SMT FSC-UFC24 Instruction Manual

Technical Data Sheet FSC-UFC24
Page 1 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
Technical Data
Content
Universal Field Controller for motorized re and smoke extraction dampers.
For bus (Modbus or BACnet) or analog integration into a superior system.
Electrical Data Nominal Voltage 24 V AC / DC
Nominal Voltage Range -20%... + 20%
Dimensioning 2 VA + damper actuator (max. 24 VA)
Power Consumption 2 W + damper actuator
Connections AMP plug-in connections and quick
connections (terminals)
Communication / Modbus Protocol Modbus RTU
Medium RS-485, not electrically isolated
Transmission Formats Specied by Modbus RTU Standards
Number of Devices per Line 100 (without repeater)
Baud Rates 9’600, 19’200, 38’400, 76’800 bps
Address 1..127 (1-10 reserved for FSC-M200)
(0 reserved for broadcast)
Termination 120Ω line termination. Jumper
available on extra pin on PCB.
Position of jumper if FSC-UFC24
is last Modbus device in line see
electrical installation, page 7
Typical Response Time <200 ms
Technical Data 1
Cable Specication 4
Dimensions 5
Removing the Cover of the Housing 6
Electrical Installation 7
Power Supply 7
Modbus and BACnet Addressing 8
Conguration through Dip-Switch 9
Connection Details 10
Section (continuation) Page Section (continuation) Page
Thermoelectric Tripping Device - Connection 11
Smoke Detectors – Connections 12
Analog Application 13
Electrical Installation for Analog Application 14
Explanation of LEDs 15
Functionality of Test Button 16
Run Time Monitoring of Actuator 17
Full Auto Test Application 17
Bus Monitoring Application 18

Technical Data Sheet FSC-UFC24
Page 2 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
Communication / BACnet Protocol BACnet MS/TP
Medium RS-485, not electrically isolated
Number of Devices per Line 65 (without repeater)
Baud Rates 9’600, 19’200, 38’400, 76’800 bps
(auto detect)
Address 1..127 (0 reserved for broadcast)
Termination 120Ω line termination. Jumper
available on extra pin on PCB.
Position of jumper if FSC-UFC24
is last BACnet device in line see
electrical installation, page 7
Typical Response Time <100 ms
Device Instant Automatically assigned by physical
address, writable
Safety Protection Class III (safety extra low voltage)
Protection Degree IP42, housing of non-ammable
polycarbonate
Electromagnetic Tolerance CE in accordance with 2004/108/EC
Low Voltage Directive CE in accordance with 2006/95/EC
Mode of Operation Type 1 (EN 60730-1)
Rated Impulse Voltage 2.5 kV (EN 60730-1)
Degree of Pollution of Environment 2 (EN 60730-1)
Ambient Temperature -20° C to + 50 °C
Storage Temperature -20° C to + 80 °C
Humidity Test 95% RH, non-condensing
(EN 60730-1)
Maintenance Maintenance free
Mechanical Data Width 120 mm
(Dimensions / Weight) Length 153 mm
Height 57 mm (with bracket)
Weight ca. 415 g (with bracket)
See drawings page 5

Technical Data Sheet FSC-UFC24
Page 3 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
Installation The FSC-UFC24 is directly installed at or close to the re or smoke
extraction damper. The bracket can be pre-installed. The FSC-UFC24 can
be snapped onto the bracket any time (at the damper manufacturer or
at the job site).
Electrical Installation See details page 7.
Safety Notes The FSC-UFC24 is not allowed to be used outside the specied eld
of application, especially in aircraft or in any other airborne means of
transport.
The company buying and / or mounting the FSC-UFC24 on site bears
full responsibility for the proper functioning of the whole system. Only
authorized specialists may carry out the installation. All applicable legal
or institutional installation regulations must be complied with during
installation.
The device contains electrical and electronic components and is not
allowed to be disposed of as domestic refuse. All locally valid regulations
and requirements must be observed.
Product Features / Application The FSC-UFC24 is used together with a re or smoke extraction damper
actuator to control and monitor one re or smoke extraction damper. It
oers Modbus, BACnet or analog connection and is normally mounted at
or close to the damper. Following control modes can be chosen through
dip switch terminal:
•Fireorsmokeextractionapplication
•Busprotocols:ModbusorBACnet
Conventional: Analog output and digital input signals for conventional
application.
This digital input in the FSC-UFC24 always overrides the bus commands.
Universal System Link between re or smoke extraction damper and any
Modbus or BACnet system or analog control.
Power Supply The FSC-UFC24 needs to be powered up with 24 V AC / DC. The
FSC-UFC24 provides the power supply to the actuator and to other
connected devices (e. g. smoke detector). For more details see page
7.

Technical Data Sheet FSC-UFC24
Page 4 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
FSC-UFC24 FSC-UFC24 FSC-UFC24 FSC-UFC24
120Ω at 1 Mhz. Made of 24 # exible twisted pairs
overall foil + braid shielded and overall jacketed with a
exibel compound for indoor use.
The shield is connected in between the wires
but not connected to the FSC-UFC24.
The shield is connected to KNOWN/TESTED GROUND
at one point in one line (no matter middle or end).
Shield is not
connected
Up to 1’200 meters and max. 100 FSC-UFC24 with Modbus RTU and 65 FSC-UFC24 with BACnet MS/TP
Wires are interconnected between them and then
inserted to the terminal.
Control Conventional
The FSC-UFC24 oers the option to work without the bus
communication (Modbus / BACnet) and can be controlled in a
conventional way. There is one input to open or close the damper. The
home position is depending on the re or smoke extraction application.
It is also possible to monitor the damper position conventional through
a digital output signal.
There is one analog output to signalize the status of the FSC-UFC24 and
the actuator. This analog output can be read from any controller.
Communication Serial Communication – RS-485
Through Modbus RTU (RS-485) or BACnet MS/TP (RS-485).
Actuator Connection 3-pole AMP plug and terminal connection for standard 24 V AC/DC re
or smoke extraction actuator.
6-pole AMP plug and terminal connection for 2 internal actuator end
switches. Identication of the end position switches of the actuators.
Additional Connections Input Modules
2-pole AMP plug and 3-pole connection (terminal) for thermoelectric
tripping device. Dry contact input.
4-pole connection (terminal) for smoke detector (incl. power supply).
Dry contact input. Digital input for analog application.
Output Module
1 analog output, indicates the status of the FSC-UFC24.
120Ω at 1 Mhz. Made of 24# exible twisted pairs overall foil +
braidshielded and overall jacketed with a exible compound for indoor
use, or similar. Cable type: Belden 3105a or equivalent.
IMPORTANT: SMT takes no responsibility of the functionality of the
units/network if a dierent cable is used to the one specied here.
Cable Specication

Technical Data Sheet FSC-UFC24
Page 5 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
153 mm
57 mm
incl. bracket
120 mm
116 mm
70 mm
153 mm
130 mm
4,5 mm
diameter
100 mm
FSC-UFC24
Mounting Bracket
Dimensions

Technical Data Sheet FSC-UFC24
Page 6 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
1. Open the lid 2. Unlock the screw
3. Move the sliding cover
10 mm to the top
a
b
c
1. Open the small lid on the lower end of the housing by apping up the cover
2. Unlock the screw which is placed on the lower end in the middle
3. Move the sliding cover 10 mm to the top
4. Remove the cover
Lid for Easy Access to Dip Switch Terminals (Conguration / Addressing) and Test Button
The blue coloured dip switch terminal is for the Modbus or BACnet addressing.
The red one for the conguration.
Test button: For detailed explanation of the function of the test button see page 16.
a
b
c
Removing the Cover of the Housing

Technical Data Sheet FSC-UFC24
Page 7 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
Thermoelectric
Tripping Dev.
Connection with specified
RS-485 cable only (see page 4)
Modbus RTU or BACnet MS/TP
dip switch selectable
Main 24V AC/DC
Daisy Chain
from and to other FSC-UFC24
Analog Output
Signals the status
of the FSC-UFC24
AB
Coms
CR1 C
Power In Power Out / Damper
DAMPER OUT
Power
Close
Status
TX
RX
Open
Error
ADDRESS
CONF
Test
Button
ON
123456 8
7
4
1
1
5
3
2
2
6
R1 C
+24 -24 DI2 C DI3 C C
ON
123456 8
7
1 C 2
DI1 C AO1 C
Power to Actuator
Fire Application:
1-Open C–Common
Smoke Extr. Application:
Configuration FSC-UFC24
Modbus/BACnet addressing
1-Close C-Common 2-Open
120 Ώ
AMP Plug in
parallel
Conventional Application
Digital input for manual override
Can be selected via bus as
“Normally Open” (=standard open) or
“Normally Closed” (=standard closed)
Default = “Normally Open”
Position of line termination
120Ω if FSC-UFC24 is last
Modbus or BACnet device in line
Smoke Detector
24VDC – Power supply – max 25mA
Digital input – 24V
Can be selected via bus as
“Normally Open” or “Normally Closed”
Default = “Normally Closed” – factory
production short
Thermoelectric Tripping Device
Digital input – dry contact
Factory production – short
When contact open – damper closes
Contact open
Contact closed
S1 S2 S3
S4 S5 S6
General Information
Main Power – FSC-UFC24
The FSC-UFC24 is dual power 24V AC/DC.
The actuator has to be 24V AC and/or DC. Meaning it has to operate with the same voltage (AC or DC) as the
FSC-UFC24. There are 2 terminals for the power, in order to make the daisy chain connection for the installer
easier.
The polarity must be respected when connecting multiple FSC-UFC24 to one power source
(phase to phase, com to com)!
R1 Com
Power In Power Out
R1 Com R1 Com
Power In Power Out
R1 Com R1 Com
Power In Power Out
R1 Com R1 Com
Power In Power Out
R1 Com
Actuator
24VAC/DC
Actuator
24VAC/DC
Actuator
24VAC/DC
Actuator
24VAC/DC
24VAC/DC
Electrical Installation
Power Supply

Technical Data Sheet FSC-UFC24
Page 8 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
*Attention: If the FSC-UFC24 is used in combination with the FSC-M200 controller, Modbus
addresses 1-10 are reserved for the FSC-M200. That means that the Modbus addressing of
the FSC-UFC24 starts with Modbus address 11. Furthermore, the Baud Rate needs to be
changed to 38’400 (PIN 5 to ON).
CONF
ON
1 2 3 4 5 6 8
7
If the FSC-UFC24 is used in combination with the FSC-M60, the addressing needs to be done in consecutive
order.
ON
1 2 3 4 5 6 8
7
ADDRESS
Address Switches On Address Switches On Address Switches On Address Switches On
0* Broadcast-not in use 33 1+6 66 2+7 99 1+2+6+7
1* 1 34 2+6 67 1+2+7 100 3+6+7
2* 2 35 1+2+6 68 3+7 101 1+3+6+7
3* 1+2 36 3+6 69 1+3+7 102 2+3+6+7
4* 3 37 1+3+6 70 2+3+7 103 1+2+3+6+7
5* 1+3 38 2+3+6 71 1+2+3+7 104 4+6+7
6* 2+3 39 1+2+3+6 72 4+7 105 1+4+6+7
7* 1+2+3 40 4+6 73 1+4+7 106 2+4+6+7
8* 4 41 1+4+6 74 2+4+7 107 1+2+4+6+7
9* 1+4 42 2+4+6 75 1+2+4+7 108 3+4+6+7
10* 2+4 43 1+2+4+6 76 3+4+7 109 1+3+4+6+7
11 1+2+4 44 3+4+6 77 1+3+4+7 110 2+3+4+6+7
12 3+4 45 1+3+4+6 78 2+3+4+7 111 1+2+3+4+6+7
13 1+3+4 46 2+3+4+6 79 1+2+3+4+7 112 5+6+7
14 2+3+4 47 1+2+3+4+6 80 5+7 113 1+5+6+7
15 1+2+3+4 48 5+6 81 1+5+7 114 2+5+6+7
16 5 49 1+5+6 82 2+5+7 115 1+2+5+6+7
17 1+5 50 2+5+6 83 1+2+5+7 116 3+5+6+7
18 2+5 51 1+2+5+6 84 3+5+7 117 1+3+5+6+7
19 1+2+5 52 3+5+6 85 1+3+5+7 118 2+3+5+6+7
20 3+5 53 1+3+5+6 86 2+3+5+7 119 1+2+3+5+6+7
21 1+3+5 54 2+3+5+6 87 1+2+3+5+7 120 4+5+6+7
22 2+3+5 55 1+2+3+5+6 88 4+5+7 121 1+4+5+6+7
23 1+2+3+5 56 4+5+6 89 1+4+5+7 122 2+4+5+6+7
24 4+5 57 1+4+5+6 90 2+4+5+7 123 1+2+4+5+6+7
25 1+4+5 58 2+4+5+6 91 1+2+4+5+7 124 3+4+5+6+7
26 2+4+5 59 1+2+4+5+6 92 3+4+5+7 125 1+3+4+5+6+7
27 1+2+4+5 60 3+4+5+6 93 1+3+4+5+7 126 2+3+4+5+6+7
28 3+4+5 61 1+3+4+5+6 94 2+3+4+5+7 127 Reserved factory
defaults
29 1+3+4+5 62 2+3+4+5+6 95 1+2+3+4+5+7
30 2+3+4+5 63 1+2+3+4+5+6 96 6+7
31 1+2+3+4+5 64 7 97 1+6+7
32 6 65 1+7 98 2+6+7
Modbus and BACnet Addressing

Technical Data Sheet FSC-UFC24
Page 9 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
Information Pin 2:
If Pin 2 is changed from re to smoke extraction application or from smoke extraction to re application, the
FSC-UFC24 needs to be taken o the power supply and put back again to activate the new mode.
Information Pin 3:
When a FSC-UFC24 has been connected and operated in one bus protocol rst (Modbus or BACnet) and then
will be operated by the other (BACnet or Modbus) the factory reset functionality in the FSC-UFC24 MUST be
activated by bus communication as soon as it is connected to the other protocol (Modbus register 33, BACnet
Object List BV 19). If the FSC-UFC24 is used in connection with the FSC-M60, Pin 3 has to be on ON
(BACnet).
Information Pin 5:
If the FSC-UFC24 is used in connection with the FSC-M200, Pin 5 has to be on ON (Baud Rate 38400).
Explanation Pin 7:
• Smoke Detector Alarm “System” = The signal of the smoke detector is transferred directly to the system
and processed there.
• Smoke Detector Alarm “Actuator“ = The signal of the smoke detector is directly linked with the actuator.
In case of a smoke detector alarm the re damper connected to the same FSC-UFC24 will be closed. The
signal of the smoke detector is forwarded to the controller.
The above is only valid for the re safety application. In the smoke extraction application the signal of the
smoke detector has no direct inuence to the actuator. The signal will be forwarded to the system in any case.
Baud Rate Selection Modbus
This has to be done when choosing Modbus only.
Default Dip Switch Position
Conguration Possibilities
CONF
ON
1 2 3 4 5 6 8
7
Conguration through Dip-Switch
Pin O (Default) On
1 Bus Analog
2 Fire Application Smoke Extr. Application
3 Modbus RTU BACnet MS/TP
4 Baud Rate (O-Default)
5 Baud Rate (O-Default)
6 Not in use=O
7 Smoke Detector Alarm “System“ Smoke Detector Alarm “Actuator“
8 Not In Use=O
9600 (Default) 19200 38400 76800
4O On O On
5O O On On
Baud Rate Selection BACnet
Baud rate in BACnet is automatically detected.

Technical Data Sheet FSC-UFC24
Page 10 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
Fire Damper Actuator – Connections
Fire damper actuator (spring return). When the actuator has power it is open, when there is no power the
actuator is closed with the spring.
1 2Com
Power to Actuator
Fire Damper
Actuator
Spring Return
Open Close
CONF
ON
123456 8
7
2
1Com
Smoke Damper Actuator
Power Open and Power
Close
Power to Actuator
OpenClose
CONF
ON
123456 8
7
1 2
Com
2
1Com
Fire Damper
Smoke Damper
When the FSC-UFC24 is powered up,
the power to the actuator is on
output 'open' (pin nr 1).
On power up the CLOSE
output will be ON.
During normal operation the FSC-UFC24 in
this application ONLY, will hold the
last command on memory.
3
2
1
2
1
Open Close
Open
Close
Smoke Extraction Damper Actuator – Connections
If the actuator is powered up the smoke extraction damper is either open or closed. If the FSC-UFC24 sends
the smoke extraction damper actuator the open signal, pin OPEN is powered. If the FSC-UFC24 sends the
smoke extraction damper actuator the close signal, pin CLOSE is powered.
Fire Damper
Smoke Extraction Damper
After Connection - Power Reset:
• Fire Damper Application will always go to OPEN.
• Smoke Extraction Damper Application will hold last command on memory.
Connection Details

Technical Data Sheet FSC-UFC24
Page 11 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
Digital input volt free, normally close as default (can be changed on bus). Factory shorted.
When this input is active the damper will close and you can override from the bus.
The 2 connections, the normal quick terminals and the AMP connector are in parallel.
AMP plug 2-pole. Quick connector 3-pole.
When a thermoelectric tripping device is mounted in the 2-pole AMP plug, the factory production
mounted jumper between DI3 and C must be removed!
The above is only valid for the re safety application. No function in the smoke extraction application.
Electrical Installation Thermoelectric Tripping Device
Thermoelectric
Tripping Dev.
DI3 C C
Thermoelectric Tripping Dev.
Digital Input – Dry Contact
Factory Production – Short
When Contact Open –
Damper Close
AMP Plug in
Parallel
Thermoelectric Tripping Device - Connection

Technical Data Sheet FSC-UFC24
Page 12 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
Smoke detector connection Hekatron ORS 142
Possibility to connect one smoke detector
communication interface
FSC-UFC24
24V DC 1
2
4
5
24V DC
DI2
Com
5
6
4
3
2
1
-
+
operating voltage relay contact
The ORS 142 may only be connected to Hekatron
mainspower devices and matches the existing
bases type 143.
FSC-UFC24
24V DC X
X
X
X
6
3
6
5
6
3
6
5
6
3
6
5
24V DC
DI2
Com
External power
supply
ABAV-S3 24V
Calectro
central
unit
EVC-PY-DA
Calectro
smoke
detector
EVC-PY-DA
Calectro
smoke
detector
EVC-PY-DA
Calectro
smoke
detector
Smoke detector connection Calectro EVC-PY-DA
Multiple smoke detector connections possible with ABAV-S3 24V central unit from Calectro
Smoke Detectors – Connections

Technical Data Sheet FSC-UFC24
Page 13 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
The FSC-UFC24 has the option to work without the bus communication connected. There is one input to
open or close the damper, depending on the re or smoke extraction application. It is also possible to
monitor the damper position conventionally through a digital output signal.
The analog output, signals the status of the FSC-UFC24:
• 0V – No Power to FSC-UFC24
• 2V – Damper Open
• 4V – Damper Close
• 6V – Smoke Detector Alarm
• 8V – Thermoel. Tripping Device Alarm
• 10V – More than one Alarm Condition
During normal operation this output will signalize the position of the damper (2V, 4V).
This output can be connected in parallel between the various FSC-UFC24 in order to monitor their status.
Current output max is 5mA.
Digital input volt free, normally open as default (can be changed on bus).
The digital input allows to control the damper position through an external contact/device.
Selection of the analog settings by dip switch.
This digital input for the analog application in the FSC-UFC24 overrides always the bus commands.
Electical Installation for Conventional Application
Feedback signals from the FSC-UFC24:
Contact Open
Contact Close
S1 S2 S3
S4 S5 S6
Analog Application

Technical Data Sheet FSC-UFC24
Page 14 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
FSC-UFC24
AO.1 Com
Analog Output Layout - Example
AO.1 Com AO.1 Com
Programmable controller
with analog input Analog
Input
Smoke
Detector
AO.1 Com
Analog Ouput – Signals the Status of FSC-UFC24
0V - No Power to FSC-UFC24
2V - Damper Open
4V - Damper Close
6V - Smoke Detector Alarm
8V - Thermoel. Tripping Device Alarm
10V - More than one Alarm Condition
Thermoel. Tripping
Device
Analog
Connection
Analog
Output
FSC-UFC24 FSC-UFC24
Electrical Installation for Analog Application

Technical Data Sheet FSC-UFC24
Page 15 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
The LEDs are only visible if they are active. If not active the symbols will not appear.
Rx Tx
41 mm
61mm
Led Color Action Description
Power Green On Power is connected
Status Yellow O Bus operation
On Analog connection
Error Red Flash Interval 1 sec Actuator did not reach end switch
position within the set time
Flash Interval 2 sec Smoke detector alarm
Flash Interval 3 sec Thermoelectric tripping device alarm
Flash Interval 0.3 sec Error on 2 devices or more
Error message test report
Flash Interval 5 sec General alarm
Rx Yellow Flash Receive data
Tx Green Flash Transmit data
Close Yellow On Damper close
Open Green On Damper open
Close + Open Flashing Damper is moving
Explanation of LEDs

Technical Data Sheet FSC-UFC24
Page 16 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
Depending on the application (re or smoke extraction) the test button creates dierent test scenarios.
Fire Application:
• Power on the FSC-UFC24: actuator (damper) opening until end position is reached
• Pushing test button will interrupt the power supply to the actuator. Spring is closing the actuator
• As soon as the test button is released the power comes back to the actuator and the damper will open again
Smoke Extraction Application:
• Power on: actuator makes self-test and remains in position dened by controls
• Pushing test button changes command of the actuator – actuator (damper) runs into opposite direction
• Release test button: actuator (damper) runs back into last dened position
Functionality of Test Button

Technical Data Sheet FSC-UFC24
Page 17 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
The FSC-UFC24 is equipped with an actuator run time monitoring function. This function monitors the time
required by the actuator from leaving of the one and reaching of the other end switch. If the actuator does
not reach the other end switch in the specied time an error message is sent.
The default value for the actuator run time is 90 seconds. This can be adapted via Modbus or BACnet from
0…360 seconds.
The FSC-UFC24 oers a‘Full Auto Test’ function. This can be controlled through the Modbus or BACnet
controller.
Basis of the Functionality
Basis for this function is the run time monitoring of the actuator.
Fire Damper
To start the full auto test functionality, the corresponding bus-register hast to be activated via bus. By starting
the full auto test, the timer of the run time monitoring starts to count the time and the re damper actuator is
closing (spring) and remains in the closed position until the timer of the set running time has reached the set
time. Then the actuator will open again automatically until the end switch has been reached. The timer of the
run time monitoring starts to count again as soon as the command ‘open’ has been sent. Once the timer of
the set running time has reached the set time, the FSC-UFC24 will go back into normal operation mode and a
feedback ”full auto test ok” is activated. If one of the end switches is not reached within the dened running
time, an error message is activated.
Smoke Extraction Damper
To start the full auto test functionality, the corresponding bus-register has to be activated via bus. By starting
the full auto test, the timer of the run time monitoring starts to count the time and the smoke extraction
damper actuator is moving to the opposite direction and remains in that position until the timer of the
set running time has reached the set time. Then the actuator will automatically move back to the original
position until the end switch has been reached. The timer of the run time monitoring starts to count again as
soon as the command ‘opposite direction’has been sent. Once the timer of the set running time has reached
the set time, the FSC-UFC24 will go back into normal operation mode and a feedback ”full auto test ok” is
activated. If one of the end switches is not reached within the dened running time, an error message is
activated.
Run Time Monitoring of Actuator
Full Auto Test Application

Technical Data Sheet FSC-UFC24
Page 18 of 18 November 2017 Technical changes reserved www.smtec-ag.ch
The FSC-UFC24 is equipped with a Bus Monitoring Function. If the bus signal to the FSC-UFC24 is interrupted
the damper will move to the safety position after the dened period of time and remain there until the bus
functionality is back to normal operation.
Objects
There are 2 objects which can be activated by Modbus or BACnet:
• Logic Alarm / Bus Monitoring Function
• Logic Alarm Delay / Set Delay (time in sec)
Default settings:
Logic Alarm / Bus Monitoring Function not active
Activation (via Bus):
• Logic Alarm / Bus Monitoring Function 1 (on)
• Logic Alarm Delay is activated, default delay time is 120 sec. Option to set the delay time via bus between
30…360 sec
Functionality
Fire Damper
After the dened period of time the re damper will move to the closed position and remains closed until the
bus functionality is back to normal operation.
Smoke Extraction Damper
If the smoke extraction damper is closed:
After the dened delay the smoke extraction damper will move to the open position and remains open until
the bus functionality is back to normal operation.
If the smoke extraction damper is open:
The smoke extraction damper remains in the open position even if the bus signal is interrupted.
Systems & Modules Technology AG
Frohwiesstrasse 43
CH-8630 Rüti
Switzerland
Phone: +41 79 400 38 10
Fax: +41 55 240 66 30
Mail: info@smtec-ag.ch
Bus Monitoring Application