Refrigerant Charge kg 0.93 1.05
Connection
Pipe
Length m 5 5
Gas Additional Charge g/m 20 50
Outer Diameter of Liquid Pipe inch 1/4" 1/4"
Outer Diameter of Gas Pipe inch 1/2" 5/8"
Max Distance Height m 10 10
Max Distance Length m 25 25

9
Specifications
3.2 Operation Characteristic Curve
3.3 Capacity Variation Ratio According to Temperature
50
60
70
80
90
100
110
120
130
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Capacity ratio(%)
Outdoor temp. (°C)
Capacity ratio(%)
HeatingCooling
HeatingCooling
-20 -15-10 -5 0510
110
120
130
100
90
80
70
60
50
40
Outdoor temp.(°C)
50
60
70
80
90
100
110
120
130
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Capacity ratio(%)
Outdoor temp. (°C)
Capacity ratio(
%)
–15–10 –5
110
100
90
80
70
60
50
40
05
710
Conditions
Indoor:DB20°C
Indoor air flow:Super High
Pipe length:5m
Outdoor temp.(°C)
Condition
Indoor:DB27°C WB19°C
Indoor air flow:
High
Pipe length:5m
Condition
Indoor:DB27°C WB19°C
Indoor air flow:
High
Pipe length:5m
Condition
Indoor:DB20°C
Indoor air flow:
High
Pipe length:5m
Heating operation ambient temperature range is -20ºC~24ºC
Heating operation ambient temperature range is -15ºC~24ºC
Compressor Speed(rps)
Compressor Speed(rps)
Cooling
Heating
Current(A)
Current(A)
0
1
2
3
4
5
6
7
8
9
10
020406080 100 120
WB19
°C
0
1
2
3
4
5
6
7
8
020406080100
12
0
Condition
Indoor:DB 27°C
Indoor air flow: Super High
Pipe length:5m
Voltage:230V
Condition
Indoor:DB 20°C
Indoor air flow: Super High
Pipe length:5m
Voltage:230V

10
Specifications
3.4 Cooling and Heating Data Sheet in Rated Frequency
Model
Rated cooling
condition(°C) (DB/WB)
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe
temperature of heat
exchanger
Fan speed of
indoor unit Outdoor fan
mode (rpm)
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
Super High
09K,12K
27/19 35/24 0.9~1.1 12 to 14 75 to 37
880
18K 850
24K 800
T1: Inlet and outlet pipe temperature of evaporator; T2: Inlet and outlet pipe temperature of condenser;
P: Pressure of air pipe connecting indoor and outdoor units.
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.(Thermistor themometer)
(2) Connecting piping condition : 5m
Model
Rated heating
condition(°C) (DB/WB)
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe
temperature of heat
exchanger
Fan speed of
indoor unit Outdoor fan
mode (rpm)
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
Super High
09K,12K
20/- 7/6 2.2~2.4 70 to 35 2 to 4
880
18K 850
24K 800
3.5 Noise Curve
Indoor side noise when blowing Outdoor side noise when blowing
Indoor fan motor rotating speed Compressor frequency(Hz)
Noise/dB(A)
50
60
30
40
20
Low Middle High Super High
12K
09K
40
42
44
46
48
50
52
54
56
20 03045060708
090
Noise dB(A)
09&12K Cooling
09&12K Heating
Indoor side noise when blowing Outdoor side noise when blowing
Indoor fan motor rotating speed Compressor frequency(Hz)
Noise/dB(A)
50
60
30
40
20
Low Middle High Super High
24K
18K
42
44
46
48
50
52
54
56
58
20 03045060708
090
Noise dB(A)
18&24K Cooling
18&24K Heating
●09K&12K
●18K&24K

11
Function and Control
4. Function and Control
4.1 Remote Controller Operations
Turbo mode
Health function
Wi-Fi signal
Set fan speed
Child lock
Sleep mode
Up&down swing
Light
Dual-8 nixietube
Auto mode
Cooling mode
Dry mode
Fan mode
Heating mode
Clock display
Fan button
+ button
Left&right swing button
Light button
Timer off button
Timer on button
Health button
Clean button
button
I feel
Left&right swing
Up&down swing button
Turbo button Sleep button
Clock button
ECO button
I feel button
Quiet button
- button
ON/OFF button
Mode button
Quiet mode
Clean mode
ECO mode
Temp. display
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●●●●●
●
●
●
●
●
●
●
●
●
●
After connecting the power, the air conditioner will make a sound.
Power indicator is ON. After that, you can operate the air conditioner by using remote controller.
Under on status, pressing the button on the remote controller, the display will show the corresponding set function icons.
Under off status, light and clock icon will be displayed on the display of remote controller (If timer on, timer off and light functions are set, the
corresponding icons will be displayed on the display of remote controller at the same time).

12
Function and Control
ON/OFF button
Press this button can turn on or turn off the air conditioner.
MODE button
Press this button to select your required operation mode.
●
When selecting auto mode, air conditioner will operate automatically according to ex-factory
setting. Set temperature can’t be
adjusted and will not be displayed as well. Press "FAN" button can adjust fan speed. Press " " or " " button can adjust fan
blowing angle.
● After selecting cool mode, air conditioner will operate under cool mode. Press "+" or "-" button to adjust set temperature.
Press "FAN" button to adjust fan speed. Press " " or " " button to adjust fan blowing angle.
●
When selecting dry mode, the air conditioner operates at fan1, fan speed can’t be adjusted.
Press " " or " " button to adjust
fan blowing angle.
● When selecting fan mode, the air conditioner will only blow fan, no cooling and no heating. Press "FAN" button to adjust fan
speed. Press " " or " " button to adjust fan blowing angle.
● When selecting heat mode, the air conditioner operates under heat mode. Press "+" or "-" button to adjust set temperature.
Press "FAN" button to adjust fan speed. Press " " or " " button to adjust fan blowing angle. (Cooling only unit won’t receive
heat mode signal. If setting heat mode with remote controller, press "ON/OFF" button can’t start up the unit).
Note:
● For preventing cold air, after starting up heating mode, indoor unit will delay 1~5 minutes to blow air (actual delay time is depend
on indoor ambient temperature).
● Set temperature range from remote controller: 16~31°C; Fan speed: auto, fan1, fan2 , fan3 , fan4, fan5, stepless speed.
Auto Cool Dry Fan Heat
fan1 fan2 fan3
fan4fan5
stepless speed
AUTO
Note:
● When selecting " " with remote controller, it’s auto swing.
up&down swing louver
of air conditioner will swing up&down
automatically at the maximum angle.
● When selecting " , , , , " with remote controller, it's the xed position swing.
Up&down swing louver
of air
conditioner will stop at that position as shown by the icon to swing.
FAN button
Pressing this button can set fan speed circularly as: auto (AUTO), fan1( ), fan2 ( ) ,fan3 ( ) , fan4 ( ), fan5
( ), stepless speed.
Note:
● In AUTO speed, air conditioner will select proper fan speed automatically according to ambient temperature.
● Fan speed under dry mode is fan1.
● After entering the stepless speed mode, users can adjust the fan speed according to the button "+" or "-".
button
button
● Press this button the up&down swing function can be started and canceled. The remote controller defaults to static swing condition.
● Press "MODE" button and " " button at the same time when remote controller OFF to switch between simple swing and static
swing.
●
In static swing condition, pressing this button, the swing angle of up&down swing louver changes as
below:
● Press this button the left&right swing function can be started and canceled. The remote controller defaults to static swing condition.
●
Press "MODE" button and " " button at the same time at remote controller OFF to switch between simple swing and static swing.
●
In static swing condition, pressing this button, the swing angle of left&right swing louver changes
as below:
No display
No display

13
Function and Control
● Press this button to start or cancel clean function.
● It is unable to set clean function when the unit is on; if the air conditioner runs in cool or dry mode before turning off, press
"CLEAN" button and show " " then the clean function is on; press "CLEAN" button again, " " disappeared, then the clean
function is off, or running 10 mins in clean function then turn off automatically.
● In the rst power on, the clean function is off acquiescently.
● The clean function can not be set and displayed when the air conditioner is in auto, fan and heat mode before turn off.
CLEAN button
+ and - button
Press "+" or "-" button once to increase or decrease 1°C of set temperature. Holding "+" or "-" button, set temperature on remote
controller will change quickly. On releasing button after setting is nished, temperature indicator on indoor unit will change
accordingly. (Temperature can’t be adjusted under auto mode)
● When setting TIMER ON, TIMER OFF or CLOCK, press "+" or "-" button to adjust time (Refer to CLOCK, TIMER ON, TIMER
OFF buttons).
TURBO button
Press this button to turn on or turn off the TURBO function in cool,heat,fan mode.
Note:
● Press "QUIET" or "FAN" button the unit will quit this function.
● This function is no use in auto mode or dry mode.
● When selecting " " with remote controller, it’s auto swing.
left&right swing
louver of air conditioner will swing
left&right
automatically at the maximum angle.
● When selecting " , , , , , " with remote controller,it's the xed position swing.
Left&right swing
louver of air
conditioner will stop at that position as shown by the icon to swing.
● When selecting " ", it’s the circulating swing.
Left&right swing
louver of air conditioner will swing circularly according to the
angle as shown by the icon.
Note:
There is no this function for the units. If press this button, the main unit will sound, but it also runs under original status.
HEALTH button
Press this button to turn on or turn off the health function.
Note: This function is not available for some models.
SLEEP button
Press this button to turn on or turn off the SLEEP function under cool,heat ,dry mode.
Note:
● This function is off as defaulted after power on.
● It will be cleared after changing mode.
● It is no use under "FAN" mode and "AUTO" mode.
I FEEL button
Press this button to start I FEEL function and " " will be displayed on the remote controller. After this function is set, the remote
controller will send the detected ambient temperature to the indoor unit and the unit will automatically adjust the indoor temperature
according to the detected temperature. Press this button again to close I FEEL function and " " will disappear.
Note:
Please put the remote controller near user and conrm the unit can receive the remote code when this function is set. Do not put the
remote controller near the object of high temperature or low temperature in order to avoid detecting inaccurate ambient temperature.
CLOCK button
Press this button to set clock time. " "and " " icon on remote controller will blink. Press "+" or "-" button within 5s to set
clock time. Each pressing of "+" or "-" button, clock time will increase or decrease 1 hour. Press this button again, " " and "
" icon on remote controller will blink. Press "+" or "-" button within 5s to set clock time. Press this button another time, "
" and " " icon on remote controller will blink. Press "+" or "-" button within 5s to set clock time. If hold "+" or "-" button, clock
time will change quickly. Release when reaching your required time. Press "CLOCK " button to conrm the time, " " icon stops
blinking.
Note:
● Clock time adopts 24-hour mode.
● The interval between two operation can’t exceeds 5s. Otherwise, remote controller will quit setting status. Operation for TIMER
ON/TIMER OFF is the same.

14
Function and Control
TIMER ON button
This button can set the time for timer on. After pressing this button, " " icon disappears, "ON" and " " icon on remote
controller blinks. Press "+" or "- "button within 5s to set "TIMER ON" time. Each pressing of "+" or "-" button, the time will increase
or decrease 1 hour. Press this button again, "ON" and " " icon on remote controller will blink. Press "+" or "-" button within 5s
to set the time. Press this button another time, "ON" and " " icon on remote controller will blink. Press "+" or "-" button within
5s to set the time. Hold "+"
or "-" button, the time will change quickly until reaching your required time. Press "TIMER ON"
to conrm
it. The word "ON" will stop blinking. " " icon resumes displaying.
Cancel TIMER ON
Under the condition that TIMER ON is started up, press "TIMER ON" button to cancel it.
TIMER OFF button
This button can set the time for timer off. After pressing this button, " " icon disappears, "OFF" and " " icon on remote
controller blink. Press "+" or "-" button within 5s to set "TIMER OFF" time. Each pressing of "+" or "-" button,the time will increase
or decrease 1 hour. Press this button again, "OFF" and " " icon on remote controller will blink. Press "+" or "-" button within
5s to set the time. Press this button another time, "OFF" and " " icon on remote controller will blink. Press "+" or "-" button
within 5s to set the time. Hold "+" or "-" button, the time will change quickly until reaching your required time.
Press "TIMER OFF" to conrm it.The word "OFF" will stop blinking. " " icon resumes displaying.
Cancel TIMER OFF
Under the condition that TIMER OFF is started up, press "TIMER OFF" button to cancel it.
QUIET button
Press this button to turn on or turn off the QUIET function in cool,heat,auto mode.
Note:
● Press "TURBO" or "FAN" button the unit will quit this function.
● This function is no use in fan mode or dry mode.
ECO button
In cool mode, press "ECO" button and the unit will operate under ECO mode.
Note:
● Remote controller displays " ".
● Air conditioner will operate at auto speed. Set temperature can’t be adjusted.
● Under cool mode, sleep function can not work with ECO mode together at the same time.
● Change mode will exit the ECO mode.
LIGHT button
Press this button can turn off the light for indoor unit’s display. " " icon on remote controller will disappear.Press this button again
to turn on the light for indoor unit’s display. " " icon on remote controller will be displayed.
Function introduction for combination buttons
Child lock function
Press "+" and "-" simultaneously to turn on or turn off child lock function. When child lock function is on, " " icon is displayed on
remote controller. If you operate the remote controller, the " " icon will blink three times without sending signal to the unit.
Temperature display switchover function
In the off mode, press "-" and "MODE" buttons simultaneously to switch temperature display between °C and °F.
button
Press this button to turn on or turn off the SMART function, for more details, please see next page for Smart APP User Guide.

15
Function and Control
● During operation, point the remote control signal sender at the receiving window on indoor unit.
● The distance between signal sender and receiving window should be no more than 8m, and there should be no obstacles
between them.
● Signal may be interfered easily in the room where there is uorescent lamp or wireless telephone; remote controller should be
close to indoor unit during operation.
● Replace new batteries of the same model when replacement is required.
● When you don’t use remote controller for a long time, please take out the batteries.
● If the display on remote controller is fuzzy or there’s no display, please replace batteries.
NOTE:
Replacement of Batteries
1. Press the back side of remote controller marked with " ", as shown in the g,and then push out the cover of battery box
along the arrow direction.
2. Installation two 7# (AAA 1.5V) dry batteries, and make sure the position of "+" polar and "-" polar are correct.
3. Reinstall the cover of battery box.
Setting the dehumidifying mode with 30 degree after the unit is powered on within 60s.And then press "LIGHT" →"SLEEP"
→"LIGHT" →"SLEEP",it could change the memory to not memory function.The light blink and show the error code 3s.
Memory setting
Press "light" and "-" button together for 3s,It could enter or exit this function.It will show the error code when this function is on.
Display by remote controller
Press the "FAN" and "MODE" 3s at the same time in heating mode,it will enter or exit the manually defrost.Remote controller will
display "dF" 5s,and it will show the setting temperature after 5s.
Manually defrost
Repowered within 5mins, set 16 degree under cooling mode, then press the "TURBO" button 6 times within 3s, will enter this
function.
Collecting freon
In the heating mode, press "SLEEP" and "TURBO" buttons together for 3s would start or cancel the Timing defrost.
Timing defrost
The minimum cooling temperature setting
In the off mode,pressing "TEMP"and "-" button at the same time,the LCD will display the minimum cooling temperature.The
default temperature is 16°C and you can adjust the temperature with "+" or "-" from 16°C to 31°C, 3 seconds later it will return to
the standby mode.
In the off mode,pressing "TEMP" and "+" button at the same time,the LCD will display the maximum heating temperature.The
default temperature is 31°C and you can modulate the temperature with "+" or "-" from 16°C to 31°C, 3 seconds later it will
return to the standby mode.
● In heating mode, pressing "Mode" and "+" button at the same time will enter/exit the low temperature heating function.
● "LA" would be showed on the remote controller after entered into the low temperature heating funtion.
● When switching from one mode to another mode, low temperature heating function was canceled. Turn off and then turn on
air conditioner that will remain the low temperature heating function. After powered on, the low temperature heating mode was
default to off status.
● In the low temperature heating mode, "SLEEP" and "Low temperature heating" function cannot start at same time.When low
temperature heating mode has already started,
meanwhile you press the "
SLEEP
" button, the air conditioner will exit low
temperature heating
mode and enter the sleep mode. Vice versa.
Note:
1. In the low temperature heating mode, the fan speed was default to Auto and non-ajusatable.
2. In the low temperature heating mode, "TURBO" and "QUIET" can't be set. If enter the low
temperature heating mode, the turbo
and quiet function that started before will be canceled. As well as when exit the low temperature heating mode, it will not resume.
3. When exit from the low temperature heating mode, the speed and temperature will turn into the original condition before it started.
4. You can set up other function.
The maximum heating temperature setting
Low temperature heating function setting

16
Function and Control
4.2 Smart APP User Guide
4.2.1 Download the Easy Home AMS Application(Referrer to as APP hereinafter)
Search "Easy Home AMS" to download Andriod version APP from Google Play and
search "Easy Home AMS" to download IOS version APP from App Store.
4.2.2 Production Introduction
Easy Home air conditioner is functioning based on the built-in smart module SWM100 through the Wi-Fi network, that the
mobile phones or other mobile devices can be connected to the Easy Home air conditioner to monitor and control the air
conditioning status after installing the Easy Home AMS APP.
4.2.3 Parameter of Smart Module SWM100
Model SWM100
Transmitting Frequency 2.4G
Transmitting Power ≤18dBm
Power Supply 12V DC / 0.5A
Operating Temperature -10℃~70℃
Operating humidity 10%-90%RH
4.2.4 Precautions for Use
(1) Please ensure both air conditioner and mobile phone connect to the same Wi-Fi hot pot when
congure.
(2) Air conditioners can only be controlled by APP when connecting to the same routher as mobile
phone.
(3) Supported Devices:
● Android phone/tablet:(Requires Android 4.4 or later version.)
Turn on your phone →Settings → About device→Check the Android version;
● iOS (iPhone/iPad/iPod Touch): (Requires iOS7.0 or later version.)
Turn on your iPhone → Settings → General→ About → Check the current version;
(4) This APP support wireless router with WPA/WPA2 connected encryption or no
password. 5G wireless router is temporarily not supported.
4.5 Cellphone data will be generated in the use of 3G/4G network of mobile phone.
model number
Andriod version 4.4.4 KTU84P
MIUI 7.0 Stable
7.0.5.0(KXDCNCI)
Quad-core 2.3GHz
MIUI version
CPU
about phone
21:09
Available1.6GB
version 8.4.1(12H321)
20.0
MGA92ZP/A
Carrier
Model
General
21:09
4.2.5 Add Air Conditioner
(1) Please nd the operating steps and method about download APP in Chapter 1 for detail.
(2) Add Air Conditioner.
● Complete the following steps to register for Android ystem:
A. Smart Module conguration:
Connect the mobile phone with wireless router, turn on the power of the air conditioner, press " " button of the remote
controller to start the Wi-Fi conguration.
B. Press "add Air Conditioner" in the APP, chose "No/ Don’t know" if it is the rst start.
Please follow the instruction in Chapter 6, point 1 To add air conditioner, if it has been connected to Wi-Fi hotspot.
C. Follow the interface instruction, long press the " " button of the remote controller for 2 seconds, the air conditioner will enter
conguration mode if the following three phenomena appear at the same time:
◆
After long beep sound from air conditioner, and there will be another short beep sound.
◆Air conditioner will display "A2" for 3 seconds.
◆The Wi-Fi indication light will blink once every second on air conditioner panel.
TTIMER
LC
Distance ≤ 8m
Enter Home
Enter Home
Enter Home
Y
es
Does your air-conditioning has been
connected to the netword yet?
No/Don’t kno
w
21:09
Yes
No/Don’t know
Next
please lon
g
press the AC remote
control about 2 seconds toward
AC,When hear a long and a short
beep,The AC enters configuration
state.
21:09
Next

17
Function and Control
D. Waiting for APP automatically search for congure the Air conditioner.
Click to choose air conditioner on the list.
Notice:
Air conditioner hotspot name and password
can be nd at the left corner
of the indoor unit.
Hot spot Name: SkySAC _XXXX
Hot spot Password: 88888888 Refresh
Search for air conditioners
Wait for connecting...14
21:09
Refresh
S
e
ar
c
h fo
r
air con
d
i
t
ion
e
r
s
9
Q
_
9
'
)
>>>>
21
:
09
Search for air conditioners
9Q_9')>>>>
21:09
Connect
SSID:
PS
W:
21
:
09
SSID:
PSW:
Connect
Cancel
Network Connecting
Connecting...99
21:09
ZKYZ')
21:09
z
z
z
25đ
18
17
16
19
20
21
RTPM2.5Wiping
Mode SleepSwing SpeedLight
ON
đ
5TROTK
E. Choose the Wi-Fi network , type in the password and press "connect" to connect. Two beep sound from air conditioner
indicates the connection is successful. Air conditioner panel will display "A3" for 3 seconds, the APP will enter operation
interface at the same time.
The APP will remind after the connection failure. Please check the APP failure by the instruction.
Notice:
◆Support WPA/WPA2 wireless router connected encryption.
◆5G wireless router is not supported.
◆The password should limit in 8-32 characters or without password.
Cancel
Connecting Failed
21:09
Please check the network is ok
Please check air condictioners
connect to the power
TTIMER
LC
Distance ≤ 8m
Enter Home
Enter Home
Enter Home
Y
es
Does your air-conditioning has been
connected to the netword yet?
No/Don’t kno
w
21:09
Yes
No/Don’t know
Next
please lon
g
press the AC remote
control about 2 seconds toward
AC,When hear a long and a short
beep,The AC enters configuration
state.
21:09
Next
● Complete the following steps to register for iOS system:
A. Smart Module conguration:
Connect the mobile phone with wireless router, turn on the power of the air conditioner, press " " button of the remote
controller to start the Wi-Fi conguration.
B. Press "add Air Conditioner" in the APP, chose "No/ Don’t know" if it is the rst start.
Please follow the instruction in Chapter 6, point 1 To add air conditioner, if it has been connected to Wi-Fi hotspot.
C. Follow the interface instruction, long press the " " button of the remote controller for 2 seconds, Then after long beep and
short beep, hotspot SkySAC_XXXX will appear for conguration from air conditioner.
The last 4 digits of hotspot name from 0-9 number and A-F English letters composition the air conditioner will enter conguration
status.
The air conditioner will enter conguration mode if the following three phenomena appear at the same time:
◆
After long beep sound from air conditioner, and there will be another short beep sound.
◆Air conditioner will display "A2" for 3 seconds.
◆The Wi-Fi indication light will blink once every second on air conditioner panel.
This manual suits for next models
3
Table of contents
Other Skyworth Air Conditioner manuals

Skyworth
Skyworth SMVH24A-5C1A3NG User manual

Skyworth
Skyworth SDVH12M-A3NAI User manual

Skyworth
Skyworth SDVH12M-A1NBI/P User manual

Skyworth
Skyworth SUV2-H18/3CFA-N User manual

Skyworth
Skyworth SKVH09A-A3NAI User manual

Skyworth
Skyworth SMVH09D-1B1A3NA User manual

Skyworth
Skyworth SAVH12A-A1NAO User manual
Popular Air Conditioner manuals by other brands

INVENTOR
INVENTOR OMI-09 owner's manual

Mitsubishi Electric
Mitsubishi Electric MXZ-2D33VA-E1 Service manual

Panasonic
Panasonic CS-BE25TKE-1 operating instructions

Carrier
Carrier CRTWOPOS007A00 installation instructions

GE
GE ASQ12AL Dimensions and installation information

Tokyo Gas
Tokyo Gas MISTY IBD-4110ACSKJ3M manual